Home » Service & Support » Technical Documentation
District Heating Exchangers - Temperature Control Valve Selection
Release time:2026-11-28 11:55:43 | Views:

Temperature control valves of district heating exchangers regulate primary-side heat according to secondary-side demand, with self-operated thermostatic valves and pressure-independent control valves as common solutions. Based on official data sheets for SAMSON Type 43, Type 2213 and Type 42-36 E / 2488 / 2489, this article reviews the general selection dimensions of medium, temperature, pressure, material, size, flow characteristic, sealing and explosion protection; specific parameters are subject to the official catalogue, standard texts and design conditions.

I. Service Conditions and Product Positioning

ItemContent
ServicePrimary- or secondary-side temperature control of plate/shell-and-tube exchangers
MediumHot water, steam, thermal oil; water quality and temperature difference affect selection
ControlSelf-operated thermostatic (adsorption/capillary), electric, pressure-independent PICV
RepresentativeSAMSON Type 43-1/2/3/5/6/7, Type 2213, Type 42-36 E / 2488 / 2489
Main referencesSAMSON data sheets T 2171, T 2172, T 2173, T 2174, T 2175, T 2043, T 3018, T 3135

Sources: SAMSON data sheets T 2171 / T 2172 / T 2173 / T 2174 / T 2175 (Type 43), T 2043 (Type 2213), T 3018 (Type 42-36 E), T 3135 (Type 2488 / 2489).

Control valve illustration
Control valve illustration, not the actual model; parameters subject to the official catalogue

II. Heating, Cooling and Three-Way Types

TypeActionApplication
Heating (43-1 / 43-2 / 43-5 / 43-7)Closes as temperature risesPrimary-side heat supply control
Cooling (43-6)Opens as temperature risesCooling circuit control
Three-way (43-3)Mixing or divertingBypass mixing and flow-dividing control
Self-operated thermostat (2213 STM)Limit control with automatic resetLow-temperature protection and limit control

Sources: SAMSON data sheets T 2171 / T 2172 / T 2173 / T 2174 / T 2175, T 2043; action subject to official catalogue.

III. Set Points and Actuation

DimensionSelection directionCheck item
Set rangeSelect by secondary target temperatureCheck official set-point range table
SensorCapillary or remote typeCheck capillary length and allowable temperature
Electric actuationWith signal and fail-safe actionChange flow by controller signal
Pressure independencePICV offsets differential fluctuationCheck flow set-point range
StandardControl devices testable to DIN EN 14597Per official data sheet

Basis: SAMSON data sheet T 3018 (Type 42-36 E, DIN EN 14597), T 3135 (Type 2488 / 2489); T 2043 (Type 2213).

IV. Materials and Connections

PartMaterial / constructionNote
BodyEN-GJL-250, EN-GJS-400-18-LT, 1.0619, 1.4408For PN16 / 25 / 40
Seat1.4104, 1.4006, 1.4404 etc.Paired with body material
Plug Dezincification-resistant brass or stainlessWith EPDM / FKM soft seal
DiaphragmEPDM fabric reinforcedUse FKM for mineral oil
EndsFlange EN 1092-1, threaded, weldedPer official catalogue

Sources: SAMSON data sheets T 3018, T 3135, T 2171; EN 1092-1.

V. Commissioning and Maintenance

ItemPoint
Temperature setSet and verify by secondary target temperature
Flow setSet PICV to design flow
Differential checkEnsure restriction differential in effective range
CleaningProvide strainer and drain on exchanger side
Winter protectionPrevent freezing with insulation where needed

Basis: SAMSON data sheets T 3018 / T 3135 (flow set-point range and restriction differential); subject to official manual.

VI. Selection Guide and Common Configurations

StepCheck item
1 MediumHot water, steam or thermal oil
2 T & PPrimary/secondary temperature, differential and PN class
3 ControlSelf-operated, electric or pressure-independent
4 MaterialBody, seat, seal and ends
5 CommissioningSet point, flow setting and differential check

Selection guide: The sequence is: define hot-side medium and temperature difference, then control method, then materials and commissioning. Determine valve type from primary medium and secondary target temperature, decide whether pressure-independent control is needed by differential fluctuation, check body material and sealing, then complete set point and flow setting. Parameters are subject to the official catalogue, standard texts and design conditions; no project-specific values are invented.

Common models and configurations: Common configurations: SAMSON Type 43-1 / 43-2 / 43-3 / 43-5 / 43-6 / 43-7 self-operated temperature regulators (T 2171 etc.), Type 2213 STM (T 2043), Type 42-36 E (T 3018) and Type 2488 / 2489 (T 3135); specific models subject to official selection.

If you are reviewing control valve selection for a process unit, please send us the medium, temperature, pressure, size and signal requirements. We can review the selection dimensions together against the official catalogue and design conditions.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.