Control valves in the nuclear conventional island mostly belong to balance-of-plant (BOP) systems; beyond general selection dimensions, quality assurance class, seismic qualification and material traceability must be checked. Based on official data for Fisher nuclear valves and Crosby nuclear safety valves, together with ASME Section III and IEEE 344, this article gives selection points; specific parameters and documents are subject to the project specification and official QA documents.

I. Scope and Product Positioning

ItemContent
ScopeConventional island (secondary circuit): feedwater, steam, condensate, circulating water and auxiliary steam
Vs nuclear islandConventional island is mostly non-nuclear-safety BOP; QA and qualification per project specification
MediumWater, steam and condensate; some systems require high cleanliness
RepresentativeFisher easy-e D3 / D4, Baumann family; nuclear reference SS-84PSV4
Main referencesASME Section III; RCC-M; IEEE 344; Fisher manual D103416X012

Sources: Fisher SS-84PSV4 manual D103416X012; Crosby nuclear safety valve catalogue VCPBR-00999-EN; ASME Section III, RCC-M, IEEE 344.

Control valve illustration
Control valve illustration, not the actual model; parameters subject to the official catalogue

II. QA and Qualification Requirements

DimensionCheck itemNote
QA classSafety class per project specificationConventional and nuclear islands differ
SeismicQualification report such as IEEE 344Check equipment qualification documents
QA systemRequirements per 10CFR50 Appendix BFollow project QA programme
TraceabilityCMTR and NDT recordsCheck per official and project documents
Nuclear approvalN-Stamp / RCC-M etc.For nuclear-grade parts only, per certificate

Basis: ASME Section III; RCC-M; IEEE 344; 10CFR50 Appendix B; Fisher nuclear data D103416X012. Project-level documents subject to official supply.

III. Pressure, Temperature and Materials

DimensionSelection directionCheck item
Design dataPer project specificationNo invented values
Body materialCarbon or stainless steel by medium and temperaturePressure boundary per ASME B16.34
TrimHardened or stainless trimBy erosion and corrosion tendency
SealingMetal or soft seatBy leakage class and temperature
EndsFlanged or butt weldedPer ASME B16.5 / B16.25

Basis: ASME B16.34 / B16.5 / B16.25; Fisher catalogue; subject to design conditions and official catalogue.

IV. Construction and Flow Characteristics

ItemSelection point
Valve typeSingle-seat, cage or multistage by differential
CharacteristicLinear or equal percentage by control loop
Leakage classCheck per ANSI/FCI 70-2 / IEC 60534-4
NoisePredict high-differential noise per IEC 60534-8-3 and add low-noise trim
Flow directionInstall per official manual

Basis: IEC 60534-4 / 60534-8-3; ANSI/FCI 70-2; Fisher catalogue.

V. Actuator and Fail-Safe

ItemConfiguration point
ActuatorPneumatic diaphragm/piston or electric, by thrust and response
Fail-safeFail-open or fail-close per process
Partial strokePST and diagnostics for safety-related valves
Ex protectionEx ia intrinsic safety is NOT Ex d flameproof; certificate per nameplate
IsolationProvide isolation valve and bypass where maintenance isolation is needed

Sources: Fisher catalogue; Crosby catalogue VCPBR-00999-EN; approvals subject to official documents and nameplate.

VI. Selection Guide and Common Configurations

StepCheck item
1 ScopeConfirm conventional island system and QA class
2 DataDesign pressure, temperature and medium
3 ConstructionValve type, trim, characteristic and leakage class
4 QualificationSeismic, QA and traceability documents
5 ActuatorThrust, fail-safe, PST and Ex protection

Selection guide: The sequence is: define system scope and qualification, then construction parameters, then actuator and safety accessories. Determine QA class and qualification documents from the project specification, fix valve type, trim and sealing from design pressure, temperature and medium, check characteristic, leakage and noise, then verify actuator, fail-safe and Ex protection. Parameters and documents are subject to the project specification and official QA documents; no project-specific values are invented.

Common models and configurations: Common configurations: Fisher easy-e D3 / D4 with easy-Drive electric actuator, Baumann family, nuclear reference Fisher SS-84PSV4 (manual D103416X012); specific models and qualification documents subject to official supply.

If you are reviewing control valve selection for a process unit, please send us the medium, temperature, pressure, size and signal requirements. We can review the selection dimensions together against the official catalogue and design conditions.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.