Valve position analog feedback returns stem position to the DCS as a 4-20 mA signal, forming the basis for position monitoring, diagnostics and closed-loop confirmation. Based on official data for Fisher 4400 and SIPART PS2 AOM, this article covers output forms, load capability, calibration steps and common deviation handling; specific parameters are subject to the official catalogue and nameplate.

I. Product Positioning and Output Forms

ItemContent
Position feedbackConverts stem position into a 4-20 mA analog output to the DCS
ImplementationBuilt-in positioner feedback module or standalone position transmitter
Common solutionsFisher 4400/4200 digital valve position transmitters; SIPART PS2 AOM analog output module
Additional functionsMay include HART communication and solid-state limit switches
Main referencesFisher bulletin D104739X0CN; SIPART PS2 official technical data
BoundarySpecific outputs and accuracy subject to the official catalogue

Position feedback runs opposite to the command: command goes from DCS to positioner, feedback returns from positioner/transmitter to DCS.

Sources: Fisher bulletin D104739X0CN and Fisher 4200 instruction manual D200354X012; SIPART PS2 official technical data; subject to the official catalogue.

Valve position controller illustration
Valve position controller illustration, not the actual model; parameters subject to the official catalogue

II. Output Parameters and Load Capability

Model / SourceOutput signalLoad / accuracy
Fisher 44004-20 mA DCReference accuracy +/-1% (including hysteresis, linearity and deadband)
SIPART PS2 AOM 6DR4004-8J4-20 mA two-wireRB <= (UAux[V] - 12) / I[mA], UAux 12-35 V
SIPART PS2 AOM transmission error<=0.3%Temperature effect <=0.1%/10 K
ASD-5000 position transmitter4-20 mA two-wireSupply 12-30 V DC, load 0-1000 ohm (650 ohm typical at 24 V)
Masoneilan SVI1000 /PR4-20 mA position retransmitPer official catalogue

Sources: Fisher bulletin D104739X0CN; SIPART PS2 official technical data (AOM 6DR4004-8J); ASD-5000 official IOM; Masoneilan SVI1000 official catalogue.

III. Calibration Steps

StepPracticeCheck item
1 Mechanical alignmentInstall feedback lever / magnet strip correctlyFull stroke free of sticking
2 Set zeroFully closed corresponds to 4 mAPosition matches feedback
3 Set full scaleFully open corresponds to 20 mAPosition matches feedback
4 Multi-point checkCompare at 0/25/50/75/100%Linearity and error per catalogue
5 Return checkRecord ascending and descending runsHysteresis per catalogue
6 Save parametersSave and lock per official manualRetained on power loss

Calibration basis: Fisher bulletin D104739X0CN (local button calibration without tools/cams/potentiometers); SIPART PS2 official manual; specific steps subject to the official manual.

IV. DCS-Side Setup

ItemDescription
AI rangeMap 4-20 mA to 0-100% valve position
DirectionConfirm feedback direction matches valve action
AlarmsSet position deviation and failure alarms
Command comparisonFeedback-versus-command deviation used for diagnostics
HART integrationRead further diagnostics via DD/EDDL/DTM
BoundaryParameters subject to the official manual and DCS configuration

Basis: Fisher bulletin D104739X0CN (HART and 4-20 mA sharing a two-wire loop, integration with major DCS); SIPART PS2 official technical data (AOM isolated from main board).

V. Common Deviations and Handling

SymptomPossible causeAction
Zero offsetFully closed not at 4 mAReset zero and recheck mechanical position
Full-scale deviationFully open not at 20 mAReset full scale
Feedback jumpsLoop noise or poor contactCheck shield grounding and wiring
Large feedback-command deviationWrong characteristic or split-range settingCheck official parameters
Insufficient loadExternal resistance too highCalculate RB per official manual
BoundaryParameters subject to the official catalogue and nameplate

Sources: SIPART PS2 official technical data (RB <= (UAux - 12)/I); Fisher bulletin D104739X0CN; Flowserve official document FCD LGENIM0105-16 (shield grounding); subject to the official manual.

VI. Selection Guide and Common Models

Selection guide: First choose the feedback form (built-in positioner feedback module or standalone position transmitter) by system needs, then check output signal, accuracy and load capability per the official catalogue, then complete mechanical alignment, zero/full-scale and multi-point calibration, and finally set range, direction and alarms in the DCS. Parameters are subject to the official catalogue and nameplate; no values are invented.

Common models: Position feedback devices: Fisher FIELDVUE 4400 / 4200, SIPART PS2 with AOM 6DR4004-8J, ASD-5000 position transmitter, Masoneilan SVI1000 /PR; specific models subject to official selection.

If you are calibrating position feedback or matching DCS ranges, please send the feedback device model and DCS configuration. We can review the load, zero and full scale together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.