Valve position analog feedback returns stem position to the DCS as a 4-20 mA signal, forming the basis for position monitoring, diagnostics and closed-loop confirmation. Based on official data for Fisher 4400 and SIPART PS2 AOM, this article covers output forms, load capability, calibration steps and common deviation handling; specific parameters are subject to the official catalogue and nameplate. I. Product Positioning and Output Forms
Position feedback runs opposite to the command: command goes from DCS to positioner, feedback returns from positioner/transmitter to DCS. Sources: Fisher bulletin D104739X0CN and Fisher 4200 instruction manual D200354X012; SIPART PS2 official technical data; subject to the official catalogue.
II. Output Parameters and Load Capability
Sources: Fisher bulletin D104739X0CN; SIPART PS2 official technical data (AOM 6DR4004-8J); ASD-5000 official IOM; Masoneilan SVI1000 official catalogue. III. Calibration Steps
Calibration basis: Fisher bulletin D104739X0CN (local button calibration without tools/cams/potentiometers); SIPART PS2 official manual; specific steps subject to the official manual. IV. DCS-Side Setup
Basis: Fisher bulletin D104739X0CN (HART and 4-20 mA sharing a two-wire loop, integration with major DCS); SIPART PS2 official technical data (AOM isolated from main board). V. Common Deviations and Handling
Sources: SIPART PS2 official technical data (RB <= (UAux - 12)/I); Fisher bulletin D104739X0CN; Flowserve official document FCD LGENIM0105-16 (shield grounding); subject to the official manual. VI. Selection Guide and Common ModelsSelection guide: First choose the feedback form (built-in positioner feedback module or standalone position transmitter) by system needs, then check output signal, accuracy and load capability per the official catalogue, then complete mechanical alignment, zero/full-scale and multi-point calibration, and finally set range, direction and alarms in the DCS. Parameters are subject to the official catalogue and nameplate; no values are invented. Common models: Position feedback devices: Fisher FIELDVUE 4400 / 4200, SIPART PS2 with AOM 6DR4004-8J, ASD-5000 position transmitter, Masoneilan SVI1000 /PR; specific models subject to official selection. If you are calibrating position feedback or matching DCS ranges, please send the feedback device model and DCS configuration. We can review the load, zero and full scale together. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |