Valve Performance Curves & Flow Characteristic Testing Methods
Release time:2026-11-28 11:55:43 | Views:

Valve performance curves describe the relation between valve position and flow, divided into inherent and installed characteristics; testing methods cover flow coefficient determination, step/ramp tests and signature recording. Based on the IEC 60534 series and official positioner manuals, this article covers characteristic classes, curve setting, test methods and interpretation; specific values are subject to the official catalogue and standard text.

I. Characteristic Classes and Standard Basis

ClassMeaningBasis
Inherent characteristicPosition-to-flow relation at constant pressure dropIEC 60534-2-1
Installed characteristicActual relation after installation with varying pressure dropGeneral practice
LinearFlow approximately proportional to travelIEC 60534 / official catalogues
Equal percentageConstant percentage flow change per unit travelIEC 60534 / official catalogues
Quick openingFlow rises rapidly at small openingsIEC 60534 / official catalogues
Flow coefficientCv / Kv reflects flow capacityIEC 60534-2-1

The inherent characteristic is determined by the trim, while the installed characteristic also depends on system pressure-drop distribution; the two must not be confused.

Sources: IEC 60534-2-1 (flow coefficient and inherent characteristic); Fisher bulletin D100025X012 (linear, equal percentage, quick opening); values subject to the standard text and official catalogue.

Control valve illustration
Control valve illustration, not the actual model; parameters subject to the official catalogue

II. Characteristic Curve Setting

ItemDescriptionSource
POSITION_CHAR_TYPE1 linear; 2 equal percent (50:1); 3 equal percent (30:1); 4 quick open; 255 customGE Energy FVP110 official manual
Custom curve255 defined by 10 line segments with fixed endpoints (0,0)/(100,100)GE Energy FVP110 official manual
Positioner characteristicLinear/equal percentage/quick opening/custom, matched to the valveFlowserve official document FCD LGENIM0105-16
Characteristic compensationCorrects input command by a curve for nonlinear valvesFlowserve official document FCD LGENIM0105-16
BoundaryOptions depend on model and firmwareOfficial manual

Sources: GE Energy FVP110 Fieldbus Valve Positioner Manual (POSITION_CHAR_TYPE and 10-segment custom curve); Flowserve official document FCD LGENIM0105-16 (characteristic options).

III. Performance Test Methods

TestContentSource
Ramp testHysteresis, deadband, linearity, positionMasoneilan SVI1000 official catalogue
Step testOvershoot, response times T86/T63/TdMasoneilan SVI1000 official catalogue
Signature testRecord stem position, control signal and frictionFlowserve official document FCD LGENTB0520-03
Travel accumulationCumulative travel, open/close time, time near endsFisher bulletin D104739X0CN
Flow coefficient testDetermine Cv/Kv per IEC 60534-2-1IEC 60534-2-1
PreconditionComplete calibration and limit setting before testingFlowserve official document FCD LGENIM0059-09

Sources: Masoneilan SVI1000 official catalogue (ramp/step tests); Flowserve official documents FCD LGENTB0520-03 and FCD LGENIM0059-09; Fisher bulletin D104739X0CN; IEC 60534-2-1.

IV. Curve Interpretation Points

PointDescription
Consistent conditionsInherent characteristic measured under specified pressure-drop conditions
Installation effectInstalled characteristic affected by system pressure-drop distribution
Deadband effectDeadband and hysteresis shift the measured curve from the setting
Hysteresis checkRamp test distinguishes deadband from hysteresis
Response checkStep test shows overshoot and settling time
Standard firstMeasurement and calculation follow the original IEC 60534 text

Basis: IEC 60534-2-1; Masoneilan SVI1000 official catalogue (ramp/step test metrics); Flowserve official document FCD LGENTB0520-03 (signature and friction).

V. Implementation Precautions

ItemDescription
Calibrate before testingComplete travel and pressure calibration before measuring characteristics
Record conditionsLog pressure drop, medium and temperature
Curve versionSave test curves for trend comparison
Do not mix basesCv and Kv follow different standards and units
BoundarySpecific values subject to the official catalogue and standard text

Sources: IEC 60534-2-1; Flowserve official document FCD LGENIM0059-09 (calibration); specific values subject to the official catalogue and standard text.

VI. Selection Guide and Common Models

Selection guide: First clarify the inherent characteristic and Cv/Kv basis per IEC 60534-2-1, then determine the desired installed characteristic from system pressure-drop distribution, then set linear/equal percentage/quick opening or a custom curve in the positioner, and finally verify deadband, hysteresis and response time by ramp and step tests. Measurement follows the standard text and official catalogue; no values are invented.

Common models: Positioners supporting characteristic setting and testing: Fisher DVC6200, SAMSON 3730 series, Flowserve Logix 520MD+, Masoneilan SVI1000, GE FVP110; test tools per official manuals.

If you are checking the flow characteristic or test method of a valve, please send the valve type, pressure-drop conditions and positioner model. We can review the curve and test items together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.