4-20 mA Loop - Load Capability & Voltage Drop Calculation
Release time:2026-11-28 05:55:42 | Views:

The load capability of a 4-20 mA two-wire loop is determined by the supply voltage, the minimum voltage required by the field device (compliance voltage), and the resistance of wiring and barriers. This article gives the Ohm-law calculation method and examples from official manuals, covering load budget, HART and bus-powered differences, and common checks; specific parameters are subject to the official catalogue and nameplate.

I. Loop Composition and Constraints

ItemContent
Loop elementsCurrent source (DCS output card), wiring resistance, barrier resistance, positioner equivalent impedance
Basic constraintVoltage at the field device at maximum current must not fall below its minimum operating voltage
General calculationApply Ohm law U = I x R section by section
Typical minimum voltageVaries widely by model: roughly 6.8 V to 10 V at 20 mA
Current rangeCommon operation 3.8-24 mA; startup current must meet model requirements
Main referenceIEC 60381-1 (4-20 mA analog signal); specific values subject to the official catalogue

The purpose of the load check is to ensure the field device still has enough operating voltage at the worst-case current point (normally 20 mA).

Sources: Flowserve official document FCD LGENIM0105-16 (Compliance Voltage section); IEC 60381-1.

Instrumentation illustration
Instrumentation illustration, not the actual model; parameters subject to the official catalogue

II. Voltage Drop Calculation Method

StepFormula / PracticeNote
1 Set maximum currentImax = 20 mAAt loop full scale
2 Calculate available voltageAvailable voltage = controller voltage at Imax - Imax x (Rbarrier + Rwire)Flowserve document FCD LGENIM0105-16, Equation 1
3 Compare with minimumLoop is acceptable if available voltage exceeds device minimumOtherwise raise supply or reduce resistance
4 Check device dropDevice drop = Imax x device equivalent resistanceResistance varies by model, roughly 340-500 ohm at 20 mA
5 Reserve marginAllow for aging, temperature rise and supply variationSubject to the official manual

Calculation basis: Flowserve official document FCD LGENIM0105-16, Equation 1 (Available Voltage = Controller Voltage - Currentmax x (Rbarrier + Rwire)).

III. Official Examples and Equivalent Resistance

Model / SourceMinimum voltage or dropEquivalent resistance
Flowserve Logix 500+Requires 10 V at 20 mAAbout 500 ohm
Official worked example19 V - 0.020 x (300+25) = 12.5 V > 10 VAcceptable, about 2.5 V margin
Flowserve Logix 3200IQ10.0 V at 20 mA495 ohm at 20 mA (add about 20 ohm when HART is active)
ASD-5000 standard6.8 V at 20 mA340 ohm
ASD-5000 HART with advanced diagnostics9.5 V at 20 mA475 ohm

Sources: Flowserve official documents FCD LGENIM0105-16 and Logix 3200IQ IOM; ASD-5000 official IOM. Examples are under official manual conditions and are not general values.

IV. Cable, Barriers and HART

ItemRequirementBasis
Barrier compatibilityIS barrier must be HART compatible or communication may be blockedFlowserve document FCD LGENIM0105-16
Cable capacitanceExcessive network capacitance requires limiting cable lengthFlowserve document FCD LGENIM0105-16, Equations 2/3
Shield groundingGround shield at one end, normally at the signal sourceFlowserve document FCD LGENIM0105-16
Conductor sizeUse larger conductor for long runs to control resistanceFlowserve document FCD LGENIM0105-16
Bus powerPROFIBUS PA / FF powered by the bus at 9-32 VSAMSON 3730-4 official catalogue

Sources: Flowserve official document FCD LGENIM0105-16 (cable capacitance and shield grounding); SAMSON official data sheet T 8384-4 EN (3730-4 bus power).

V. Common Check List

Check itemCriterion
Supply voltageProvides enough voltage at Imax (per device minimum)
Total loop resistanceSum of wiring and barrier resistance within drop budget
Startup currentNot below model requirement (commonly 3.6-3.8 mA)
HART compatibilityBarrier and output card support HART superposition
PolarityWire per official manual, avoid reversal
MarginReserve margin for maintenance and aging

Sources: Flowserve official documents FCD LGENIM0105-16 and Logix 3200IQ IOM; minimum voltage and resistance subject to the corresponding official catalogue.

VI. Selection Guide and Common Models

Selection guide: First determine the voltage budget from the field device minimum operating voltage, then total the wiring and barrier resistance and calculate the available voltage at 20 mA, then check startup current and HART compatibility, and finally reserve margin. Examples are taken from official manuals; no general vendor values are assumed.

Common models: Current output cards, intrinsic safety barriers and 4-20 mA smart positioners (e.g. Fisher DVC6200, SAMSON 3730-3, Flowserve Logix 520MD+); specific load parameters subject to the official catalogue.

If you are checking the load capability of a 4-20 mA loop, please send the supply voltage, cable length and device model. We can work through the voltage drop and margin together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.