Valve Positioners - Stroking Time Setting
Release time:2026-11-28 05:55:42 | Views:

Stroking time is the time a valve takes to move from fully closed to fully open or the reverse; it is a key dynamic parameter in positioner tuning and safety function verification. The Flowserve 520MD+ records open/close stroke times during Quick-Cal and offers minimum open/close time as a speed limit. Based on official manuals, this article covers definitions, setting methods, influencing factors and verification; specific values are subject to the official catalogue.

I. Product Positioning and Terms

ItemContent
Parameter nameStroking time / valve action time
Open stroke timeFastest time from 0% to 100% (measured in Quick-Cal)
Close stroke timeFastest time from 100% to 0% (measured in Quick-Cal)
Minimum open/close timeSpeed limit; default 0 means fastest possible action
Related metricsT63 / T86, overshoot, deadband, actuator leakage
Main documentsFlowserve official document FCD LGENIM0105-16; SAMSON official data sheets T 8384-3/4/5 EN

Sources: Flowserve official document FCD LGENIM0105-16 (Chapter 28 on stroking time and speed limits); definitions subject to the original manual.

Digital positioner illustration
Digital positioner illustration, not the actual model; parameters subject to the official catalogue

II. Setting Method and Official Example

StepPracticeExample / Note
1 CalibrationRun Quick-Cal and record fastest open/close stroke timesFlowserve official document FCD LGENIM0105-16
2 Set limitSet minimum open/close time per process sensitivityDefault 0 seconds means fastest action
3 Scale small movesConvert small movements proportionallyWith 20 s full stroke, 40% to 50% takes about 2 s
4 Direction settingChoose independent gains per direction or conservative single gainDual is the default
5 RecheckStep test to confirm no abnormal overshoot or oscillationSubject to field testing

Source: Flowserve official document FCD LGENIM0105-16 (example: with 20 s full stroke, 40% to 50% takes about 2 s; default 0 s).

III. Influencing Factors

FactorEffectNote
Actuator sizeLarger air volume means longer fill/vent timeOfficial manual response-time note
Supply pressurePressure affects flow and action speedSubject to official catalogue supply range
Tubing and boosterSmall tubing or a booster changes responseFlowserve document FCD LGENIM0105-16
FrictionStem friction affects start and seatingAssessed by step test
TemperatureLow temperature slows responseFlowserve safety manual gives low-temperature examples
Starting position and directionOpen and close times may differOfficial manual records open/close times separately

Source: Flowserve official document FCD LGENIM0105-16 (response-time factors: actuator size, booster, stroke, starting position, tubing, supply pressure and temperature).

IV. Link to Safety Functions

ItemDescriptionSource
Fail-safe response timeTime to safe position on loss of power must meet the applicationFlowserve official safety manual
Typical exampleSpool relay about 0.06 s near 22 degCFlowserve document FCD LGENIM0105-16
Whole-valve movement50% to 0% about 0.22 s (specific test conditions)Flowserve document FCD LGENIM0105-16
Partial stroke testPST can serve as a diagnostic in a SIL-rated logic solverFlowserve official safety manual
Lifetime limitFMEDA reliability data valid for about 10 yearsFlowserve official safety manual

Source: Flowserve official document FCD LGENIM0105-16 safety chapter (Chapter 35); examples are under specific test conditions and are not general values, subject to the official manual.

V. Setting Precautions

ItemDescription
Faster is not always betterExcessive speed may cause water hammer or actuator oscillation; set by process sensitivity
Set limits after calibrationComplete Quick-Cal before setting speed limits
Keep diagnostic recordsStroking times are stored in the positioner and viewable via panel or DTM
Coordinate with loop tuningRecheck loop stability after changing stroking time
Values subject to official dataExamples here are not general values for specific models

Source: Flowserve official document FCD LGENIM0105-16; setting ranges subject to the corresponding official manual.

VI. Selection Guide and Common Models

Selection guide: First decide whether a minimum stroking time limit is needed based on process sensitivity to rapid flow/pressure changes, then run Quick-Cal and record actual open/close times, then set speed limits while maintaining stability, and finally review together with the fail-safe response time of the safety function. Stroking time varies with actuator and service; no model-specific values are assumed.

Common models: Smart positioners supporting stroking-time tuning and speed limits: Flowserve Logix 520MD+/510+, SAMSON 3730 series, Fisher DVC6200, Masoneilan SVI1000; specific parameters subject to the official catalogue.

If you are setting the stroking time of a valve or reviewing fail-safe response, please send the model, actuator and process sensitivity. We can review the settings and verification method together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.