Fisher Positioners - Single vs Double-Acting Configuration & Air Switching
Release time:2026-11-27 23:56:05 | Views:

The difference between single-acting and double-acting configuration in Fisher positioners lies in the pneumatic relay and output air circuit: single-acting pairs with a spring-return actuator, while double-acting pairs with a double-acting piston actuator. A wrong configuration prevents normal travel or gives an incorrect fail position. This article organizes acting-form codes, air connections and switching checks according to official ordering data. Relays and ports are subject to the official catalogue and nameplate.

I. Product Positioning

ItemDescription
Brand and ownershipFisher (a brand of Emerson)
SubjectFisher FIELDVUE DVC6200 / DVC7K digital valve controllers
Acting formsDouble-acting, single-acting forward, single-acting reverse
Relay mappingRelay A = double-acting; Relay B = single-acting reverse; Relay C = single-acting forward
Output span0.4-9.5 bar, up to full supply pressure
Supply limitMaximum 10.0 bar (145 psig) or actuator rating, whichever is lower
Key documentsEmerson/Fisher bulletins D104363X0CN, D104765X012

Reference: Emerson/Fisher product bulletins D104363X0CN and D104765X012 (DVC7K Product Bulletin). Acting-form codes are subject to the latest ordering matrix.

Fisher positioner single/double acting reference
Appearance reference only, not the actual model; parameters subject to the official catalogue.

II. Acting-Form Code Cross-Reference

Acting formRelayOrdering code (DVC7K example)Description
Double-actingRelay A8ATwo output ports alternately supply/vent air, for double-acting piston actuator
Single-acting reverseRelay B8BSingle output with spring return, fail action follows spring direction
Single-acting forwardRelay C8CSingle output with spring return, opposite direction to 8B
Single-acting forwardRelay A8DRelay A used for single-acting forward
Double-acting low bleedRelay A Low Bleed8ELow-bleed version reducing steady air consumption
Single-acting low bleedRelay B/C Low Bleed8F/8G/8HSubdivided by reverse/forward and relay type

The DVC6200 ordering code field 5 likewise defines pneumatic action: 5A single-acting forward (Relay C), 5B single-acting reverse (Relay B), 5C double-acting (Relay A). DVC7K and DVC6200 use different code lengths; their digit tables must not be interchanged.

Reference: Emerson/Fisher bulletins D104363X0CN (DVC6200 field 5: 5A/5B/5C) and D104765X012 (DVC7K field 8: 8A-8H).

III. Air Connections and Switching

PointSingle-acting configurationDouble-acting configuration
ActuatorDiaphragm or single piston + return springDouble-acting piston actuator, alternately supplied on both sides
Output portsOne output used, the other plugged per manualTwo outputs connected to both sides of the cylinder
Fail actionDetermined by spring directionRequires a lock-up valve or air reservoir for fail-safe/hold
Air supplyClean dry air or natural gas per ISA 7.0.01Same; air volume sized to actuator displacement
SwitchingReplace relay and reconfigure to matchReplace relay and reconfigure to match
VerificationCheck spring chamber vent is clearCheck both output connections to avoid reversal

Air-circuit switching requires both actions: replace the corresponding relay and set the acting form in configuration to match. Changing configuration without changing the relay, or the reverse, will make output direction disagree with the setpoint signal.

Reference: Emerson/Fisher bulletins D104363X0CN and D104765X012; air quality per ISA 7.0.01 and ISO 8573-1, air circuit subject to the official manual.

IV. Air Consumption and Output Capability

ItemStandard relayLow-bleed relay
Steady consumption at 1.4 bar<0.38 Nm3/haverage 0.056 Nm3/h
Steady consumption at 5.5 bar<1.3 Nm3/haverage 0.184 Nm3/h
Max output at 1.4 bar10.0 Nm3/hSubject to the official catalogue
Max output at 5.5 bar29.5 Nm3/hSubject to the official catalogue
ApplicationGeneral serviceLimited air supply or reduced consumption
NoteLow-bleed options are specified in the ordering code and are not freely interchangeable on site

Reference: Emerson/Fisher manual D103409X012 (DVC6200 consumption and output) and bulletin D104363X0CN. Specific values are subject to the official catalogue.

V. Switching Verification Checklist

Check itemDescription
Actuator formFirst confirm spring return or double-acting piston
Relay typeA/B/C and standard or low bleed match the ordering code
Configuration directionWhether stem extends or retracts as the signal increases
Output port pluggingPlug unused output per manual; no leakage allowed
Fail-safe positionSingle-acting follows spring; double-acting depends on hold-up configuration
Travel calibrationReperform travel calibration and end-point confirmation after switching

Reference: Emerson/Fisher bulletins D104363X0CN and D104765X012; acting direction and fail position are subject to the official manual and nameplate.

VI. Selection Guide and Common Models

Selection guide: Decide single- or double-acting from the actuator form first, then choose Relay B or C (single-acting) or Relay A (double-acting) by the required direction, then determine whether a low-bleed option is needed, and finally verify supply pressure, output connections and fail-safe position. Re-calibrate travel after switching configuration. Unconfirmed items are subject to the official catalogue, ordering code or nameplate.

Common models: DVC6200 (pneumatic action codes 5A/5B/5C), DVC7K (pneumatic action codes 8A-8H), DVC6200 SIS (standard low-bleed relay). Related DVC6205/DVC6215 are feedback units and do not change the acting-form code. Ordering codes are subject to the official catalogue.

If you are confirming single/double-acting configuration or air switching, please share the actuator form, acting direction and air supply conditions. We can review the relay and air circuit configuration together against the official ordering code.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.