The difference between single-acting and double-acting configuration in Fisher positioners lies in the pneumatic relay and output air circuit: single-acting pairs with a spring-return actuator, while double-acting pairs with a double-acting piston actuator. A wrong configuration prevents normal travel or gives an incorrect fail position. This article organizes acting-form codes, air connections and switching checks according to official ordering data. Relays and ports are subject to the official catalogue and nameplate. I. Product Positioning
Reference: Emerson/Fisher product bulletins D104363X0CN and D104765X012 (DVC7K Product Bulletin). Acting-form codes are subject to the latest ordering matrix.
II. Acting-Form Code Cross-Reference
The DVC6200 ordering code field 5 likewise defines pneumatic action: 5A single-acting forward (Relay C), 5B single-acting reverse (Relay B), 5C double-acting (Relay A). DVC7K and DVC6200 use different code lengths; their digit tables must not be interchanged. Reference: Emerson/Fisher bulletins D104363X0CN (DVC6200 field 5: 5A/5B/5C) and D104765X012 (DVC7K field 8: 8A-8H). III. Air Connections and Switching
Air-circuit switching requires both actions: replace the corresponding relay and set the acting form in configuration to match. Changing configuration without changing the relay, or the reverse, will make output direction disagree with the setpoint signal. Reference: Emerson/Fisher bulletins D104363X0CN and D104765X012; air quality per ISA 7.0.01 and ISO 8573-1, air circuit subject to the official manual. IV. Air Consumption and Output Capability
Reference: Emerson/Fisher manual D103409X012 (DVC6200 consumption and output) and bulletin D104363X0CN. Specific values are subject to the official catalogue. V. Switching Verification Checklist
Reference: Emerson/Fisher bulletins D104363X0CN and D104765X012; acting direction and fail position are subject to the official manual and nameplate. VI. Selection Guide and Common ModelsSelection guide: Decide single- or double-acting from the actuator form first, then choose Relay B or C (single-acting) or Relay A (double-acting) by the required direction, then determine whether a low-bleed option is needed, and finally verify supply pressure, output connections and fail-safe position. Re-calibrate travel after switching configuration. Unconfirmed items are subject to the official catalogue, ordering code or nameplate. Common models: DVC6200 (pneumatic action codes 5A/5B/5C), DVC7K (pneumatic action codes 8A-8H), DVC6200 SIS (standard low-bleed relay). Related DVC6205/DVC6215 are feedback units and do not change the acting-form code. Ordering codes are subject to the official catalogue. If you are confirming single/double-acting configuration or air switching, please share the actuator form, acting direction and air supply conditions. We can review the relay and air circuit configuration together against the official ordering code. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||