Home » Service & Support » Technical Documentation
Three-Way Control Valves (Flow-Combining / Flow-Dividing) - Structure & Selectio
Release time:2026-11-27 17:54:05 | Views:

Three-way control valves combine a common port with two branch ports to provide flow combining (mixing / converging) or flow dividing (diverting). Typical duties include heat-exchanger bypass, hot and cold stream mixing and flow splitting. Combining and diverting valves are not interchangeable: port flow direction, plug throttling surfaces and differential-pressure handling differ. This article outlines the general structure, the combining-versus-dividing differences and the selection dimensions. Specific sizes, pressure limits and materials are subject to the manufacturer's data sheet and nameplate.

I. Product Positioning

ItemDescription
Valve typeThree-way flow-combining (mixing / converging) and flow-dividing (diverting) valves
Port definitionCommon port C, upper port U, lower port L. Combining: U + L in, C out. Diverting: C in, U and L out
Representative seriesSAMSON Type 3253 / 3244; Emerson Fisher YD / YS / Baumann 24003
TrimBalanced plug, dual plug with stem guiding, or cage-guided construction
Flow characteristicPrimarily linear; refer to the data sheet for the exact characteristic
Leakage classMetal seat per IEC 60534-4 and ANSI/FCI 70-2
Key documentsSAMSON u T 8055 / u T 8056; Fisher D100031X012 / D100425X012

Reference: SAMSON data sheets u T 8055 / u T 8056 and instruction manual EB 8051; Emerson/Fisher catalogues D100031X012 and D100425X012; leakage classes per IEC 60534-4 and ANSI/FCI 70-2.

Three-way control valve structure reference
Appearance reference only, not the actual model (not the actual three-way valve); parameters subject to the official catalogue.

II. Structure and Operating Principle

ElementDescription
Valve bodyOne-piece cast three-way body reducing external leak paths; grey cast iron, WCC, WC9 and CF8M options
Plug and seatsTwo seats work with the plug. In diverting service the plug travel sets the split between outlets; in combining service the two inlets throttle in opposite directions
GuidingCage guiding, top-and-bottom guiding or stem guiding for stability over the full travel
Pressure balanceA balanced plug offsets most unbalanced fluid force, reducing actuator thrust
ActuatorLinear diaphragm or electric actuator sized by the actual differential pressure and thrust
Temperature and pressureVary with body material and bonnet type. Typical standard range minus 10 to plus 220 degrees Celsius (SAMSON 3253); subject to the data sheet

Throttling in a three-way valve involves two seats at the same time, so the plug must keep both throttling surfaces coordinated throughout travel. A one-piece body can accommodate two trim designs and share bonnets, gaskets and packing with the same series, reducing spare-part variety. However, combining and diverting plugs are arranged differently and the function cannot be swapped simply by changing pipe connections.

Reference: SAMSON data sheets u T 8055 / u T 8056; Emerson/Fisher catalogues D100031X012 and D100425X012. Temperature and pressure figures are catalogue examples only; subject to the official catalogue and nameplate.

III. Combining versus Diverting

ItemCombining (mixing)Diverting
Flow directionU and L in, C outC in, U and L out
Process functionHot and cold stream mixing, heat-exchanger bypass mixingFlow splitting, bypass switching and diverting control
Throttling surfacesTwo inlets throttle in opposite directionsTwo outlets throttle in opposite directions
Flow splitDetermined by inlet differential pressures and plug positionDetermined by plug travel
Pressure checkCheck dynamic differential pressure at common and branch ports separatelyCheck dynamic differential pressure at common and branch ports separately
InterchangeabilityFixed by plug arrangement, not convertible in the fieldFixed by plug arrangement, not convertible in the field

For the Baumann 24003, diverting service feeds medium through port C and out through U and L; combining service feeds through U and L and out through C. Differential pressure must be checked separately against the dynamic and static limits for the common and test ports given in the official catalogue. Operation beyond those limits is not permitted.

Reference: Emerson/Fisher catalogues D100031X012 and D100425X012 and Fisher three-way and multiport valve documentation. Pressure limits subject to the official catalogue.

IV. Service Matching and Selection Dimensions

DimensionCheck itemsNotes
Medium and temperatureMixing temperature difference, fouling and solidsFor high temperature, select high-temperature packing or an insulating section per the data sheet
Size and pressureNominal size and PN / Class ratingSAMSON 3253 example: DN15 to DN200, PN16 to PN160 / Class150 to Class900; verify the range for the chosen material
Body materialGrey cast iron, cast steel, cast stainless steelSelect by corrosiveness and temperature-pressure rating
Leakage classMetal-seat classVerify against IEC 60534-4 / ANSI/FCI 70-2 and process requirements
ActuatorUnbalanced force and thrust estimationA balanced plug needs less thrust, but verification against differential pressure is still required with margin
InstallationFlow direction and plug arrangementCombining and diverting plugs are not interchangeable; check the nameplate and flow arrow before installation

Reference: SAMSON data sheets u T 8055 / u T 8056; Emerson/Fisher catalogue D100031X012. Flanges per ASME B16.5 or EN 1092-1; subject to the purchase order and official catalogue.

V. Selection Guide and Common Models

Selection guide: Select three-way valves in the order function, then plug, then material and differential pressure. First decide whether the duty is mixing or splitting, then confirm the plug arrangement and flow direction in the official catalogue. Next check size, pressure class, body material and leakage class, and finally size the actuator from the unbalanced force. Items that cannot be confirmed in official documentation should be marked "subject to the official catalogue / nameplate" or "please confirm" rather than assumed.

Common models: SAMSON Type 3253 and Type 3244; Emerson Fisher YD, YS and Baumann 24003. These are public product series examples; ordering codes, sizes and pressure limits are subject to the official catalogue and nameplate.

If you are selecting a three-way valve for mixing or splitting duty, please share the medium, temperature difference, pressure and required port flow direction. We can review the plug arrangement and model together against the official catalogue.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.