Honeywell Elster 372 Pilot-operated Gas Regulator DN25-150
1. Product Overview
The Honeywell HON 372 is a pilot-operated gas regulator, the pilot version of the HON 370, and can be fitted with an integrated safety shut-off valve. It is used at gas transmission reduction stations and for commercial and industrial users.
Official literature lists DN25, 50, 80, 100 and 150 with PN16 and ANSI 150 flanges and a maximum inlet pressure of 20 bar. The outlet and set range spans 0.01 to 15 bar, with accuracy class AC1 to AC10 by outlet band, shut-off class SG5 or SG10 and shut-off zone SZ2.5. Pilots offered include the HON 610, HON 650 and BD-600, and an integrated straight-through SSV can be supplied.
This page is a selection overview. Where official sources give different inlet pressure figures, both are shown side by side; final data are per the official datasheet and refer to the official datasheet; verify with the manufacturer.



2. Technical Description
Design: Globe pilot-operated regulator with modular functional units and an optional integrated shut-off valve.
Size range: DN25, 50, 80, 100 and 150.
Connections: PN16 and ANSI 150; DIN flange PN16 or ANSI Class 150 (ANSI 16.5); other flanges on consultation.
Pressure: Maximum inlet pressure 20 bar in Chinese data; the English Bulletin distinguishes 16 bar and 20 bar by integrated overpressure protection; outlet and set range 0.01-15 bar (10 mbar-15 bar).
Control: HON 610, HON 650 or BD-600 pilot; accuracy AC1 to AC10 by outlet band, shut-off class SG5 or SG10, shut-off zone SZ2.5; minimum start-up differential 0.2 bar.
SSV and construction: Integrated straight-through SSV with an internal pressure balancing bypass, set Wdo 50 mbar to 20 bar and Wdu 10 mbar to 15 bar; ductile iron or cast steel body; cast aluminium actuator; NBR and ECO diaphragms; CE (PED) and DVGW.
3. Main Technical Specifications
| Parameter | Specification / Description |
|---|---|
| Product type | Pilot-operated gas regulator with optional integrated SSV |
| Series / model | Honeywell Elster HON 372 |
| Size range | DN25, 50, 80, 100, 150 |
| Max inlet pressure | 20 bar in Chinese data; English Bulletin 16 bar or 20 bar by integrated overpressure protection |
| Pressure class / connection | PN16, ANSI 150; DIN PN16 or ANSI Class 150 (ANSI 16.5); other flanges on consultation |
| Medium | DVGW G260 natural gas and neutral non-corrosive gas; other gases on consultation |
| Outlet / set range | 0.01-15 bar (10 mbar-15 bar) |
| Pilot options | HON 610, HON 650 and BD-600 pilots |
| Accuracy / shut-off | AC1 to AC10 by outlet band; shut-off class SG5 or SG10; shut-off zone SZ2.5 |
| Minimum start-up differential | 0.2 bar |
| Integrated SSV settings | Wdo 50 mbar-20 bar; Wdu 10 mbar-15 bar; internal pressure balancing bypass |
| Materials / temperature | Ductile iron or cast steel body; cast aluminium actuator; NBR and ECO diaphragms; -20 C to +60 C (Class 2) |
| Flow / approvals | KG flow coefficients by seat diameter with and without silencer per the Bulletin; CE (PED), DVGW; refer to the official datasheet; verify with the manufacturer |
4. Selection Guide
Selection sequence: Duty definition -> Size and connection -> Pressure check -> Pilot selection -> SSV and noise -> Verification.
| Step | Item | Key point |
|---|---|---|
| 1 | Duty definition | Confirm a reduction station or commercial and industrial regulating duty |
| 2 | Size and connection | Check DN25 to DN150 and PN16 or ANSI 150 flanges |
| 3 | Pressure check | Confirm inlet against the 16 or 20 bar figure and the outlet against 10 mbar to 15 bar |
| 4 | Pilot selection | Choose the HON 610, HON 650 or BD-600 pilot for the required outlet band |
| 5 | SSV and noise | Specify the integrated SSV settings and noise reduction where required |
| 6 | Verification | Check the KG coefficient by seat diameter on the official data sheet; refer to the official datasheet; verify with the manufacturer |
Boundary: For duties needing more capacity than the HON 370, a wide 10 mbar to 15 bar outlet range and an integrated shut-off valve. Final data are per the official datasheet; refer to the official datasheet; verify with the manufacturer.
5. Complete Model Enumeration
| Model | Family / function | Key specification |
|---|---|---|
| HON 711 | Axial flow safety shut-off valve | DN25-400; overpressure and underpressure shut-off; DIN EN 14382 |
| HON HSV086 | Pilot-operated globe safety shut-off valve | DN25-500; ANSI 150-1500; accuracy class AC1; response under 1 s |
| Elster Jeavons S100 | Spring loaded slam shut valve | DN50-100; 19 bar inlet; full bore; BS EN 14382 |
| HON 305 | Self-operated safety shut-off valve | DN50-200; up to 19 bar; single inline orifice |
| HON 512 | Axial flow pilot pressure regulator | DN25-300; outlet 0.3-90 bar; AC1 / SG5 |
| HON R100 | Globe pilot high pressure regulator | DN25-400; high differential; optional cage silencer |
| HON R100NG | Globe pilot high pressure regulator | DN25-200; HON P095NG pilot; fail-closed or fail-open |
| HON R-50 | Dome loaded high pressure regulator | ANSI 1500 design; accuracy within 1 percent |
| HON Elster AFV | Axial flow valve for multi-purpose use | DN50-300; ANSI 300 / 600; reversible sleeve |
| Elster Jeavons J123 | Spring loaded direct acting regulator | 2 in to 4 in; 4 bar inlet; outlet up to 350 mbar |
| Elster Jeavons J123HP | High outlet spring loaded regulator | 2 in and 3 in; 4 bar inlet; outlet around 1 bar |
| HON 530 | Electric flow and pressure control valve | DN50-500; equal percentage and linear; AC1 |
| HON C210S | Globe flow control valve | DN50-400; noise reduction up to 40 dB(A); electric or pneumatic |
| HON 274 | Lever spring loaded regulator with integrated SSV | 1-1/4 to 2 in thread, DN50 flange; outlet 15-420 mbar |
| HON 370 | Spring loaded direct acting regulator | DN25-150; 20 bar; outlet 20 mbar-4 bar |
| HON 372 | Pilot-operated regulator with integrated SSV | DN25-150; outlet 10 mbar-15 bar; AC1 to AC10 |
| HON 402 | Pilot-operated regulating and shut-off valve | DN25-100; inlet up to 50 bar; outlet 20 mbar-40 bar |
6. Related Models
| Related model | Description |
|---|---|
| HON 370 | Direct acting regulator on the same platform with lower capacity |
| HON 402 | Regulating and shut-off valve for higher inlet pressure |
| HON 610 / HON 650 | Pilots available for the HON 372 regulator |
| Elster Jeavons J123 | Direct acting regulator for smaller distribution sizes |
7. Common Spare Parts
| Spare part | Description |
|---|---|
| Pilot spare set | Matched to the HON 610, HON 650 or BD-600 pilot fitted |
| Diaphragm set | NBR or ECO matched to the original material |
| Seat and internal trim | Matched to the seat diameter and noise reduction option |
| SSV control set | Matched to the integrated shut-off valve where fitted |
8. Accessories
| Accessory | Description |
|---|---|
| Integrated SSV | Straight-through shut-off with internal pressure balancing |
| Noise reduction trim | Selected by seat diameter from the Bulletin |
| Position indication | Local or remote position reporting where offered |
| Module cartridge set | Spare functional module for simplified maintenance |
9. Disclaimer
The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.