Honeywell Elster Jeavons J123HP Spring Loaded Gas Regulator High Outlet
1. Product Overview
The Elster Jeavons J123HP is the higher outlet pressure version of the J123 family. It is a spring loaded, direct acting distribution, commercial and industrial regulator with the same construction principles as the J123.
Official literature lists 50 mm and 80 mm (2 in and 3 in), a maximum inlet pressure of 4 bar (60 psig) and outlet pressure up to about 1 bar, with the Chinese site stating up to 1.035 bar and the J123 family data sheet noting up to 1.015 bar. The valve is fully inlet pressure balanced with full shut-off capability, external sensing, position indication, a dust breather and a high sensitivity rolling diaphragm.
This page is a selection overview. Temperature figures differ between official sources and both are shown; final data are per the official datasheet and refer to the official datasheet; verify with the manufacturer.



2. Technical Description
Design: Spring loaded direct acting regulator with full inlet pressure balance and full shut-off capability.
Size range: 50 mm and 80 mm (2 in and 3 in) on the Chinese site.
Connections: Flange BS EN 1092-2 NP16 or ANSI flange unless otherwise required; external sensing.
Pressure: Maximum inlet pressure 4 bar (60 psig); outlet pressure up to 1.035 bar on the Chinese site and up to 1.015 bar in the family data sheet.
Construction: Position indicator, dust breather and high sensitivity rolling diaphragm; modular design for maintenance.
Standards: BGC/PS/E26 (formerly DIR6) and IGE/TD/10; PED approval within the family; temperature -20 C to +60 C on the Chinese site and -20 C to +70 C in some family data sheets.
3. Main Technical Specifications
| Parameter | Specification / Description |
|---|---|
| Product type | High outlet spring loaded direct acting gas regulator |
| Series / model | Elster Jeavons J123HP; higher outlet version of J123 |
| Size range | 50 and 80 mm (2 and 3 in) |
| Max inlet pressure | 4 bar (60 psig) |
| Outlet pressure | Up to 1.035 bar on Chinese site; family data sheet notes up to 1.015 bar |
| Connection | Flange BS EN 1092-2 NP16 or ANSI flange unless otherwise required |
| Medium | Natural gas, LPG and manufactured gas |
| Installation | Horizontal or vertical with external sensing |
| Operation | Fully inlet pressure balanced, full shut-off, external sensing, position indicator and dust breather |
| Diaphragm | High sensitivity rolling diaphragm |
| Materials | Ductile iron body and seat; aluminium alloy chamber and cover; reinforced NBR diaphragms; stainless steel stem and seat; carbon steel load spring |
| Temperature range | -20 C to +60 C on Chinese site; some family data sheets give -20 C to +70 C; official datasheet governs |
| Approvals | BGC/PS/E26 (formerly DIR6), IGE/TD/10 and PED within the family; refer to the official datasheet; verify with the manufacturer |
4. Selection Guide
Selection sequence: Duty definition -> Size and connection -> Pressure check -> Sensing line -> Monitor or working role -> Verification.
| Step | Item | Key point |
|---|---|---|
| 1 | Duty definition | Confirm a distribution or industrial duty needing an outlet around 1 bar |
| 2 | Size and connection | Check 50 or 80 mm and the NP16 or ANSI flange against the official data sheet |
| 3 | Pressure check | Confirm inlet within 4 bar and the required outlet against the 1.015-1.035 bar figures |
| 4 | Sensing line | Arrange external downstream pressure sensing |
| 5 | Monitor or working role | Specify whether the regulator acts as a monitor or a working regulator |
| 6 | Verification | Confirm temperature and final configuration on the official data sheet; refer to the official datasheet; verify with the manufacturer |
Boundary: For J123 series duties needing a higher outlet pressure around 1 bar, with sizes limited to 50 and 80 mm. For outlet pressure below 350 mbar use the standard J123. Final data are per the official datasheet; refer to the official datasheet; verify with the manufacturer.
5. Complete Model Enumeration
| Model | Family / function | Key specification |
|---|---|---|
| HON 711 | Axial flow safety shut-off valve | DN25-400; overpressure and underpressure shut-off; DIN EN 14382 |
| HON HSV086 | Pilot-operated globe safety shut-off valve | DN25-500; ANSI 150-1500; accuracy class AC1; response under 1 s |
| Elster Jeavons S100 | Spring loaded slam shut valve | DN50-100; 19 bar inlet; full bore; BS EN 14382 |
| HON 305 | Self-operated safety shut-off valve | DN50-200; up to 19 bar; single inline orifice |
| HON 512 | Axial flow pilot pressure regulator | DN25-300; outlet 0.3-90 bar; AC1 / SG5 |
| HON R100 | Globe pilot high pressure regulator | DN25-400; high differential; optional cage silencer |
| HON R100NG | Globe pilot high pressure regulator | DN25-200; HON P095NG pilot; fail-closed or fail-open |
| HON R-50 | Dome loaded high pressure regulator | ANSI 1500 design; accuracy within 1 percent |
| HON Elster AFV | Axial flow valve for multi-purpose use | DN50-300; ANSI 300 / 600; reversible sleeve |
| Elster Jeavons J123 | Spring loaded direct acting regulator | 2 in to 4 in; 4 bar inlet; outlet up to 350 mbar |
| Elster Jeavons J123HP | High outlet spring loaded regulator | 2 in and 3 in; 4 bar inlet; outlet around 1 bar |
| HON 530 | Electric flow and pressure control valve | DN50-500; equal percentage and linear; AC1 |
| HON C210S | Globe flow control valve | DN50-400; noise reduction up to 40 dB(A); electric or pneumatic |
| HON 274 | Lever spring loaded regulator with integrated SSV | 1-1/4 to 2 in thread, DN50 flange; outlet 15-420 mbar |
| HON 370 | Spring loaded direct acting regulator | DN25-150; 20 bar; outlet 20 mbar-4 bar |
| HON 372 | Pilot-operated regulator with integrated SSV | DN25-150; outlet 10 mbar-15 bar; AC1 to AC10 |
| HON 402 | Pilot-operated regulating and shut-off valve | DN25-100; inlet up to 50 bar; outlet 20 mbar-40 bar |
6. Related Models
| Related model | Description |
|---|---|
| Elster Jeavons J123 | Standard J123 regulator with outlet up to 350 mbar |
| Elster Jeavons S100 | Slam shut valve for upstream overpressure protection |
| HON 370 | Direct acting regulator with a wider DN range |
| HON 274 | Small flow regulator with an integrated shut-off option |
7. Common Spare Parts
| Spare part | Description |
|---|---|
| Diaphragm set | Reinforced NBR rolling diaphragm matched to the original |
| Seat and disc set | Matched to the higher outlet pressure trim |
| Load spring | Carbon steel spring matched to the high outlet range |
| Dust breather | Replacement breather for the spring chamber |
8. Accessories
| Accessory | Description |
|---|---|
| Monitor pilot kit | Allows the regulator to serve as a monitor |
| Position indicator | Local indication of valve position |
| External sensing kit | Pilot line for downstream pressure sensing |
| Flange gasket set | Matched to the NP16 or ANSI flange connection |
9. Disclaimer
The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.
10. Sources & Contact
We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China