Honeywell Elster Jeavons J123 Spring Loaded Gas Regulator with Dust Breather
1. Product Overview
The Elster Jeavons J123 is a spring loaded, direct acting distribution, commercial and industrial gas regulator. It can be used as a monitor regulator or as a working regulator, and uses a dust breather to keep the spring chamber clean.
Official literature lists 50 mm, 80 mm and 100 mm (2 in, 3 in and 4 in), a maximum inlet pressure of 4 bar (60 psig) and a maximum outlet pressure of 350 mbar (5 psig). The valve is fully inlet pressure balanced with full shut-off capability, external sensing, position indication and a high sensitivity rolling diaphragm. The modular design allows the regulator assembly to be removed by taking out four nuts without disturbing the pipework.
This page is a selection overview. Temperature figures differ between official sources and both are shown; final data are per the official datasheet and refer to the official datasheet; verify with the manufacturer.



2. Technical Description
Design: Spring loaded direct acting regulator, fully inlet pressure balanced with full shut-off capability.
Size range: 50 mm, 80 mm and 100 mm (2 in, 3 in and 4 in).
Connections: Flange BS EN 1092-2 NP16 or ANSI flange unless otherwise required; external sensing from at least 15 pipe diameters downstream.
Pressure: Maximum inlet pressure 4 bar (60 psig); maximum outlet pressure 350 mbar (5 psig).
Construction: Dust breather, position indicator and high sensitivity rolling diaphragm; modular assembly removable after four nuts are released.
Materials and approvals: Ductile iron body and seat, aluminium alloy diaphragm chamber and cover, reinforced NBR diaphragms and stainless steel stem and seat; PED 2014/68/EU Module B+D, BGC/PS/E26 and IGE/TD/10.
3. Main Technical Specifications
| Parameter | Specification / Description |
|---|---|
| Product type | Spring loaded direct acting gas regulator |
| Series / model | Elster Jeavons J123 |
| Size range | 50, 80 and 100 mm (2, 3 and 4 in) |
| Max inlet pressure | 4 bar (60 psig) |
| Max outlet pressure | 350 mbar (5 psig) |
| Connection | Flange BS EN 1092-2 NP16 or ANSI flange unless otherwise required |
| Medium | Natural gas, LPG and manufactured gas |
| Installation | Horizontal or vertical; external sensing at least 15 pipe diameters downstream |
| Operation | Fully inlet pressure balanced, full shut-off, external sensing, position indicator and dust breather |
| Flow relation | Flow Q calculated from Q = K times the square root of Po(Pi - Po), with K values per the official data sheet |
| Materials | Ductile iron body and seat; aluminium alloy chamber and cover; reinforced NBR diaphragms; stainless steel stem, seat and guide ring; zinc plated carbon steel load spring |
| Temperature range | -20 C to +60 C on the Chinese site; some data sheets give -20 C to +70 C; official datasheet governs |
| Approvals | PED 2014/68/EU Module B+D (BSI, Category IV); BGC/PS/E26 (formerly DIR6) and IGE/TD/10 |
4. Selection Guide
Selection sequence: Duty definition -> Size and connection -> Pressure check -> Sensing line -> Maintenance access -> Verification.
| Step | Item | Key point |
|---|---|---|
| 1 | Duty definition | Confirm a distribution, commercial or industrial regulating duty and whether the valve monitors or works |
| 2 | Size and connection | Check 50, 80 or 100 mm and the BS EN 1092-2 NP16 or ANSI flange |
| 3 | Pressure check | Confirm inlet within 4 bar and the required outlet within 350 mbar |
| 4 | Sensing line | Locate the external sensing point at least 15 pipe diameters downstream |
| 5 | Maintenance access | Allow clearance to remove the modular regulator assembly without disturbing the pipework |
| 6 | Verification | Confirm size, K value and temperature on the official data sheet; refer to the official datasheet; verify with the manufacturer |
Boundary: For low and medium pressure distribution and commercial or industrial users with outlet pressure up to 350 mbar and a need for modular maintenance. Final data are per the official datasheet; refer to the official datasheet; verify with the manufacturer.
5. Complete Model Enumeration
| Model | Family / function | Key specification |
|---|---|---|
| HON 711 | Axial flow safety shut-off valve | DN25-400; overpressure and underpressure shut-off; DIN EN 14382 |
| HON HSV086 | Pilot-operated globe safety shut-off valve | DN25-500; ANSI 150-1500; accuracy class AC1; response under 1 s |
| Elster Jeavons S100 | Spring loaded slam shut valve | DN50-100; 19 bar inlet; full bore; BS EN 14382 |
| HON 305 | Self-operated safety shut-off valve | DN50-200; up to 19 bar; single inline orifice |
| HON 512 | Axial flow pilot pressure regulator | DN25-300; outlet 0.3-90 bar; AC1 / SG5 |
| HON R100 | Globe pilot high pressure regulator | DN25-400; high differential; optional cage silencer |
| HON R100NG | Globe pilot high pressure regulator | DN25-200; HON P095NG pilot; fail-closed or fail-open |
| HON R-50 | Dome loaded high pressure regulator | ANSI 1500 design; accuracy within 1 percent |
| HON Elster AFV | Axial flow valve for multi-purpose use | DN50-300; ANSI 300 / 600; reversible sleeve |
| Elster Jeavons J123 | Spring loaded direct acting regulator | 2 in to 4 in; 4 bar inlet; outlet up to 350 mbar |
| Elster Jeavons J123HP | High outlet spring loaded regulator | 2 in and 3 in; 4 bar inlet; outlet around 1 bar |
| HON 530 | Electric flow and pressure control valve | DN50-500; equal percentage and linear; AC1 |
| HON C210S | Globe flow control valve | DN50-400; noise reduction up to 40 dB(A); electric or pneumatic |
| HON 274 | Lever spring loaded regulator with integrated SSV | 1-1/4 to 2 in thread, DN50 flange; outlet 15-420 mbar |
| HON 370 | Spring loaded direct acting regulator | DN25-150; 20 bar; outlet 20 mbar-4 bar |
| HON 372 | Pilot-operated regulator with integrated SSV | DN25-150; outlet 10 mbar-15 bar; AC1 to AC10 |
| HON 402 | Pilot-operated regulating and shut-off valve | DN25-100; inlet up to 50 bar; outlet 20 mbar-40 bar |
6. Related Models
| Related model | Description |
|---|---|
| Elster Jeavons J123HP | Higher outlet pressure version of the J123 family |
| Elster Jeavons S100 | Slam shut valve often installed upstream of the J123 |
| HON 370 | Direct acting regulator for larger DN sizes |
| HON 274 | Small flow regulator with an integrated shut-off valve option |
7. Common Spare Parts
| Spare part | Description |
|---|---|
| Diaphragm set | Reinforced NBR main and rolling diaphragm matched to the original |
| Seat and disc set | Stainless steel seat and NBR disc matched to the orifice |
| Load spring | Zinc plated carbon steel spring matched to the outlet range |
| Dust breather | Replacement breather for the spring chamber |
8. Accessories
| Accessory | Description |
|---|---|
| Monitor pilot kit | Allows the regulator to serve as a monitor |
| Position indicator | Local indication of valve position |
| External sensing kit | Pilot line for downstream pressure sensing |
| Flange gasket set | Matched to the NP16 or ANSI flange connection |
9. Disclaimer
The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.
10. Sources & Contact
We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文