KSB BOA-Control IMS Balancing Valve, Measuring Valve and Globe Valve with Thrott
1. Product Overview
The KSB BOA-Control IMS is a flanged valve that combines balancing, measuring and shut-off in one body. Its measuring accuracy is independent of the differential pressure, and an embedded ultrasonic sensor can be fitted without contacting the medium.
The official KSB page covers BOA-Control and BOA-Control IMS together. The valve is rated PN16, spans DN15 to DN350, and handles temperatures up to 120 °C. Body materials include EN-GJL-250, EN-GJS-400-18-LT and EN-GJL-250-EKB.
BOATRONIC 100 MOD provides fixed monitoring of flow direction, flow and temperature with 24 V AC/DC and Modbus, while the battery-powered BOATRONIC 100 is used for mobile measurement. Dimensions, Kvs and accuracy values are not published here; Per official data sheet, verify with the manufacturer.



2. Technical Description
Three-in-one function: Balancing, measuring and shut-off in one flanged valve with a throttling cone.
Measurement: Accuracy independent of differential pressure; optional embedded ultrasonic sensor that does not contact the medium.
Size and pressure: DN15-DN350, PN16; face-to-face to EN 558/1.
Body material: EN-GJL-250, EN-GJS-400-18-LT or EN-GJL-250-EKB.
Monitoring options: BOATRONIC 100 MOD, 24 V AC/DC and Modbus, fixed monitoring of flow direction, flow and temperature with optional supply and return temperature and heat logging; BOATRONIC 100 battery unit for mobile measurement.
Drive / actuation: Handwheel or electric actuator; graduated position indicator, travel stop and dew-point barrier insulation cover; maintenance-free and fully insulatable.
3. Main Technical Specifications
| Parameter | Specification / Description |
|---|---|
| Product type | Balancing valve / measuring valve / globe valve with throttling cone |
| Series / model | KSB BOA-Control IMS |
| Design standard | DIN/EN flange; standard face-to-face to EN 558/1 |
| Nominal size | DN15-DN350 |
| Pressure rating | PN16 |
| Medium temperature | Up to 120 °C |
| Body material | EN-GJL-250, EN-GJS-400-18-LT, EN-GJL-250-EKB |
| Connection form | Flanged (DIN/EN) |
| Measurement | Optional embedded ultrasonic sensor, non-contact with the medium |
| Monitoring devices | BOATRONIC 100 MOD (24 V AC/DC, Modbus) fixed; BOATRONIC 100 (battery) mobile |
| Drive / actuation | Handwheel or electric actuator |
| Special features | Graduated position indicator, travel stop, dew-point barrier insulation cover; maintenance-free, fully insulatable |
| Application | Hot water heating, air conditioning, cooling circuits, district heating, potable water, mobile measurement, process monitoring |
| Certification | DVGW drinking water approval available with the EKB electrostatic coating version; Per official data sheet, verify with the manufacturer |
| Dimensions / Kvs / accuracy | Per official data sheet, verify with the manufacturer |
4. Selection Guide
Selection sequence: Duty confirmation -> Size and pressure -> Measurement method -> Monitoring device -> Material and approval -> Ordering check.
| Step | Item | Key point |
|---|---|---|
| 1 | Duty confirmation | Confirm balancing, measuring and shut-off duties in heating, cooling or district heating |
| 2 | Size and pressure | Select within DN15-DN350 at PN16 and check the EN 558/1 face-to-face |
| 3 | Measurement method | Choose standard measurement or the embedded non-contact ultrasonic sensor |
| 4 | Monitoring device | Select BOATRONIC 100 MOD for fixed Modbus monitoring or BOATRONIC 100 for mobile measurement |
| 5 | Material and approval | Confirm EN-GJL-250, EN-GJS-400-18-LT or EKB version and the DVGW approval where potable water is involved |
| 6 | Ordering check | Dimensions, Kvs and accuracy per official data sheet; Ordering code per official data sheet / selection software, verify with the manufacturer |
Boundary: The upper temperature limit is 120 °C and the pressure rating is PN16. Fixed monitoring requires the 24 V AC/DC and Modbus interface of BOATRONIC 100 MOD; verify all device details with the official data sheet.
5. Complete Model Enumeration
| Model / configuration | Function | Description |
|---|---|---|
| BOA-Control IMS | Balancing, measuring and shut-off valve | DN15-DN350, PN16, face-to-face to EN 558/1 |
| BOA-Control IMS with ultrasonic sensor | Measuring valve | Embedded sensor that does not contact the medium |
| BOA-Control IMS with BOATRONIC 100 MOD | Fixed monitoring valve | 24 V AC/DC, Modbus, flow direction, flow and temperature |
| BOA-Control IMS EKB | Potable water version | EKB electrostatic coating with DVGW drinking water approval |
| Other ordering configurations | Per official data sheet | Complete ordering code per official data sheet; verify with the manufacturer |
6. Related Models
| Related model | Description |
|---|---|
| BOA-Control DPR | Self-operated differential pressure control valve, DN15-DN100 |
| BOA-Systronic ePIC | Pressure-independent all-in-one energy valve |
| BOA-CVE IMS | Soft-seat control valve built on the IMS body |
| BOA-Compact | Short face-to-face globe valve for shut-off and control |
7. Common Spare Parts
| Spare part | Description |
|---|---|
| Throttling cone | Matched to the original nominal size; refer to the official spare parts list |
| Ultrasonic sensor module | Matched to the original valve and monitoring device; verify with the manufacturer |
| Position indicator and travel stop | Checked to the original bonnet assembly; refer to the official spare parts list |
| Seal and packing set | Selected for the original body material; refer to the official spare parts list |
| Insulation cover | Dew-point barrier cover matched to the original valve; verify with the manufacturer |
8. Accessories
| Accessory | Description |
|---|---|
| BOATRONIC 100 MOD | Fixed monitoring unit with 24 V AC/DC and Modbus interface |
| BOATRONIC 100 | Battery-powered mobile measuring unit |
| Flange connection parts | Selected to the DN piping flange standard |
| Electric actuator | For motorized operation; confirm control signal with the data sheet |
| Insulation jacket | For fully insulated installation with the dew-point barrier cover |
9. Disclaimer
The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.
10. Sources & Contact
We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文
ENGLISH