Home » Service & Support » Technical Documentation
Hygienic Control Valves: Selection Points for Pharmaceutical Applications
Release time:2026-11-25 16:01:06 | Views:

Control valves for pharmaceutical and biotech service differ from industrial valves: aseptic design, clean-in-place/steam-in-place (CIP/SIP) capability, materials and surfaces compliant with hygienic regulations, and spare parts at the original grade. Based on the SAMSON hygienic/aseptic valve catalogue and relevant certification requirements, this article covers regulatory compliance, materials and surfaces, construction and connections, sizing and spare-part points.

I. Scope and Hygienic Regulations

ItemContent
Design goalMinimized dead space, self-draining, CIP/SIP capable, avoiding residue and microbial growth
Material regulationsFDA 21 CFR 177.1550 / 177.2600 / 177.2415; NSF H1; EC 1935/2004; EU 10/2011
Biological safetyEC 2023/2006; ADI-free (no animal-derived ingredients); EC 999/2001 rev.2015 (TSE/BSE free)
Hygienic approvalsUSP Class VI-121 C; EHEDG and 3-A versions available on request
Typical productsSAMSON Type 3347 hygienic angle valve, 3349 aseptic angle valve, 3321CT, Steripur series, KMA series

Source: SAMSON hygienic and aseptic pneumatic control valve official catalogue (PDF p.59-68 / printed p.58-67), conformity sections. Approvals subject to official certificates and data sheets; if not found, state "unable to confirm, please verify with the manufacturer".

Control valve illustration
Control valve illustration, not a hygienic product; parameters subject to the official data sheet

II. Materials and Surface Requirements

ItemCommon choiceNotes
Body / bonnet1.4404 / 316L, 1.4409 / CF3M, 1.4435 / 316L, 1.4408 / A351 CF8MSpecial materials such as 1.4539 / AISI 904L available on request
Diaphragm materialEPDM Code 28; PTFE/EPDM Code 30 / 44EPDM meets FDA 177.2600, USP Class VI, 3-A Class II; PTFE/EPDM meets FDA 177.1550, 3-A Class I
SealsFood-grade certified elastomersSpare parts at the same grade as the original
SurfaceHygienic polishing to reduce surface roughness RaSpecific Ra and electropolishing requirements per data sheet and project specification

The "hygienic" quality of a valve depends not only on the material grade but also on surface finish, dead volume and drainability. If Ra values cannot be found, state "subject to the official data sheet/project specification" and never invent Ra figures.

Source: SAMSON hygienic valve official catalogue material and diaphragm code tables (EPDM Code 28, PTFE/EPDM Code 30/44); Baumann flange face roughness per EN and ASME versions (EN 500-300 Ra concentric, ASME 250-125 Ra concentric). Hygienic Ra subject to the official data sheet.

III. Construction and Connections

Product familyConstructionConnectionsData sheet
Type 3347 hygienic / 3349 aseptic angle valveAngle body, aseptic designFlanges, welding ends, clamps, aseptic flangesT 8097 / T 8048; T 8048-21 / -22
Type 3321CTHygienic control valvePer official data sheetT 8115
Steripur 217/317/417/407 etc.Aseptic diaphragm/seat valve seriesPer official data sheetT 217 / T 317 / T 417 / T 407
KMA 190/195/395/495Plastic actuator with stainless adapter, on/off, quick-open self-drainingWelding ends, clamps, aseptic flangesT 190 / T 195 / T 395 / T 495

KMA example: KMA 190/195 are DN 4-15 / 8-20, EPDM diaphragm maximum working pressure 8 bar and PTFE diaphragm 7 bar; KMA 395/495 are DN 15-65 / 15-100, EPDM diaphragm 10 bar (up to DN50) and PTFE diaphragm 8 bar (up to DN50), maximum medium temperature 160 C. Subject to the data sheet.

Source: SAMSON official catalogue data sheet numbers and technical tables (PDF p.66-67 / printed p.65-66). Dimensions, weights and digit-by-digit ordering codes are not published in the catalogue and are marked "pending / generated by sizing software"; no values are invented.

IV. Sizing and Actuators

ItemBasisNotes
SizingPer IEC 60534, Kvmax = 0.7-0.8 x KvsCalculated by SAMSON sizing software
ActuatorType 3271 / 3277 pneumatic actuator, or 3372 / 3379Allows integrated mounting of positioner and accessories
Micro-flow versionmicro-flow valveLow-flow clean media control
Fail actionfail-open / fail-closeSet by process safety requirements
AccessoriesPositioner/limit switch, position transmitter, solenoid valve, pneumatic lock valve, air pressure reducerFill in item by item per official general ordering data

The official catalogue does not publish digit-by-digit ordering codes for these hygienic products; it only gives application, conformity, versions, technical data and data sheet numbers. Therefore ordering codes are written as "pending / generated by sizing software" and must not be inferred from other series.

Source: SAMSON official catalogue general section 1.3.3 Selection and ordering (PDF p.24 / printed p.23) and hygienic valve sections; sizing per IEC 60534 with Kvmax = 0.7-0.8 x Kvs. Subject to the official data sheet and sizing software.

V. Spare Parts and Maintenance Points

PartCategory
DiaphragmCore wear part
Plug / pistonWear part
SealsWear part
Connections / clampsMaintenance part
BodyMain part

Hygienic and aseptic applications impose mandatory requirements on materials and surface roughness (Ra); spare parts must match the original grade. Provide order number, tag, model and nameplate data when ordering. Digit-by-digit part numbers for diaphragms, plugs and seals require the full EB documents (such as EB 8097 / EB 8048) and are not invented here.

Source: SAMSON hygienic diaphragm valve official catalogue wear-parts section and EB document numbers (EB 8097 / EB 8048); ordering data per official general ordering information. Subject to the official data sheet and spare-parts list.

VI. Selection Guide and Common Cases

Selection guide: First confirm the medium, CIP/SIP temperature and cleaning agents, then set materials, diaphragm and approval version by hygienic regulations; select the construction (angle valve/diaphragm valve/seat valve) and connections, size per IEC 60534 and define actuator and fail action; finally check spare-part grade and data sheet numbers. If approvals, Ra or ordering codes cannot be found, state "unable to confirm, please verify with the manufacturer" or "subject to the official data sheet".

Common cases: (1) Aseptic fermentation/purification: aseptic angle or diaphragm valve with EPDM/PTFE diaphragm and clamp/aseptic flange; (2) CIP/SIP high-temperature cleaning: verify diaphragm and seal temperature limits; (3) micro-flow dosing: micro-flow version; (4) critical loops: positioner with diagnostics and position feedback, configured per SIL/validation requirements.

If you are selecting a hygienic control valve for a pharmaceutical or biotech plant, or verifying material approvals, diaphragm grades and CIP/SIP boundaries, please send us the medium, cleaning method, temperature and connection standard. We can review hygienic compliance, construction and spare parts item by item against the official catalogue and data sheets.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.