| Control Valve Cavitation Coefficient FL and Differential Pressure Calculation | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-25 16:01:06 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
In liquid control valve sizing, not all differential pressure produces flow: when the pressure at the vena contracta falls to the fluid vapor pressure, the valve enters choked flow. Further pressure drop no longer increases flow but brings cavitation, flashing and noise. The liquid pressure recovery factor FL is the key parameter defining this limit. Based on IEC 60534-2-1 / GB/T 17213.2-2005 and ISA-75.01.01, this article covers the definition of FL, the choked pressure drop equation, typical values and practical judgment steps. I. Topic Positioning: What FL Is
The data in this article was obtained via web search. Sources: IEC 60534-2-1 / GB/T 17213.2-2005; Emerson Product Bulletin "Understanding Choked Flow in Fisher Valves" (document en-122950, https://www.emerson.com/documents/automation/product-bulletin-understanding-choked-flow-in-fisher-valves-en-122950.pdf); Chinese technical note https://www.reallycv.com/newsinfo/159266.html. Manufacturer figures subject to the official data sheet.
II. Liquid Choked Flow and Pressure Drop Calculation
Calculation approach: First obtain Pv and Pc at inlet temperature and compute FF; then use the FL of the selected body, trim and opening to find dP choked; compare it with the actual pressure drop and use the smaller value in the flow coefficient equation. If the actual pressure drop already exceeds the choked value, increasing drop further will not raise flow; select different trim, raise inlet pressure or stage the pressure reduction instead. The data was obtained via web search. Sources: Emerson Product Bulletin "Understanding Choked Flow in Fisher Valves" (en-122950) gives dP choked = FL^2[P1 - FF x Pv] and FF = 0.96 - 0.28(Pv/Pc)^0.5; GB/T 17213.2-2005 / IEC 60534-2-1 and https://www.reallycv.com/newsinfo/159266.html give liquid and compressible choking criteria. Subject to the original standard. III. Typical FL Values and Body Style Comparison
Screening values are for concept comparison only: FL enters the choked pressure drop squared, so the globe-to-butterfly choked drop ratio is about (0.90/0.60)^2 = 2.25. Final calculations must use manufacturer test values for the selected body, trim and opening; screening figures must not replace them. The data was obtained via web search. Sources: screening figures from https://calcengineer.com/blog/valve-cv-travel-authority-choked-flow and https://www.tangovalve.com/blogs/choked-flow-in-control-valves/ (both labeled screening figures); CAV4 recovery coefficients from Fisher Product Bulletin 51.2:CAV4, document D101497X012; ACE95 coefficients from Bulletin 74.1, document D102720X012. Subject to the official data sheet. IV. Cavitation Judgment and Calculation Steps
Recommended steps: (1) Define P1, P2, T and fluid Pv, Pc; (2) find FL of the selected body/trim/opening and apply attached-fitting corrections if needed; (3) compute FF and dP choked; (4) compare with actual pressure drop and judge choking, cavitation or flashing; (5) if damaging cavitation exists, use staged trim or a higher-FL body and recheck materials and noise; (6) for gas or steam use the XT and Fr criteria instead. The data was obtained via web search. Sources: ISA-75.01.01 / IEC 60534-2-1 classification criteria (https://www.williamsvalve.com/blog/cost-of-cavitation-how-choked-flow-destroys-valve-internals/); cavitation vs flashing distinction per IEC 60534-8-2 references. Subject to the original standard and official data sheet. V. Common Engineering Mitigation Measures
Source: Fisher CAV4 (D101497X012) and Cavitrol official bulletins on staged pressure reduction and anti-cavitation design; specific structures, materials and allowable pressure drops subject to the official data sheet. VI. Selection Guide and Common CasesSelection guide: First calculate dP choked for the actual duty to see whether the valve is choked; then perform an accurate check using the official FL of the selected body, trim and opening. Do not treat screening FL as a final value, and do not equate choked flow automatically with cavitation damage: a globe valve may choke without damage, while a rotary valve may cavitate before choking. If FL cannot be found, state "subject to the official data sheet/nameplate" or "please confirm" and never invent figures. Common cases: (1) High-pressure-drop water: prefer multistage anti-cavitation trim and check dP choked and materials; (2) small rotary high-recovery valves: focus on incipient cavitation and outlet velocity; (3) gas or steam: switch to XT, Fr and IEC 60534-8-3 noise checks; (4) with reducers or fittings: apply the installed FL correction per the standard and iterate. If you are checking whether a liquid control valve is choked, or verifying the FL and allowable pressure drop of a selected trim, please send us the medium, inlet/outlet pressures, temperature and valve style. We can review FL, dP choked and cavitation risk item by item against IEC 60534-2-1. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |