In an Ex ia intrinsically safe loop, a safety barrier (zener barrier or galvanic isolator) must limit energy to satisfy IEC 60079-11 while not attenuating or filtering the HART FSK signal (1200/2200 Hz, about ±0.5 mA) superimposed on the 4-20 mA signal. The common field symptom "analog works but the handheld cannot connect" is usually caused by a barrier that is not HART compatible or by insufficient loop resistance/cable capacitance. Based on Flowserve/SAMSON device manuals and IS parameter practice, this article covers passthrough conditions, loop calculation and engineering notes.

I. Technical Positioning and Standards

ItemContent
IS standardIEC 60079-11 (intrinsic safety "i"); associated-apparatus parameters Uo/Io/Po/Co/Lo must match field-device Ui/Ii/Pi/Ci/Li
HART signalBell 202 FSK, 1200 Hz (1) / 2200 Hz (0), 1200 bit/s, ±0.5 mA superimposed on 4-20 mA
Barrier typesZener safety barrier and galvanic isolator
Passthrough requirementSufficient and stable impedance in the HART frequency band, with no low-pass filtering
Loop resistanceAt least about 230 ohm, commonly 250 ohm, to convert the FSK current into a measurable voltage
Field examplesSAMSON Type 3730-3: HART-band receiving impedance 350-450 ohm, sending about 115 ohm; Type 3770 is an Ex d/Ex i field barrier (data sheet uT 8379)

Source: IEC 60079-11 is the standard number; SAMSON Type 3730-3 operating manual (HART-band receiving 350-450 ohm, sending about 115 ohm) and Type 3770 field barrier data sheet uT 8379; HART frequency and amplitude from the Flowserve Logix 520MD+ manual LGENIM0105-16. Obtained via web search. Source: HART technical material (https://itotconvergentie.nl/en/hart, loop resistance at least about 230 ohm, commonly 250 ohm). Subject to the original manual and Ex certificate.

Instrument illustration, not the actual model
Instrument illustration, not the actual model; parameters subject to the official data sheet

II. Determining HART Compatibility of a Barrier

Core criterion: a barrier that "passes 4-20 mA current" is not necessarily able to pass HART. Field-device manuals explicitly require a HART-compatible barrier: an incompatible barrier may allow normal control while blocking HART communication. Check the manufacturer's HART-band impedance/bandwidth data and compatibility list; if it cannot be confirmed, treat the barrier as incompatible and verify with the manufacturer.

DimensionRequirementNon-compliant consequence
HART-band impedanceSufficient and stable at 1200/2200 Hz (typical target ≥230 ohm, commonly 250 ohm)Signal voltage too low for the handheld to decode
Frequency responseNo low-pass attenuation at 1-2.2 kHzFSK waveform smoothed away
IS parametersUo ≤ Ui, Io ≤ Ii, Po ≤ Pi, plus cable Co/Lo checkIS invalidated, approval void
Isolation and groundingSingle-end grounding per the manual, avoiding ground loopsNoise injected, communication disturbed
ApprovalEx approval covering the zone and gas groupNon-compliant in hazardous areas
ConsistencyVerify jointly with the HART input card/handheldMismatch between ends causes no response

Source: Flowserve Logix 3200MD/3400MD/520MD+ manuals ("When selecting an intrinsically safe barrier, make sure the barrier is HART compatible. Although the barrier will pass the loop current and allow normal positioner control, if not compatible, it may prevent HART communication."); IS parameter matching from IEC 60079-11 and the GE Energy "FVP 110 Fieldbus Valve Positioner Manual" Entity section. Subject to the original manual and Ex certificate.

III. Loop Voltage and Cable Capacitance Calculation

Voltage check: available loop voltage = controller output voltage (at max current) minus max current times (barrier resistance plus wire resistance); it must exceed the device's minimum terminal voltage. Flowserve 520MD+ example: 19 V - 20 mA x (300 ohm + 25 ohm) = 12.5 V, above the required 10 V, so the loop supports the device; the device minimum voltage is model-specific (e.g. 9 V for the 3400MD FF version).

ItemFormula / valueNotes
Available voltageV = V_controller(@I_max) - I_max x (R_barrier + R_wire)Must be ≥ device minimum terminal voltage
Maximum network capacitanceC ≤ 650 / (R_barrier + R_wire + 390) - 0.0032 (uF)From Flowserve 520MD+ Equation 2; example 0.08 uF
Maximum cable lengthL_max = C_network / C_cableExample 0.08 uF / 0.000072 uF/m about 1111 m
Cable gauge24 AWG below 5000 ft, 20 AWG for longer runsControls loop resistance
IS cable parametersC_cable ≤ Co - sum(Ci); L_cable ≤ Lo - sum(Li)Entity model; terminator capacitance must be included
Shield groundingSingle-end ground, normally at the signal sourceGrounding screw must not terminate signal shields

Formula and example from the Flowserve Logix 520MD+ user manual LGENIM0105-16 (Equations 1/2/3, 24/20 AWG, single-end shield grounding) and the Flowserve Logix 3400MD manual FCD LGENIM3404-10 (9 V minimum voltage, FF-compatible barrier); Entity cable parameters from the GE Energy "FVP 110 Fieldbus Valve Positioner Manual". Subject to the original manual and the IS calculation.

IV. Filters and Interference Handling

SymptomCauseAction
Analog OK but no HART responseCurrent source not HART compatible, filtering out FSKAdd a HART filter between the source and the device, or use a compatible source
Barrier blocks HARTBarrier not HART compatibleReplace with a HART-compatible barrier and check band impedance against the manual
Intermittent communicationExcess cable capacitance or lengthDerate using C ≤ 650/(R+R+390) - 0.0032 or use lower-capacitance cable
Common-mode interferenceShield grounded at both ends creating a loopChange to single-end grounding
Filter in an IS areaOrdinary filter has no hazardous-area approvalThe Flowserve example filter 139774 is not rated for hazardous areas and must be installed between the source and the barrier

Engineering note: a HART VHF filter leaves DC current unaffected and only prevents the current source from disturbing HART frequencies; it must be installed between the current source and the barrier, and a filter without Ex approval must never be placed in a hazardous area. Ex ia intrinsic safety is NOT Ex d flameproof and must never be mixed. If an approval cannot be found, state "unable to confirm, please verify with the manufacturer".

Source: Flowserve Automax Logix 3200IQ manual (HART VHF Filter, part no. 139774, "not rated for use in hazardous areas", installed between source and barrier) and the Flowserve 520MD+ manual (filter required for incompatible current sources). Subject to the original manual and Ex certificate.

V. Selection Guide and Common Configurations

Selection guide: first confirm the field device's HART revision and minimum terminal voltage; then select a HART-compatible barrier whose Ex approval covers the zone and gas group, and check Uo/Io/Po against Ui/Ii/Pi and cable Co/Lo item by item; then verify the loop with the available-voltage and network-capacitance formulas, adding a 250 ohm resistor, a HART filter or a shorter cable as needed. At commissioning, verify communication with a HART handheld at both ends of the loop; an intact analog reading alone does not prove the link works.

Common configurations: 24 V DC supply, a HART-compatible barrier (zener or galvanic isolator), 4-20 mA shielded twisted pair, an Ex ia smart positioner/transmitter, a 250 ohm loop resistor (often integrated in the input card or barrier), and a HART handheld/input card; the shield is grounded at one end and the barrier is installed on the safe-area side.

If you have a case of "analog normal but HART not connecting", or want to check barrier compatibility and loop parameters, please send us the device model, loop diagram and barrier certificate. We can check the IS parameters and HART passthrough conditions item by item against IEC 60079-11 and the device manual.