PROFIsafe is a communication profile for functional safety (fail-safe), defined in IEC 61784-3-3 and usable with both PROFIBUS and PROFINET, recognized by IFA and TÜV. It transports safety messages as the payload of standard process data on the same network; the underlying transmission channel is treated as a "black channel", removing the need for a separate safety assessment of that path. Based on PI official system descriptions and device manuals, this article covers the black-channel principle, the four safety measures and their application boundaries in valve safety control. I. Technical Positioning and Standards
Obtained via web search. Source: PI official "PROFINET System Description" section 8.1 https://www.profibus.com/index.php?eID=dumpFile&t=f&f=207029 (IEC 61784-3-3, black channel, four safety measures, document numbers) and "PROFINET Field Devices" section 7.2 https://www.profibus.com/fileadmin/media/downloadsection/technical_description_%26_books/PROFINET_Field_Devices_eng_2018.pdf. The PROFIsafe specification prevails.
II. Black Channel and Four Safety MeasuresBlack-channel principle: the PROFIsafe layers in the F-host and F-device sit above the black channel and are implemented in software (drivers), with a state machine at their core handling cyclic F-messages. Users do not need to assess the safety of the specific transmission path; safety is guaranteed end to end by add-ons to the F-message itself.
Obtained via web search. Source: PI "PROFINET System Description" 8.1 and "PROFINET Field Devices" 7.2.2 (four measures: Sign-of-life, Watchdog, F-address, CRC; F-message structure with Status Byte, Input Data, CRC; Fig. 22 black-channel diagram). The PROFIsafe System Description and specification [3.192] prevail. III. Typical Architecture in Valve Control
Key principle: implementing PROFIsafe does not turn a standard device into an F-device. The SIL achieved depends on the device's "technology" architecture, the protocol and the way both are implemented. Safety functions must be performed jointly by the F-host and F-device, not by merely sending CRC-protected messages over ordinary I/O. Architecture from PI "PROFINET Field Devices" 7.2.3 ("implementation of PROFIsafe does not turn a standard device into an F-device"; F-host/F-device state machine in Fig. 23); PST and safety solenoid example from Neles ValvGuard VG9000 material (IEC 61508 SIL 3, HART/FF communication, with PST). Subject to IEC 61508/IEC 61511 and the device safety manual. IV. Engineering Implementation and SIL
Safety-loop design, verification and maintenance follow the IEC 61511 lifecycle. This article only summarizes the recognized communication mechanisms and gives no project-specific SIL conclusion. Whether a device carries the claimed SIL capability must be checked against a third-party certificate; where none can be found, state "unable to confirm, please verify with the manufacturer". Obtained via web search. Source: PI "PROFINET Field Devices" 7.2 (IEC 61508, PROFIsafe Policy, F-host/F-device state machine) and "PROFINET System Description" 8.1 (IFA/TÜV recognition, document numbers). The PROFIsafe specification and safety manual prevail. V. Selection Guide and Common ConfigurationsSelection guide: first set the SIL target and the safe action (de-energize to open or close) from the safety requirement; then select an F-host, F-DI/F-DQ and field safety devices with PROFIsafe capability and check the scope of their third-party certificates; then configure F addresses, watchdog times and safe states under the PROFIsafe Policy, and verify that the total response time from F-message issue to the valve reaching its safe position meets the process safety time. Normal diagnostics, HART variables and PST data travel on the standard channel and must never be used as safety functions. Common configurations: a fail-safe PLC (F-host) plus a PROFINET IO or PROFIBUS DP network, remote F-modules, and the emergency-shutdown valve's solenoid and position feedback; the same network carries both ordinary I/O and PROFIsafe F-messages with no separate safety bus. Specific device combinations and SIL are subject to the official safety manual and certificate. If you are planning a valve safety loop, or want to check PROFIsafe F addresses, watchdog times and safe-state settings, please send us the safety requirement, valve action direction and network topology. We can confirm the communication-level boundaries together against IEC 61784-3-3 and the official system description. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |