HART (Highway Addressable Remote Transducer) superimposes a Bell 202 FSK digital signal on the 4-20 mA analog signal. In the default point-to-point mode one wire pair serves one device; setting a nonzero polling address enters multidrop mode, where several devices share one pair, the loop current is fixed at 4 mA and all process values are read digitally. Based on SAMSON/Flowserve field-device manuals and HART specifications, this article compares the two modes and covers addressing, loop resistance and cable-length calculation, plus the boundaries of multidrop application.

I. Technical Positioning and Standards

ItemContent
Physical layerBell 202 FSK, 1200 Hz for "1" and 2200 Hz for "0", 1200 bit/s
Signal overlayAbout ±0.5 mA AC current superimposed on the 4-20 mA DC; near-zero mean, so the analog reading is unaffected
Communication modesPoint-to-point (address 0, analog plus digital) and multidrop / standard bus (nonzero address, digital only)
MastersTwo masters per loop: primary master (control system) and secondary master (handheld communicator)
Device descriptionDD/EDDL (IEC 61804-3), DTM (IEC 62453), FDI (IEC 62769)
Command typesUniversal, common-practice and device-specific commands (e.g. Command 0 read unique identifier)

Obtained via web search. Source: SAMSON Type 3730-3/3731-3 operating manuals (HART FSK overlay, point-to-point address 0, standard bus address 1-15, Z box / 250 ohm plus 22 uF adaptation) and HART protocol technical material (Bell 202, 1200/2200 Hz, frame structure, command classes). The FieldComm Group official specification prevails.

Positioner illustration, not the actual device
Positioner illustration, not the actual device; parameters subject to the official data sheet

II. Point-to-Point vs Multidrop

ItemPoint-to-pointMultidrop / standard bus
Polling addressMust be 01-15 (HART 5); extended to 63 in HART 6/7
Loop current4-20 mA proportional to primary variable PVFixed at about 4 mA (some devices allow 0 mA)
Process valueAnalog and digital available simultaneouslyDigital only, must be read via HART commands
DevicesOne device per wire pairSeveral devices in parallel on one pair
Update rateContinuous analog, HART about 2-3 updates/sPolling about 0.5-2 updates/s per device, decreasing with device count
Typical useConventional measurement and control loopsMultipoint monitoring, split-range control, diagnostic data collection

Key limitation: multidrop removes the process-varying 4-20 mA analog signal. If the control strategy reads the primary variable through an analog input card, multidrop is the wrong tool; use point-to-point with a separate loop per device, or change the control logic to read the HART digital variable.

Source: SAMSON 3730-3 operating manual (point-to-point address must be 0, standard bus address 1-15, split-range application); extended multidrop addresses and fixed 4 mA from HART technical material and the Flowserve Logix 520MD+ manual LGENIM0105-16. Subject to the original manual.

III. Addressing Mechanism and Frame Types

ItemDescriptionPoint
Short frame addressOne-byte polling address (0-15 or 0-63)Master specifies the slave polling address in the frame
Long frame addressFive-byte unique ID: manufacturer ID (2) + device type (1) + device ID (2)Read by Command 0 for unique addressing
Start delimiterMaster to slave 0x02 (long address) / 0x06 (short address); slave to master 0x06 / 0x86 (error) / 0x16 (busy)Long and short frames use different bytes
Preamble5 to 20 bytes of 0xFFReceiver synchronization
CheckPer-byte vertical parity (odd) plus longitudinal parity and checksum (LRC)Detects transmission errors
Device identitySix-byte manufacturer ID plus three-byte device type code and serial numberAssigned centrally by FieldComm Group

In practice, use a handheld communicator to change each device's polling address from 0 to a unique value (e.g. 1, 2, 3...), confirm the loop current drops to 4 mA, then wire the devices in parallel and let the asset management system scan the loop. Address conflicts prevent devices from being polled correctly.

Obtained via web search. Source: HART protocol frames, commands and field diagnostics (https://industrialmonitordirect.com/zh-hant/blogs/knowledgebase/hart-protocol-frames-commands-and-field-diagnostics, frame length 11-36+ bytes, 15/63 devices, 1200/2200 Hz) and HART protocol communication chapter https://circuitlabs.net/?p=2118 (short/long frame format, start-delimiter bytes). The FieldComm Group specification prevails.

IV. Loop Resistance and Cable Length Calculation

Loop resistance: HART communication needs sufficient loop impedance (at least about 230 ohm, commonly 250 ohm in practice) to convert the ±0.5 mA FSK current into a measurable voltage. With insufficient impedance the handheld cannot communicate even though the analog signal is normal. When the control-system output is not HART compatible, insert a 250 ohm resistor in series and a 22 uF capacitor in parallel across the analog output, or use a Z box (approximately equivalent to 16.5 ohm at 20 mA).

ItemFormula / valueNotes
Minimum loop resistance≥ about 230 ohm, commonly 250 ohmSet by HART-frequency receive sensitivity
Maximum network capacitanceC ≤ 650 / (R_barrier + R_wire + 390) - 0.0032 (uF)From the Flowserve 520MD+ manual; example gives 0.08 uF
Maximum cable lengthL_max = C_network / C_cableExample: 0.08 uF / 0.000072 uF/m about 1111 m
Cable selection24 AWG below 5000 ft, 20 AWG for longer runsControls loop resistance
Shield groundingSingle-end ground, normally at the signal sourceDo not re-ground at the positioner
Safety barrierMust be HART compatibleAn incompatible barrier blocks HART while still passing analog current

Formula and example from the Flowserve Logix 520MD+ user manual LGENIM0105-16 (Equation 2/3: C_network = 650/(R_barrier+R_wire+390) - 0.0032, maximum cable length, 24/20 AWG, single-end shield grounding, HART-compatible barrier); 250 ohm and Z box adaptation from the SAMSON 3730-3/3731-3 operating manuals. Subject to the original manual.

V. Selection Guide and Common Configurations

Selection guide: first determine whether the control loop depends on the analog 4-20 mA primary variable: if it does, use point-to-point (address 0); only use multidrop (nonzero address) when digital-only values are acceptable and cable saving matters. For multidrop, verify the device supports HART 5/6/7 and that the manufacturer has enabled multidrop, set a unique polling address on each device and confirm the current drops to 4 mA. Then check loop resistance, cable capacitance and length, and use a HART-compatible safety barrier/input card; in hazardous areas check IS parameters by zone, and never mix Ex ia intrinsic safety with Ex d flameproof.

Common configurations: a multidrop loop consists of a HART master (handheld, multiplexer or HART input card), shielded twisted pair, several parallel HART devices (pressure/temperature/level transmitters, valve positioners) and a 250 ohm loop resistor; the handheld can join as secondary master at any time. In split-range control several positioners share one pair and are addressed separately.

If you are evaluating whether to put several instruments on one wire pair, or want to check polling addresses, loop resistance and cable length, please send us the device list, loop diagram and site distances. We can work out the applicability of multidrop and the communication margin against the official manual.