Home » Service & Support » Technical Documentation
FOUNDATION Fieldbus H1 Segment Design & Terminators
Release time:2026-11-25 14:00:33 | Views:

FOUNDATION Fieldbus H1 is an all-digital fieldbus for process instruments. It shares the IEC 61158-2 MBP physical layer with PROFIBUS PA (31.25 kbit/s, bus powered) but uses LAS (Link Active Scheduler) token scheduling and function blocks. Exactly one terminator must be installed at each physical end of the trunk; otherwise reflections and communication faults occur. Based on Fieldbus Foundation/FieldComm material and field-device manuals, this article covers H1 topology, terminators, segment length and device count, plus the FISCO/Entity/HPT models for hazardous areas.

I. Technical Positioning and Standards

ItemContent
Protocol roleFF field-device level (H1), all-digital, multidrop, bus powered; HSE (High Speed Ethernet) serves as backbone
Physical layerIEC 61158-2 MBP, 31.25 kbit/s, Manchester coding, signal current ±9 mA
Media accessLAS token scheduling, deterministic macrocycle; redundant backup LAS possible
Control architectureFunction blocks execute inside field devices (AI/AO/PID etc.), distributed control
TopologyTrunk plus spur tree; disconnecting one device does not affect the others
Main standardsIEC 61158-2, FF-816 physical layer, FF-844 H1 cable specification, IEC 60079-11 (IS), AG-140/AG-181 (installation)

Standard numbers: IEC 61158-2 and IEC 60079-11 are international standard numbers; FF-816/FF-844/AG-140/AG-181 are official Fieldbus Foundation document numbers, see the Masoneilan SVI FF manual (ES-776 Rev K) and the Flowserve Logix 3400MD manual FCD LGENIM3404-10. Obtained via web search. Source: Foundation Fieldbus H1 technical reference https://industrialmonitordirect.com/de/blogs/knowledgebase/foundation-fieldbus-h1-protocol-technical-reference-guide.

Positioner illustration, not the actual device
Positioner illustration, not the actual device; parameters subject to the official data sheet

II. Terminator Configuration

Core rule: each H1 segment must have exactly one terminator at each physical end of the trunk, two in total; never terminate a spur. A missing terminator causes abnormally high signal amplitude and reflections; a third terminator halves the amplitude and can drop devices off the bus. Terminators must match the cable characteristic impedance and the segment voltage/current; in IS segments they must be certified intrinsically safe terminators.

ItemParameter / requirementNotes
Resistance90-100 ohm (commonly 100 ohm)Matches Type A cable characteristic impedance
Capacitance0-2.2 uF (typically 1 uF in series)RC series terminator for frequency-dependent matching
QuantityExactly 2 per segmentOnly at the two physical trunk ends
LocationTrunk ends, not spursOne may be integrated in the power supply/conditioner
IS requirementCompliant with IEC 60079-11, fail-safeFISCO applications require a FISCO-certified terminator

Obtained via web search. Source: Foundation Fieldbus H1 technical reference (https://industrialmonitordirect.com/de/blogs/knowledgebase/foundation-fieldbus-h1-protocol-technical-reference-guide, 32 devices per segment including 2 terminators, 1 uF in series with 50 ohm or 100 ohm); terminator R = 90-100 ohm, C = 0-2.2 uF from GE Energy "FVP 110 Fieldbus Valve Positioner Manual". Subject to the official manual.

III. Segment Length, Spurs and Device Count

ConstraintValueNotes
Data rate31.25 kbit/sSame MBP physical layer as PA
Type A cable total length≤ 1900 m (all spurs included)Trunk plus spurs, not trunk alone
Type B cable≤ 1200 mThinner conductor, shorter length
Spur length≤ 120 m (1-12 devices)Derating: 90 m at 13-14, 60 m at 15-18, 30 m at 19-24 devices
Device count≤ 32 per segment (2 terminators consume addresses)IS FISCO/Entity often limits to 4-12 devices by power budget
Mixed cable(L_A/1900) + (L_B/1200) ≤ 1.0Each length includes trunk and spur cable of that type

Calculation basis: the length budget includes the trunk, all spurs and cabinet tails. Voltage drop is usually the main cause of dropouts on long segments; check at the most remote device using "supply voltage minus total current times loop resistance". Reserve 25-30 % current margin and at least two free addresses per segment for future additions.

Obtained via web search. Source: Foundation Fieldbus H1 Cable Length Limits and Segment Design (https://jhqkkr-kd.myshopify.com/blogs/knowledgebase/foundation-fieldbus-h1-cable-length-limits-and-segment-design, Type A 1900 m / Type B 1200 m / Type C 400 m, spur derating table, mixing formula, voltage-drop check); general parameters from the H1 technical reference (previous source). Subject to official data sheets and the segment calculation.

IV. FISCO / Entity / HPT Models in Hazardous Areas

ModelFeaturesApplication
EntitySimple parameter matching between barrier and device: Po ≤ Pi, Uo ≤ Ui, Io ≤ IiClass I Div 1 / Zone 0 conventional IS
FISCOFieldbus Intrinsically Safe Concept, simplified approval; single IS supplyGas and dust hazardous areas, most common
HPT (High Power Trunk)Higher trunk power, IS protection on spurs onlyLarge field installations
Terminator and shieldFail-safe terminator, single-end shield groundingRequired in all IS models
Example device dataFISCO: Ui 17.5 V, Ii 380 mA, Pi 5.32 W, Ci 1 nF, Li 1 uHFrom Masoneilan SVI FF manual ES-776 Rev K, example only

The FISCO figures above are a specific device example, not general values; Ui/Ii/Pi/Ci/Li differ per device, so certificate values must be taken device by device and compared with the barrier/supply parameters. Ex ia intrinsic safety is NOT Ex d flameproof and must never be mixed; where an approval cannot be confirmed, state "unable to confirm, please verify with the manufacturer".

Device example from the Masoneilan SVI FF manual ES-776 Rev K (FISCO Ui 17.5 V / Ii 380 mA / Pi 5.32 W / Ci 1 nF / Li 1 uH; Entity Ui 24 V / Ii 250 mA / Pi 1.2 W); model classification from the Foundation Fieldbus H1 technical reference (URL in the previous source). Subject to the original Ex certificate.

V. Selection Guide and Commissioning

Selection guide: choose the IS model by area classification (FISCO preferred), verify Type A trunk-plus-spur total length and spur derating, set the device count by summed current and address ceiling, then confirm the two terminators and their IS certification. At commissioning, measure segment DC voltage at the host and at the most remote device, record both and confirm the remote value exceeds the minimum with margin. Check signal amplitude with a bus diagnostic tool: uniformly low amplitude suggests a third terminator or excessive length; uniformly high amplitude suggests a missing terminator.

Common configurations: a typical H1 segment consists of an FF power supply/conditioner, Type A shielded twisted pair, two terminators, several FF positioners/transmitters and an LD link device; the LAS function is usually hosted in the DCS FF card with a backup LAS configurable. Macrocycle and function-block scheduling are downloaded by the configuration tool.

If you are designing or troubleshooting an FF H1 segment, please send us the topology, cable lengths, device list and IS certificate parameters. We can check together, against the official specification, whether the terminators, spur derating and power budget match.