PROFIBUS PA is the process-automation branch of PROFIBUS. Its physical layer uses the MBP transmission of IEC 61158-2 (Manchester Coded, Bus Powered), carrying both power and 31.25 kbit/s digital communication on one shielded twisted pair, with native support for the FISCO intrinsic-safety concept. Based on the official system description of PI (PROFIBUS & PROFINET International) and field-device manuals, this article sets out the segment topology and the calculation basis for segment length and device count, together with the constraints in intrinsically safe areas. Every figure carries its source; the final engineering basis is the standard text, official data sheets and the loop calculation.

I. Technical Positioning and Standards

ItemContent
Protocol roleProcess Automation branch of PROFIBUS (PA), master/slave structure; the PA Profile standardizes device classes and parameters
Physical layerMBP (Manchester Coded, Bus Powered), IEC 61158-2 Type 1; communication and power share one shielded twisted pair
Rate and codingFixed 31.25 kbit/s, zero-mean Manchester II coding, signal amplitude ±9 mA
TopologyTrunk plus spur in line/tree/star combinations; field devices connect via spurs
Explosion protectionMBP-IS version for hazardous areas, using FISCO or Entity intrinsic-safety models; live maintenance possible
Main standardsIEC 61158-2 (physical layer), IEC 61784-1 (communication profile), PA Profile 3.x, IEC 60079-11 (intrinsic safety)

Obtained via web search. Source: PI official "PROFIBUS System Description - Technology and Application" https://uk.profibus.com/fileadmin/media/downloadsection/PROFIBUS_Systembeschreibung_ENG_web.pdf (MBP up to 32 nodes per segment, 31.25 kbit/s, max 1900 m per segment, Type A cable impedance 80-120 ohm, loop resistance ≤44 ohm/km). IEC 61158-2 is the standard number.

Positioner illustration, not the actual device
Positioner illustration, not the actual device; parameters subject to the official data sheet

II. MBP Physical-Layer Key Parameters

ParameterValue / requirementNotes
Data rate31.25 kbit/s (fixed)PA side always runs at this rate; not the variable rate of DP
CodingManchester II, zero mean±9 mA current-mode overlay, near-zero DC component
Nodes per segmentUp to 32Includes active nodes such as couplers/supplies; realistically limited by supply current
Min. operating voltage9 V DC at deviceBelow this value the device may drop out of communication
Min. current consumption10 mA per deviceSegment supply capacity must exceed the sum of all device maximum currents
Type A cableImpedance 80-120 ohm, loop resistance ≤44 ohm/km, capacitance ≤2 nF/m, core ≥1 mm2Type A shielded twisted pair recommended for new installations
Terminator100 ohm + 1 uF (or active IEC 61158-2 terminator)One at each physical end of the trunk; never terminate a spur

Obtained via web search. Source: PI official "PROFIBUS System Description", Tables 1 and 3 (https://uk.profibus.com/fileadmin/media/downloadsection/PROFIBUS_Systembeschreibung_ENG_web.pdf); example field-device data from the SAMSON Type 3730-4 data sheet (IEC 61158-2 fieldbus interface, bus-powered, FISCO device, 15 mA maximum operating current). Subject to the latest original data sheet.

III. Segment Length and Device Count Calculation

Calculation basis: total length budget of one segment = trunk length + sum of all spur lengths. For Type A cable the non-IS trunk limit is 1900 m; for intrinsically safe (Ex ia IIC) applications the trunk limit is 1000 m and the spur limit 30 m (IIB may allow 120 m). The device count N is subject to two constraints at once: N ≤ 32 (address/node ceiling), and the sum of device currents ≤ available segment current. Therefore 32 is a protocol ceiling, not a guaranteed number of simultaneously powered devices; each device must be accumulated from its data-sheet current.

ConstraintValueCalculation note
Maximum trunk length1900 m (non-IS, Type A cable)All spurs count toward the total length budget
Hazardous-area trunk1000 m (IIC)Ex ia applications use FISCO/Entity certificate parameters
Spur length30 m (IIC) / 120 m (IIB)Take the stricter value from the device manual and Ex certificate
Node count≤ 32 per segmentPer-station current consumption sets the realizable count
RepeatersCan extend the trunkExtension capability subject to the coupler/link manual
Mixed cableCalculate by length fraction of each typeMixed cable types require a fractional budget, subject to the official installation guide

Segment and spur figures from GE Energy "FVP 110 Fieldbus Valve Positioner Manual" (cable R' 15-150 ohm/km, L' 0.4-1 mH/km, C' 80-200 nF/km; spur 30 m IIC / 120 m IIB; trunk 1 km IIC / 1.9 km IIB); 1900 m and 32 nodes from the PI official system description (URL in the previous source). These are general rules; the standard text, device manual and loop calculation prevail.

IV. Intrinsically Safe Segment Design

ModelApplicability and constraintsCalculation point
FISCOSingle IS supply plus FISCO-compliant field devicesOnce model parameters are met, no per-segment calculation is normally needed; terminators must be Ex certified and fail-safe
EntityBarrier and device parameters matched item by itemPo ≤ Pi, Uo ≤ Ui, Io ≤ Ii; C_cable ≤ Co - sum(Ci), L_cable ≤ Lo - sum(Li)
TerminatorResistance 90-100 ohm, capacitance 0-2.2 uFResistor must be fail-safe per IEC 60079-11; one of the two may be integrated in the bus supply
Shield groundingSingle-end groundingNormally grounded at the supply/control-room end to avoid ground loops

FISCO and Entity are the two recognized models for intrinsically safe fieldbuses, both within the IEC 60079-11 framework. Design starts by confirming the zone (Zone 0/1/2 or Div 1/2) and gas group (IIC/IIB), then selecting the corresponding certificate parameters. Different protection concepts (Ex ia intrinsic safety is NOT Ex d flameproof) must never be mixed; when an approval cannot be found, state "unable to confirm, please verify with the manufacturer".

Obtained via web search. Source: PI official system description, FISCO section, and GE Energy "FVP 110 Fieldbus Valve Positioner Manual" Entity/FISCO parameter tables (terminator R = 90-100 ohm, C = 0-2.2 uF); IEC 60079-11 is the intrinsic-safety standard number.

V. Selection Guide and Common Configurations

Selection guide: first fix the coupling method to the control system (DP/PA coupler for transparent coupling, or DP/PA Link with rate conversion); next set the IS model by area classification (FISCO preferred, Entity calculation when needed); then verify trunk-plus-spur length and total device current; finally confirm the two terminators and single-end shield grounding. When the length approaches the limit, shorten spurs, reduce nodes or split the segment rather than compensating with a higher supply voltage. All parameters are subject to the IEC 61158-2 standard text, PI installation guides and the specific device/coupler manual.

Common configurations: a typical PA segment consists of a DP/PA coupler (or Link), Type A shielded twisted-pair trunk, several spurs with PA smart devices (e.g. valve positioners, pressure/temperature transmitters), and terminators at both trunk ends; hazardous areas use a FISCO IS supply and certified field devices. Realistic device counts are often far below the ceiling of 32 because of the current budget.

If you are planning a PA segment, or want to check the match between segment length, spurs, device count and the IS model, please send us the topology sketch, device list and area classification. We can work through the current budget and length budget item by item against the official installation guide.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.