Home » Service & Support » Technical Documentation
Azbil AVP300 / AVP301 Smart Positioners - Technical Data & Selection
Release time:2026-11-25 12:00:52 | Views:

azbil AVP300/AVP301 are smart electro-pneumatic valve positioners of the SVP3000 Alphaplus 300 series, using microprocessor control and auto-setup with IS and flameproof versions. The AVP300 is a pure positioning type (no feedback, no HART); the AVP301 adds 4-20 mA valve-position transmission (position feedback) on the AVP300 basis; neither includes HART communication (HART versions are AVP302/307). This article organizes the technical data, model structure, Ex protection and selection of AVP300/AVP301 based on azbil official data sheets; the differences are distinguished item by item, and specific parameters are subject to the official catalogue and nameplate.

I. Product Positioning

ItemContent
Brandazbil (independent brand, not to be mixed with Honeywell)
SeriesSVP3000 Alphaplus 300 series smart electro-pneumatic valve positioners
AVP300Smart type, no position feedback, no HART (pure positioning)
AVP301AVP300 + 4-20 mA valve-position transmission (position feedback), no HART
Control principleMicroprocessor control, auto-setup; one model configures single/double acting, split range and flow characteristics by software
Main documentsazbil official data sheets SS4-AVP300-0100, SS4-AVP301-0100, etc.

Source: azbil official data sheets SS4-AVP300-0100 (4th edition), SS4-AVP301-0100; parameters subject to the official data sheets.

Product illustration
Digital positioner illustration, not the actual model; parameters subject to the official catalogue

II. Main Technical Data (AVP300 / AVP301)

ParameterAVP300AVP301
Input signal4-20 mA DC, min drive current 3.84 mA, split-range capableSame as AVP300
Input impedanceabout 300 ohm (weatherproof/flameproof 300 ohm, IS 350 ohm by version)Same as AVP300
ProtocolNo HART (SFN setup)No HART (SFN setup)
Position feedbackNone4-20 mA valve-position transmission, accuracy +/-1% F.S.
ActuatorsSingle/double acting (double acting needs reversing relay), linear/rotarySame as AVP300
Travel14.3-100 mm (feedback lever +/-4 deg to +/-20 deg)Same as AVP300
Air supply140-700 kPaSame as AVP300
Air consumption (single)4/5/6 Nl/min @140/280/500 kPaSame as AVP300
Accuracy+/-1% F.S. (custom +/-2.5%; 4-8 mA span +/-1.5%)Same as AVP300, transmission +/-1% F.S.
ProtectionJIS C0920 / NEMA 4X / IP66Same as AVP300
Ambient temperature-40 to 80 degC (Flameproof/IS graded per certificate)Same as AVP300
SILSIL 3 capable (certificate SIL-8602566)Same as AVP300

Source: azbil official data sheets SS4-AVP300-0100, SS4-AVP301-0100 and "Azbil AVP Selection Update (2026-11)"; current 20th-edition code changes subject to the latest official catalogue.

III. Model Structure and Version Changes

ItemDescriptionNote
Fixed model (old)AVP300-RSD3A-XXXX-X / AVP301-RSD3A-XXXX-XR=CCC flameproof+IS, S=standard coating, D=direct acting, 3=300<Ps<=400 kPa, A=kPa
Fixed model (current 20th ed.)AVP30x-RAD3A-XXXX-XCoating position changed S/B/D to A/C/D; whether old RSD3A is still accepted needs manufacturer confirmation
Standard colour changeFrom dark blue to silver/dark grey100 series remains dark blue
Input impedance refinedAVP300/301 weatherproof/flameproof 300 ohm, IS 350 ohmPer current data sheet
Special modelAnything outside the fixed-model list is quoted as specialAVP200/201/202 remote type has no fixed model

Source: azbil official data sheets SS4-AVP300-0100, SS4-AVP301-0100; code changes subject to the latest official catalogue and ordering tool.

IV. Ex Protection and Electrical Data

ItemAVP300/301Notes
Flameproof markingEx d IIC T6 GbCurrent data sheet specifies CCC flameproof + IS
IS markingEx ia IIC T4 Ga; dust Ex ia IIIC T200 135 degC DaDust Ex added in current version
IS input circuitUi=30 V, Ii=100 mA, Pi=1 W, Ci=5 nF, Li=0.22 mHIS loop requires a safety barrier
Electrical connectionG1/2, 1/2 NPT or M20x1.5Per ordering code
Air connectionRe1/4 or 1/4 NPTPer ordering code

Ex ia intrinsic safety is NOT Ex d flameproof and must be strictly distinguished; AVP300/301 are available in IS or flameproof versions, verified by zone classification and certificate when ordering. If an approval cannot be found, state "unable to confirm, please verify with the manufacturer".

Source: azbil official data sheets and embedded CCC certification information; IS/flameproof markings subject to nameplate and certificate.

V. Selection Points and Precautions

DimensionSelection directionCheck items
Feedback needFor independent 4-20 mA position feedback choose AVP301; positioning only choose AVP300HART versions are AVP302/307
Acting formSingle acting standard; double acting adds reversing relayActuator acting form
Travel typeLinear standard lever; rotary with bracket14.3-100 mm / +/-4 deg to +/-20 deg
Ex protectionIS Ex ia or flameproof Ex dEx ia is NOT Ex d; barrier parameters
Bracket and optionsSelect bracket code by actuator brand, add feedback/switch options as neededFull code per official ordering tool

The core difference between AVP300 and AVP301 is only the position feedback (transmission); other positioning parameters are essentially the same; AVP302/307 are the HART versions. Do not mix these models, and do not mix with the remote AVP200/201/202.

Source: azbil official data sheets and "Common Smart Positioner Selection Logic"; model differences subject to the official catalogue.

VI. Selection Guide and Common Models

Selection guide: First define the feedback need (AVP300 no feedback / AVP301 with 4-20 mA transmission), HART needs go to AVP302/307; then determine configuration and bracket by actuator acting form and linear/rotary travel, then select IS or flameproof by zone, and finally generate the full code with the official ordering tool. Note the 20th-edition changes in coating position and colour; whether old code RSD3A is still accepted needs manufacturer confirmation. Ex ia intrinsic safety is NOT Ex d flameproof and must never be mixed; if an approval cannot be found, state "unable to confirm, please verify with the manufacturer".

Common models: AVP300-RSD3A-XXXX-X (old) / AVP300-RAD3A-XXXX-X (current), AVP301-RSD3A-XXXX-X (old) / AVP301-RAD3A-XXXX-X (current). Related HART models AVP302, AVP307; remote type AVP200/201/202. Specific ordering codes and parameters subject to the azbil official catalogue and nameplate.

If you are selecting an azbil positioner or verifying the feedback and Ex configuration of AVP300/301, please send us the actuator, signal and zone requirements. We can review the model and ordering code together against the official catalogue.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.