The SAMSON 3730-3 is a HART-enabled 4-20 mA two-wire smart electropneumatic positioner, with HART FSK superimposed on the setpoint loop. Host systems can read valve position (controlled variable x), setpoint w, output signal pressure y and device status; the 3730-6 additionally reads supply and output pressure. This article covers HART physical-layer parameters, readable process variables, host software and configuration points based on the official data sheet and operating instructions; HART command numbers and variable mappings are subject to the device description DD/DTM and are not guessed.

I. Product Positioning

ItemContent
BrandSAMSON (independent brand)
Model3730-3 (HART) is the common version; 3730-4 PROFIBUS PA and 3730-5 FF are other bus versions
Communication principleHART FSK superimposed on the 4-20 mA loop; a handheld communicator or a PC with an FSK modem can establish communication
Readable quantitiesValve position x, setpoint w, output signal pressure y and device status; 3730-6 adds supply and output pressure
Device descriptionA Device Description (DD/EDD) or DTM matching the firmware is required; DTM specification 1.2
Main documentsSAMSON data sheet T 8384-3 EN, 3730-3 operating instructions, T 8384-6 EN, NA 0122

Source: SAMSON official data sheet T 8384-3 EN and the 3730-3 operating instructions, Communication chapter; HART command numbers subject to the DD/DTM and not guessed here.

SAMSON 3730 series positioner illustration
SAMSON 3730 series positioner illustration, same-series reference; parameters subject to the official data sheet

II. HART Physical Layer and Loop Parameters

ParameterValue / requirement
Input signal4-20 mA, two-wire, reverse polarity protection; minimum span 4 mA
Minimum current3.6 mA for display; 3.8 mA for operation
Load impedanceUp to 8.2 V (equivalent to about 410 ohm at 20 mA)
HART frequency-range impedanceReceiving 350-450 ohm; sending about 115 ohm
Static destruction limit100 mA
Electrical connectionOne M20x1.5 cable gland (6-12 mm clamping range), second connection optional; screw terminals for 0.2-2.5 mm2 wire
Degree of protectionIP66 / NEMA 4X

The loop must maintain sufficient compliance voltage at 20 mA and keep the HART frequency-range impedance within 350-450 ohm, otherwise communication may become unstable. IS loops also require barrier and cable constant calculations.

Source: SAMSON official data sheet T 8384-3 EN Technical data table; loop calculation subject to the official manual and loop calculation sheet.

III. Process Variables and Readable Quantities

VariableMeaningSource / note
Controlled variable xValve stem travel or rotation angle (position feedback)Measured by a wear-free travel sensor; LCD shows percent
Setpoint w0-100% setpoint corresponding to the 4-20 mA signal from the control systemReadable on the LCD and in the host
Output variable ySignal pressure sent to the actuatorSoftware limit to 1.4 / 2.4 / 3.7 bar +/-0.2 bar possible
Device statusNE 107 classified status and device alarmsGenerated by EXPERTplus diagnostics and uploadable over HART
Pressure valuesSupply pressure and output pressureAvailable only on the 3730-6 with integrated pressure sensors
Discrete valuesSoftware limit switches, fault alarm, binary input statusConfigurable as HART-readable statuses

The 3730-5 FF data sheet lists function blocks PID, AO, MAO, MAI, 2xDO and 2xDI as a modular description; the exact HART mapping is subject to the device description.

Source: SAMSON official data sheet T 8384-3 EN, 3730-3 operating instructions and 3730-5 data sheet; command numbers and variable mappings subject to the DD/DTM.

IV. Host Software and Device Description

ToolPurposeRequirement
HART handheld communicatorRead process variables, configure and diagnose in the fieldLoad the Device Description for Type 3730-3
TROVIS-VIEWLocal parameterization and diagnostics via the SSP interfaceRequires database module 3730-3
DTM / FDT frameworkIntegration into FDT/DTM frameworks such as PACTwareDTM specification 1.2; other integrations (AMS, PDM) available
eDDL / DDIntegration into asset management and control systemsDevice description version must match the firmware; see the SAMSON website Device Revision assignment
SSP interfaceLocal digital interface to a PC via RS-232/USB adapterUsed for TROVIS-VIEW configuration

Source: SAMSON official data sheet T 8384-3 EN, rows Communication (local) / (HART) and Software requirements; software versions subject to the SAMSON website download area.

V. Configuration and Diagnostic Reading

ItemKey point
Parameter accessAll parameters accessible over HART and via the local single-knob menu; parameters are listed in one LCD level
InitializationThe INIT key starts autotune based on pre-set parameters; closed-loop operation starts on completion
CharacteristicLinear / equal percentage / reverse equal percentage, user-defined via operating software and communication
Zero monitoringAutomatic zero monitoring gives an indication on drift; tight-closing function can be set
Diagnostic statusEXPERTplus generates diagnostic and status messages classified per NE 107
Fail direction0 mA setpoint with optional solenoid enables emergency venting, SIL 2 (single device HFT=0) or SIL 3 (redundant HFT=1)

Source: SAMSON official data sheet T 8384-3 EN, 3730-3 operating instructions and 3730-5 data sheet Special features; thresholds and SIL configuration subject to the certificate and manual.

VI. Selection Guide and Common Models

Selection guide:First set the model by protocol (3730-3 for HART, 3730-4 for PROFIBUS PA, 3730-5 for FF), then confirm that the host has a matching DD/EDD or DTM, and finally fill the diagnostics (P8=4 for EXPERTplus) and additional-equipment digits. To read supply and output pressure select the 3730-6 (14-digit code); do not promise pressure monitoring on the 3730-3. Ex ia intrinsic safety is NOT Ex d flameproof; unverified approvals must be stated as "unable to confirm, please verify with the manufacturer".

Common models:3730-3 (HART, common), 3730-6 (HART with pressure monitoring), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3731-3 (HART flameproof). HART command numbers and process variable mappings subject to the DD/DTM.

If you are configuring HART communication or reading process variables on a 3730, please send us the device firmware version, host system (such as PACTware or AMS) and ordering code. We can review loop parameters and device description matching together against the official data sheet.