| SAMSON 3730 - HART Communication Parameters & Process Variable Reading | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-25 12:00:52 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The SAMSON 3730-3 is a HART-enabled 4-20 mA two-wire smart electropneumatic positioner, with HART FSK superimposed on the setpoint loop. Host systems can read valve position (controlled variable x), setpoint w, output signal pressure y and device status; the 3730-6 additionally reads supply and output pressure. This article covers HART physical-layer parameters, readable process variables, host software and configuration points based on the official data sheet and operating instructions; HART command numbers and variable mappings are subject to the device description DD/DTM and are not guessed. I. Product Positioning
Source: SAMSON official data sheet T 8384-3 EN and the 3730-3 operating instructions, Communication chapter; HART command numbers subject to the DD/DTM and not guessed here.
II. HART Physical Layer and Loop Parameters
The loop must maintain sufficient compliance voltage at 20 mA and keep the HART frequency-range impedance within 350-450 ohm, otherwise communication may become unstable. IS loops also require barrier and cable constant calculations. Source: SAMSON official data sheet T 8384-3 EN Technical data table; loop calculation subject to the official manual and loop calculation sheet. III. Process Variables and Readable Quantities
The 3730-5 FF data sheet lists function blocks PID, AO, MAO, MAI, 2xDO and 2xDI as a modular description; the exact HART mapping is subject to the device description. Source: SAMSON official data sheet T 8384-3 EN, 3730-3 operating instructions and 3730-5 data sheet; command numbers and variable mappings subject to the DD/DTM. IV. Host Software and Device Description
Source: SAMSON official data sheet T 8384-3 EN, rows Communication (local) / (HART) and Software requirements; software versions subject to the SAMSON website download area. V. Configuration and Diagnostic Reading
Source: SAMSON official data sheet T 8384-3 EN, 3730-3 operating instructions and 3730-5 data sheet Special features; thresholds and SIL configuration subject to the certificate and manual. VI. Selection Guide and Common ModelsSelection guide:First set the model by protocol (3730-3 for HART, 3730-4 for PROFIBUS PA, 3730-5 for FF), then confirm that the host has a matching DD/EDD or DTM, and finally fill the diagnostics (P8=4 for EXPERTplus) and additional-equipment digits. To read supply and output pressure select the 3730-6 (14-digit code); do not promise pressure monitoring on the 3730-3. Ex ia intrinsic safety is NOT Ex d flameproof; unverified approvals must be stated as "unable to confirm, please verify with the manufacturer". Common models:3730-3 (HART, common), 3730-6 (HART with pressure monitoring), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3731-3 (HART flameproof). HART command numbers and process variable mappings subject to the DD/DTM. If you are configuring HART communication or reading process variables on a 3730, please send us the device firmware version, host system (such as PACTware or AMS) and ordering code. We can review loop parameters and device description matching together against the official data sheet. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |