SAMSON positioner diagnostics span four platforms: 3725, 3730, 3731 and 3730-6. EXPERT / EXPERTplus provides control-valve expert diagnostics, statuses are classified per NAMUR NE 107, and alarms are passed to host systems through software limit switches, a fault alarm contact, binary outputs and HART. This article covers diagnostic tiers, NE 107 statuses, sample 3725 fault codes, alarm channels and threshold configuration based on official data sheets and manuals; event codes and reset methods are subject to the respective manuals.
I. Product Positioning
| Item | Content |
|---|
| Brand | SAMSON (independent brand) |
| Models covered | 3725 (basic digital), 3730-0/1/2/3/4/5, 3730-6 (pressure monitoring), 3731-3/3731-5 (flameproof) |
| Diagnostic platforms | EXPERT (standard), EXPERTplus (advanced, including partial stroke test), 3730-6 pressure monitoring |
| Status classification | NAMUR NE 107: Failure / Out of Specification / Maintenance Required / Check Function |
| Alarm channels | HART device status, two software limit switches, one fault alarm contact, binary output, LCD |
| Main documents | T 8394 EN, T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8389, NA 0122 |
Source: SAMSON official data sheets T 8394 EN, T 8384 series, T 8387 series, T 8389 and NE 107 recommendation; specific diagnostic functions subject to the respective manuals.

SAMSON 3730 series positioner illustration, same-series reference; parameters subject to the official data sheet
II. Diagnostic Tiers
| Model / tier | Diagnostic content | Note |
|---|
| 3725 | Initialization, zero calibration, fault codes E0-E15 | Basic digital positioner, 10-digit ordering code |
| 3730-0 | No microprocessor, purely mechanical control | No digital diagnostics |
| 3730-1 / 3730-2 | LCD, autotune; 3730-2 with EXPERTplus | No communication (3730-2 supports parameterization and diagnostics) |
| 3730-3 / 3730-4 / 3730-5 | EXPERT / EXPERTplus (P8=4 for EXPERTplus), NE 107 statuses | HART / PROFIBUS PA / FF communication |
| 3730-6 | Supply and output pressure monitoring added to the 3730-3 platform | 14-digit code, supports pressure-related alarms |
| 3731-3 / 3731-5 | EXPERTplus including partial stroke test, flameproof enclosure | 15-digit article code with a separate position table |
Source: SAMSON official data sheets T 8394 EN, T 8384-3/4/5/6 EN, T 8387-3/5 EN and T 8389; tier codes subject to the official selection tool.
III. NE 107 Status Classification
| Status | Meaning | Typical trigger |
|---|
| Failure | Device function failed, output not trustworthy | Internal software/hardware fault, travel signal failure |
| Out of Specification | Operation outside specified conditions | Supply pressure out of range, abnormal output pressure, travel limit |
| Maintenance Required | Planned maintenance needed | Increased friction, changed time-near-closed, travel accumulator limit |
| Check Function | Diagnostics running or result pending | Initialization or partial stroke test in progress |
Source: NAMUR NE 107 classification and the "Classified status alarms acc. to NAMUR NE 107" item in SAMSON 3730/3731 data sheets; status-to-event mapping subject to the official manual.
IV. Sample Fault Event Codes (3725)
| Code | Meaning | Corrective direction |
|---|
| E0 | Zero error, zero drift over 5% of initialized value | Check mounting and seat wear, run P16 zero calibration or clear the code |
| E1 | Displayed value inconsistent with initialization, parameters changed after initialization | Restore parameters or re-initialize with P15 |
| E2 | Positioner not initialized | Set parameters then run P15 initialization |
| E3 | Wrong Kp setting, positioner oscillates | Check air flow adjustment, limit Kp at P8 and re-initialize |
| E4 | Actuation time too short (below 0.5 s) | Check air flow adjustment and re-initialize |
| E5 | Cannot detect, supply pressure too low or unstable | Check air supply and mounting, then re-initialize |
| E6 | Travel not reached during initialization | Check air supply, leakage and travel setting, then re-initialize |
| E7 | Actuator does not move, no air / blockage / signal below 3.7 mA | Check air supply, mounting and mA input |
| E8 | Position signal at low or high limit, wrong pin / feedback lever / mounting direction | Check mounting, clear the code and re-initialize |
| E9 | Internal software fault | Return to SAMSON for repair |
| E10-E15 | Internal hardware device fault | Return to SAMSON for repair |
The codes above are examples from the 3725 manual (per T 8394 EN and its installation instructions). Event codes for the 3730/3731/3730-6 must be taken from their own manuals and must not be interchanged.
Source: SAMSON 3725 installation instructions code table (P0-P20, E0-E15); event codes for 3730/3731 subject to their respective manuals and not guessed here.
V. Alarm Outputs and Threshold Configuration
| Channel | Configuration point |
|---|
| Software limit switches | Two software limit contacts standard on the 3730-3, floating, reverse-polarity protected, configurable switching behaviour; non-Ex conductive about 348 ohm, Ex version at least 2.2 mA |
| Fault alarm contact | One standard fault alarm contact, triggerable by device alarm or limit point |
| Binary input | Active/passive configurable; passive 3-30 V, about 3.7 mA at 24 V; accepts external switch or relay |
| Output pressure limit | Software limit to 1.4 / 2.4 / 3.7 bar +/-0.2 bar to prevent actuator overload |
| Tight-closing function | Full venting or pressurization when the setpoint approaches 0% or 100%, reducing seat erosion |
| Zero monitoring | Automatic zero monitoring gives a maintenance indication on zero drift; threshold subject to the official manual |
Source: SAMSON official data sheet T 8384-3 EN Binary contacts / Technical data and the 3730-5 data sheet Special features; thresholds subject to the device manual.
VI. Selection Guide and Common Models
Selection guide:Choose the platform by diagnostic depth: 3725 for basic initialization and fault codes, 3730-3/4/5 for HART/PA/FF with EXPERTplus, 3730-6 for pressure-related alarms, and 3731-3/3731-5 for flameproof service with PST. Then check alarm channel needs (software limit switches, fault alarm contact, binary input, position transmitter) and fill the corresponding ordering digits. Ex ia intrinsic safety is NOT Ex d flameproof; unverified approvals must be stated as "unable to confirm, please verify with the manufacturer", and event codes and reset methods are subject to the respective manuals.
Common models:3725 (basic digital), 3730-2 (no communication with EXPERTplus), 3730-3 (HART), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring), 3731-3 / 3731-5 (flameproof with PST). Diagnostic digits such as P8=4 subject to the official selection tool.
If you are configuring diagnostics and alarm outputs for an in-service valve, or want to confirm whether a positioner supports EXPERTplus and PST, please send us the model, communication protocol and alarm requirements. We can review diagnostic tiers, alarm channels and thresholds together against the official manual.