Intrinsic safety (Ex ia) and flameproof (Ex d) are different protection concepts and must not be mixed. Fisher FIELDVUE positioners offer intrinsically safe approvals such as ATEX Ex ia (code 1C), IECEx, NEPSI (code 1I) and low-temperature Ex ia (code 1N). An intrinsic safety loop must satisfy energy limits through the safety barrier and field cable parameters together. This article covers loop verification and configuration points; specific values are subject to the official certificates, manuals and standard text. I. Product Positioning
The data in this article was obtained via web search. Source: Emerson DVC6200f page (area classification includes Intrinsically Safe and FISCO; approvals include ATEX, IECEx, NEPSI) https://emerson.com/en/final-control/products/fisher-dvc6200f ; approval codes from Fisher official selection data.
II. Ex ia vs Ex d
Source: IEC 60079-11 / IEC 60079-25 and Fisher official Ex selection data; zoning subject to the device certificate and project specification. If unverifiable, state "unable to confirm, please verify with the manufacturer". III. Loop Parameter Verification
All five conditions must be satisfied at once, and cable distributed capacitance and inductance must be counted by actual length. Fisher positioner Ui/Ii/Pi/Ci/Li values are subject to the official certificate or nameplate; no specific numbers are listed here. Source: IEC 60079-11 / IEC 60079-25 IS loop verification principles; Fisher values subject to the official certificate and manual. IV. DVC6200 IS Configuration Points
Source: Fisher FIELDVUE official selection data (approval codes and seal options); HART passthrough and loop load subject to barrier vendor data and the site loop calculation. V. Installation and Commissioning
Source: IEC 60079-25 loop design and installation principles and Fisher official manual; site work subject to project specification and loop calculation. VI. Selection Guide and Common ModelsSelection guide: Define area classification and approval system first, then choose the Fisher positioner with the matching IS approval code. Select a barrier by checking Ui/Ii/Pi/Ci/Li with cable parameters and verify Uo <= Ui, Io <= Ii, Po <= Pi, Co >= Ci+Cc and Lo >= Li+Lc. Ex ia intrinsic safety is not Ex d flameproof and must never be mixed; if an approval cannot be found, state "unable to confirm, please verify with the manufacturer". All electrical values are subject to the official certificate and manual. Common models: DVC6200H (HART with IS option), DVC6200F (FF with FISCO IS), DVC6200P (PROFIBUS PA IS) and DVC6200 SIS; approval codes subject to the order and nameplate. If you are configuring an intrinsically safe positioner loop for a hazardous-area valve, please provide the area classification, approval system, cable length and barrier model. We can check parameter matching against official certificates and loop calculation practice, keeping Ex ia and Ex d strictly separate. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |