Home » Products » Fisher
Fisher Type 63EGLP-16 Pilot-Operated Relief Valve
Fisher Type 63EGLP-16 Pilot-Operated Relief Valve
Fisher Type 63EGLP-16 Pilot-Operated Relief Valve

Fisher Type 63EGLP-16 Pilot-Operated Relief Valve

The Fisher FIELDVUE DVC6200 instrument allows for your operation to run closer to setpoint, improving product quality with more accurate control. Using FIELDVUE Performance Diagnostics, valve operation is monitored online to evaluate performance and reliability.

Details

1. Product Overview

The Fisher Type 63EGLP-16 is a pilot-operated relief valve designed for vapor service on LP-Gas and anhydrous ammonia storage tanks at bulk plants. It is a distinct model from the general-purpose Type 63EG and must not be confused with it.

The valve uses a main valve with two Type 6358EBLP or 6358EBHLP pilots, which allows one pilot to be serviced or checked while the other remains in service. It is available in UL or ASME Section VIII Division I configurations.

The capacity of the 63EGLP-16-250 configuration is quoted as 10,540 SCFM of air. The valve provides linear flow characteristics and is suitable for vapor service only.

Above: product appearance / manufacturer literature image.

2. Technical Description

Dual pilot: Two pilots allow maintenance or set point verification without venting the tank.

Vapor only: Designed for vapor service on LP-Gas and anhydrous ammonia tanks.

Set pressure definition: For UL versions set point is pilot start-to-discharge; for ASME versions it is main valve start-to-discharge.

Linear characteristic: Main valve flow characteristic is linear, with flow upward through the seat ring and out through the cage.

NBR temperature: -20 to 180 F / -29 to 82 C; performance at -40 F / -40 C start-to-discharge and reseal has been tested.

Distinct from 63EG: The 63EGLP is a bulk plant tank relief valve; the 63EG is a general relief / backpressure valve and is not an ASME safety relief valve.

Source: Fisher Pressure Regulator Technical Data Supplement, Volume 03 - Backpressure, Relief and Vent Valves; official Type 63EGLP-16 Relief Valve Instruction Manual D450319T012.

3. Main Technical Specifications

ParameterSpecification / Description
Valve typePilot-operated relief valve for vapor service
Main valve sizesNPS 4 / DN 100 CL300 RF and 2 MNPT configurations per the manual
Port diameterNPS 4 CL300 RF 4.38 in / 111 mm; 2 MNPT 2.38 in / 60 mm
PilotsTwo Type 6358EBLP or 6358EBHLP pilots
Maximum relief (inlet) pressure400 psig / 27.6 bar including build-up
Maximum differential pressure400 psig / 27.6 bar
Minimum differential for full travelNPS 4 / DN 100 about 55 psig / 3.8 bar; 2 MNPT about 90 psig / 6.2 bar
Relief set pressure ranges85-140, 130-200, 180-350 and 250-375 psig / 5.9-9.7, 9.0-13.8, 12.4-24.1 and 17.2-25.9 bar
Capacity63EGLP-16-250 about 10,540 SCFM air (UL and ASME Section VIII Division I)
Main valve materialWCB steel body, CF8M stainless body flange, heat-treated 416 stainless cage, seat ring and plug
SealingPTFE piston ring and NBR O-rings and seals
Plug travelNPS 4 about 2.00 in / 51 mm; 2 MNPT version about 1.13 in / 29 mm
Approximate weightNPS 4 about 178 lb / 81 kg; 2 MNPT about 55 lb / 25 kg, including pilots
CertificationsUL or ASME Section VIII Division I versions per order and nameplate; Per order and certificates; verify with the manufacturer / refer to official manual
Source: Fisher Pressure Regulator Technical Data Supplement, Volume 03 - Backpressure, Relief and Vent Valves; official Type 63EGLP-16 Relief Valve Instruction Manual D450319T012.

4. Selection Guide

Selection sequence: Service -> Certification -> Set pressure -> Size and connection -> Pilots.

StepItemKey point
1ServiceConfirm vapor-only LP-Gas or anhydrous ammonia tank relief duty
2CertificationChoose the UL or ASME Section VIII Division I version required by the installation
3Set pressureSelect the spring range among 85-140, 130-200, 180-350 and 250-375 psig
4Size and connectionChoose NPS 4 CL300 RF or 2 MNPT and verify port diameter and capacity
5PilotsConfirm the dual pilot arrangement and which pilot is online for service

Boundary: Set pressures, capacities and approvals follow the official manual; the 63EGLP is not interchangeable with the general 63EG without verification.

Source: Fisher Pressure Regulator Technical Data Supplement, Volume 03 - Backpressure, Relief and Vent Valves; official Type 63EGLP-16 Relief Valve Instruction Manual D450319T012.

5. Complete Model Enumeration

ModelConfigurationDescription
63EGLP-16 NPS 4CL300 RFPilot-operated vapor relief valve, NPS 4 / DN 100
63EGLP-16 2 MNPTThreadedPilot-operated vapor relief valve with 2 MNPT inlet
63EGLP-16-250High set pointConfiguration with 10,540 SCFM air capacity
63EGDifferent modelGeneral relief / backpressure valve, not an ASME safety relief valve

6. Related Models

Related modelDescription
Type 63EGGeneral pilot-operated relief / backpressure valve for gas or liquid
Type 1098-63EGRLower-pressure relief valve using a Type 6358B pilot
Type 630RGeneral-purpose relief valve for compressor and plant service
Type H124Hydrostatic relief valve for liquid-filled sections

7. Common Spare Parts

Spare partDescription
Pilot repair kitSeat, plug, spring and seals for 6358EBLP or 6358EBHLP
Main valve trim kitSeat ring, cage and plug components
Elastomer kitNBR piston ring and O-ring set
Relief springSpring for the selected set pressure range

8. Accessories

AccessoryDescription
Pilot isolation valvesAllow one pilot to be serviced while the other stays online
Vent lineRoutes relief discharge to a safe location
Pressure gaugeTank and pilot pressure indication
Test connectionConnection for set point verification

9. Disclaimer

The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.

10. Sources & Contact

Source: Fisher Pressure Regulator Technical Data Supplement, Volume 03 - Backpressure, Relief and Vent Valves; official Type 63EGLP-16 Relief Valve Instruction Manual D450319T012.

We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Application area

Energy

Energy

Chemical Industry

Chemical Industry

Mining Industry

Mining Industry

Pharmaceutical Industry

Pharmaceutical Industry

Water treatment industry

Water treatment industry