Localization of imported control valves is not a one-to-one model mapping but an evaluation process based on service conditions, interfaces, performance, certification and life-cycle cost. This article provides only a selection evaluation framework; it lists no specific imported-to-domestic model correspondences and invents no substitution parameters. The final decision still follows the official data sheet, nameplate and project technical agreement. I. Evaluation Framework and Basic Principles
The first step in localization is to establish a performance baseline of the original valve, not to search for a similar model first. List requirements item by item from the original data sheet, nameplate, drawings and in-service test records, then compare candidates item by item. Where any item cannot be confirmed, state 'please verify with the manufacturer' rather than filling in an assumed value. The data in this article was obtained via web search. Source: IEC 60534 series of control valve standards; general engineering evaluation practice; subject to the official data sheets and project technical agreement.
II. Process and Performance Baseline
Performance must be compared at the same size, differential pressure and medium; otherwise a single catalog number is not comparable. Leakage class is checked by the test methods of IEC 60534-4 or ANSI/FCI 70-2; dead band and response time are confirmed using the test environment descriptions in IEC 61514-2 or ISA-75.25.01. The data in this article was obtained via web search. Source: IEC 60534-4:2021, ANSI/FCI 70-2, IEC 61514-2:2026, ANSI/ISA-75.25.01-2024, JIP33 S-729; subject to the original standards. III. Interface and Mounting Dimension Check
Interface dimensions are the most underestimated part of localization. Even when Cv and characteristic match, different face-to-face dimensions, flange facings or actuator mounting surfaces force field modification. Check each item with dimension drawings or 3D models during detailed design and record differences in the construction plan. The data in this article was obtained via web search. Source: ASME B16.10, EN 558, ASME B16.5, EN 1092-1, IEC 60534-6, VDI/VDE 3845; subject to the original standards and official dimension drawings. IV. Reliability, Certification and Supply Risk
Certifications cannot rely on verbal commitments: Ex ia intrinsic safety and Ex d flameproof are different protection concepts with different certificates and installation rules; if not found, state 'unable to confirm, please verify with the manufacturer'. For SIL loops, the substitute must provide corresponding functional safety data and a safety manual, and safety verification must be repeated. The data in this article was obtained via web search. Source: ASME B16.34, ISO 15848-2, ANSI/FCI 91-1, IEC 60079 series, IEC 61508/61511, GB/T 4213; subject to the original certificates and standards. V. Evaluation Workflow and Checklist
Use a phased decision: complete the baseline and pre-screening first, then perform detailed comparison and sample verification only on shortlisted candidates, avoiding early arguments over specific models. The conclusion should state unconfirmed items and residual risks and be signed by process, instrumentation, safety and procurement. Important note: this article provides no specific imported-to-domestic model correspondence and no unverified parameters. All substitutions must be determined by the project technical agreement, official data sheets and field verification; any item that cannot be found must be stated as 'subject to the official manual/nameplate' or 'please verify with the manufacturer'. The data in this article was obtained via web search. Source: IEC 60534 series, IEC 60534-4:2021, ASME B16.34, GB/T 4213, IEC 61508/61511; subject to the original standards and project documents. If you are evaluating localization of an imported control valve, please send us the original data sheet, interface drawings and service data. We can build the baseline and check items one by one using the framework above, without presuming any brand correspondence. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |