A control valve station consists of an upstream block valve, a downstream block valve, a bypass valve and drain points, allowing the control valve to be isolated for maintenance or calibration without shutting down the process. Poor configuration can cause bypass leakage, unstable manual control or defeated safety interlocks. Following ISA RP 75.06 and related engineering practices, this article reviews station functions, bypass and block valve selection, operating sequence and risk control. I. Function and Composition of a Control Valve Station
ISA RP 75.06 describes a control valve station as the control valve, isolating valves, bypass valve and bypass line. Isolation valves are installed on both inlet and outlet sides and use a non-throttling type such as a gate valve; the bypass valve maintains process control when the main valve is inoperable. Engineering documents also recommend that the bypass line be smaller than the main line but not less than half the main line size. The data in this article was obtained via web search. Source: ISA RP 75.06 (Control Valve Stations); M-014 Instruments and Control Systems for Boiler Plants, clause 6.4.4, https://pdhstar.com/wp-content/uploads/2018/12/M-014-Instruments-and-Control-Systems-for-Boiler-Plants-FINAL.pdf ; subject to the original standard.
II. Bypass Valve Selection and Sizing
M-014 recommends that the bypass valve be identical to the control valve except for manual operation, so that the correct Cv and special trim are retained; the bypass line must not be smaller than half the main line. Some engineering sources suggest a bypass Cv of at least 125% of the control valve Cv, but this is a project-specific practice and must follow the project specification and calculation rather than being treated as a universal value. The data in this article was obtained via web search. Source: M-014 clause 6.4.4 (URL above); engineering suggestion on bypass Cv from Industrial Monitor Direct, https://industrialmonitordirect.com/de/blogs/knowledgebase/control-valve-bypass-lines-design-considerations-and-safety-analysis ; subject to the project calculation. III. Block Valve Configuration Requirements
Block valves are for complete isolation, not throttling. In normal operation both valves must be fully open and sealed or locked as required; an ordinary gate valve without locking can be accidentally closed, cutting the main path while the bypass is not in service. For loops involving safety instrumented functions, bypass status must be included in management of change (MOC) and marked on the P&ID. The data in this article was obtained via web search. Source: M-014 clause 6.4.4; ISA RP 75.06; safety-valve isolation guidance from Tangovalve, https://www.tangovalve.com/valve-arrangement-in-industrial-piping-systems/ ; subject to the project procedure. IV. Switching Sequence and Risk Control
The greatest risk is leaving the bypass open: a fully open manual bypass can have several times the flow capacity of the modulating valve, which the PID cannot compensate, causing temperature deviation or interlock action. The bypass should therefore be locked closed, and opening it requires a written procedure and shift-handover confirmation; SIL loops also need a LOPA to confirm the bypass does not weaken the safety function. The data in this article was obtained via web search. Source: Industrial Monitor Direct article on bypass and SIL risk control (URL above); IEC 61511 / ISA-84.00.01; subject to the project operating procedure. V. Selection Guide and Verification Checklist
Selection guide: first confirm whether a bypass is really needed; if redundant valves, VFD slow-start or pre-positioned DCS setpoints can replace it, prefer eliminating the bypass. Where a bypass is required, size the valve and line for maintenance flow, use non-throttling block valves with locking, keep the bypass locked closed with position feedback and alarm, and document the switching procedure. Common practice: when the main valve matches the line size, take the bypass line at 1/2 to 2/3 of the main line; use a manual globe valve or the same valve type for the bypass. Final sizes, Cv and locking method follow the project specification, P&ID and official data sheets; no specific brand or model is designated here. The data in this article was obtained via web search. Source: ISA RP 75.06; M-014 clause 6.4.4; IEC 61511; subject to the original standards and project documents. If you need to verify the bypass capacity, block-valve locking or switching sequence of a control valve station, please send us the P&ID, process flow and maintenance requirements. We can review the station configuration item by item against ISA RP 75.06. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |