Control Valve Fail-safe Modes (FC / FO) - Selection Principles
Release time:2026-11-24 16:01:01 | Views:

The fail-safe position of a control valve - FC (fail closed), FO (fail open) or FL (fail last) - is one of the most important safety items on a P&ID and data sheet. It describes the resting position after loss of air supply or electrical signal, not the direction of travel when air is applied. Following ANSI/ISA-5.1 terminology and official actuator manuals, this article reviews FC/FO selection principles, implementation mechanisms and a verification checklist.

I. Fail-Position Terminology and Standard Definitions

CodeMeaningTypical actuatorTypical application
FCFail closed (valve shuts on loss of air or power)Air-to-open, spring return (stem extends, FA)Tank overfill protection, fuel shutoff
FOFail open (valve opens on loss of air or power)Air-to-close, spring return (stem retracts, FE)Cooling water, relief bypass, combustion air
FLFail last (holds the last position)Double-acting without springs, or balanced trimMaintain condition during a momentary interruption

Critical distinction: the FC/FO mark on a P&ID denotes the fail position, not the air action. An air-to-open valve is closed by its spring on air loss and is marked FC; an air-to-close valve is opened by its spring and is marked FO. SAMSON manuals call these states FA (stem extends, fail-close) and FE (stem retracts, fail-open); the direction of action can be reversed per the mounting instructions.

The data in this article was obtained via web search. Source: ANSI/ISA-5.1 Instrumentation Symbols and Identification, clause 6.7; SAMSON data sheets T 8310-1 and mounting/operating instructions EB 8310-X for Types 3251/3241; subject to the original standard and official manuals.

Illustration, not the exact model
Control valve assembly, illustrative only, not the exact model; parameters subject to the official data sheet

II. How the Fail Position Is Implemented

ImplementationWorking principleApplicable serviceVerification point
Spring return (single-acting)Air moves the diaphragm or piston against the spring; the spring returns the stem on air lossFC or FO with a defined positionSpring range; supply pressure = bench upper limit plus margin
Double-acting without springsBoth chambers are alternately pressurized; no driving force on air lossFL (requires balanced trim)Position drift; coordination with a solenoid valve
Solenoid valve (de-energized action)Pilot valve shifts on power loss to vent or chargeElectrical fail position independent of air supplyDefine energized-open or energized-close
Positioner full ventOutput is vented on signal loss, depressurizing the actuatorSmart positioners such as SAMSON 3730Signal-fail threshold and venting capacity

ABB TZIDC and Siemens SIPART PS2 offer these behaviours as ordering options: TZIDC provides four pneumatic versions (single/double acting x fail-safe venting / fail-lock) and meets IEC 61508 with optional SIL2; SIPART PS2 uses ordering digit 9, where A means fail-safe venting, F fail-in-place and G fail-open charging. Selection must consider the valve, actuator, solenoid valve and signal-failure threshold together, not the positioner alone.

The data in this article was obtained via web search. Source: ABB positioner data sheet DS/TZIDC_ZH_I.pdf REV. I; SIPART PS2 official ordering-code table; SAMSON 3730-3 operating instructions; subject to the official data sheets and manuals.

III. Selecting FC or FO by Process Safety

Process scenarioRecommended fail positionRationaleNote
Tank feed and overfill protectionFCPrevent overflow and release of hazardous materialCoordinate with high-high level interlock
Reactor cooling waterFOKeep cooling on air loss to prevent runaway temperatureCoordinate with cooling pump status
Burner fuel gasFCPrevent accumulation of unburned fuelUsually requires safety integrity verification
Relief or vent bypassFOKeep the relief path available on air lossDistinguish from the safety valve function
Reboiler steamFCPrevent overheating and energy wasteConsider thermal stress and condensate

The fail position must be determined by a process hazard analysis (PHA/LOPA), not inferred from wiring convenience or common practice. Define the fail position of each valve first, then decide the positioner signal direction, solenoid energization and split-range sequence. If neither fail mode is acceptable, consider redundant valves, an air receiver or an independent safety instrumented function rather than a compromise position.

The data in this article was obtained via web search. Source: ANSI/ISA-5.1 fail-position symbols; functional safety requirements IEC 61508 and IEC 61511; subject to the project hazard analysis and safety requirements specification.

IV. Coordination with Positioner and Solenoid Configuration

Configuration itemFunctionCommon optionsVerification point
Signal-fail actionValve position on loss of 4-20 mALow cut-off, above 20 mA alarm, hold last positionFactory default matches project requirement
Solenoid valveElectrical fail position independent of air supplyEnergized-open or energized-close; 3/2 or 5/2De-energized position stated in the data sheet
Supply pressureEnsure the spring can overcome shut-off differentialBench upper limit plus 0.2 bar, at least 1.4 barConfirm by air-failure test
Partial stroke testVerify the safe position is reachablePST with position feedbackDoes not replace a full stroke test

The SAMSON 3730 operating instructions state that emergency action is triggered by the i/p converter or solenoid valve; on supply air failure the positioner fully vents its pneumatic output, the actuator depressurizes and the valve moves to the fail position. Diagnostics, HART communication and position/status feedback remain active except open/closed-loop control. The data sheet should therefore specify both air-supply failure and electrical-signal failure cases.

The data in this article was obtained via web search. Source: SAMSON 3730-3 operating instructions, clause 9.1 Emergency action; ABB DS/TZIDC_ZH_I.pdf REV. I; subject to the official manuals.

V. Selection Guide and Common Configurations

Check itemContent to confirmReference document
Valve body and trimFlow direction, leakage class, shut-off differentialData sheet, IEC 60534-4
ActuatorAction form FA/FE, spring range, bench rangeActuator data sheet
PositionerFail action, signal direction, alarm thresholdsPositioner manual
Solenoid valveDe-energized position, energization, explosion protectionSolenoid valve manual
P&ID and data sheetFC/FO marks consistent; triggering energy statedISA-5.1, project legend

Selection guide: define the fail position from the PHA, then verify the actuator action form (FA/FE) and spring arrangement, confirming that supply pressure meets the bench range with at least 0.2 bar margin. Then align the positioner fail action, solenoid de-energized position and DCS signal-failure strategy in the data sheet. A valve marked FC must be tested on site by air failure to confirm full closure.

Common configurations: a single-acting spring-diaphragm actuator on an air-to-open body gives FC, and on an air-to-close body gives FO; a double-acting piston actuator with a solenoid valve and air receiver can provide FL or a controlled fail action. Products, certifications and test requirements follow the official data sheet, nameplate and project technical agreement; no specific brand or model is designated here.

The data in this article was obtained via web search. Source: ANSI/ISA-5.1; IEC 60534-4:2021; SAMSON EB 8310-X; subject to the official data sheets and project documents.

If you need to check whether a control valve FC/FO mark matches its site air-failure test, please send us the P&ID excerpt, data sheet and nameplate information. We can align the fail position, actuator action form and signal strategy item by item against ISA-5.1 and the official manuals.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.