Instrument Cable Glands & Junction Boxes - Selection
Release time:2026-11-24 16:01:01 | Views:

Cable glands and junction boxes are the final link in hazardous-area instrument installation. A gland must preserve the protection concept of the enclosure it enters, and a junction box must match the zone, gas group and temperature class. Intrinsically safe Ex ia and flameproof Ex d cable entries are not interchangeable; a wrong choice directly invalidates certification. This article covers protection concepts, selection factors, installation points and a checklist. Certifications and dimensions are subject to the official certificate, data sheet and nameplate.

I. Protection Concepts

TypeStandardProtection principleTypical application
Ex d flameproof enclosureIEC 60079-1Allows an internal explosion and cools escaping gas below the ignition temperature through a flame pathJunction boxes, control stations, motors; Zone 1/2
Ex e increased safetyIEC 60079-7Increased creepage and clearance, temperature limits and secure connections prevent sparks in normal operationTerminal and junction boxes, mainly Zone 2
Ex i intrinsic safetyIEC 60079-11Limits loop energy so sparks and thermal effects cannot ignite the atmosphereLow-power field instruments, up to Zone 0
Ex de combinedIEC 60079-1 + IEC 60079-7An Ex d chamber houses arc-producing parts and an Ex e chamber provides terminalsCombined devices with switching and terminal functions
Installation and zoningIEC 60079-14, IEC 60079-10-1Defines selection, installation, inspection and area classificationGas Zones 0/1/2, dust Zones 20/21/22
General and performanceIEC 60079-0, EN 62444, IEC 60529General requirements, gland performance and IP ratingEquipment marking, clamping range and ingress rating

The data in this article was obtained via web search. Source: IEC 60079-0 / IEC 60079-1 / IEC 60079-7 / IEC 60079-11 / IEC 60079-14 / IEC 60079-10-1, EN 62444 and IEC 60529 standard numbers, https://cncablegland.com/pt/ex-d-vs-ex-e-cable-gland/, https://www.sourcebyspec.com/encyclopedia/explosion-proof-junction-box.html and https://eksen.com.tr/en/useful-information/ex-d-vs-ex-e-protection-types. Approvals and markings are subject to the official certificate.

Hazardous-area field device appearance reference
Explosion-proof limit switch appearance reference, not the actual product; parameters subject to the official data sheet

II. Cable Gland Selection Factors

FactorOptions / checksNotes
Protection conceptEx d / Ex e / Ex i (blue marking often used for IS)Determined by the enclosure: an Ex d enclosure accepts only Ex d glands; an Ex e enclosure accepts Ex e or Ex d
ThreadM20 x 1.5, 1/2 NPT, G1/2; M20 to 1/2 NPT adapters availableParallel metric and tapered NPT are different geometries and must not be mixed
Clamping rangeSelect by cable outer diameter and armour typeOutside the certified range, sealing and explosion protection are compromised
MaterialBlack/blue plastic, nickel-plated brass, stainless steel (e.g. 1.4305)Choose by corrosion environment, mechanical strength and earthing requirements
Sealing methodEx d uses a compound-filled barrier or certified elastomer sealCompound types are effectively permanent; re-termination requires renewed compound
Spare entriesUse certified blanking elements (CBE) or standard blanking elements (SBE)Never improvise a temporary seal

Manual example: the SAMSON 3730-3 operating manual lists M20 x 1.5 gland options — black plastic (clamping 6-12 mm), blue plastic (6-12 mm), nickel-plated brass (6-12 mm and 10-14 mm), and stainless steel 1.4305 (8-14.5 mm); M20 x 1.5 to 1/2 NPT adapters are available in powder-coated aluminium or stainless steel. The Fisher DVC7K manual identifies CG1 as an intrinsically safe blue plastic gland, CG2 as a flameproof brass gland, and CBE/SBE as certified/standard blanking elements. These are manual examples only; the actual selection is subject to the device nameplate and official ordering table.

Source: SAMSON 3730-3 operating manual (accessories table: M20 x 1.5 cable glands and adapters) and Fisher DVC7K official selection manual (CG1 / CG2 / CBE / SBE codes); the data in this section was obtained via web search, source: IEC 60079-14 and EN 62444 standard numbers and https://eksen.com.tr/en/useful-information/ex-d-vs-ex-e-protection-types. Dimensions and codes are subject to the official manual.

III. Junction Box Selection Factors

DimensionEx d boxEx e boxSelection hint
Protection principleWithstands an internal explosion and prevents propagationAvoids arcs, sparks and excessive temperatureDecide by zone and internal components; arc-producing parts favor Ex d or Ex de
Typical materialDie-cast aluminium, cast iron, steel, 316LGRP polyester, aluminium, stainless steelChoose by corrosion and mechanical impact
EPL and zoneTypically Gb (Zone 1/2)Mainly Gc (Zone 2), some for Zone 1Zone 0 needs Ga (usually IS systems); dust areas use Da/Db/Dc
Internal componentsNon-Ex-certified components may be usedComponents must be Ex e certified; no arc-producing partsChanging internal components may void certification
Ingress ratingIP66 common industrial baselineAt least IP54, often IP66 outdoorsIP and Ex markings are separate systems and both must be checked
Terminals and entriesCertified maximum terminal count/size and entry layoutCertified Ex e terminals with spare waysNever field-drill or modify the certified structure

The data in this section was obtained via web search. Source: IEC 60079-0 / IEC 60079-1 / IEC 60079-7 / IEC 60079-10-1 and IEC 60529 standard numbers, https://sourcebyspec.com/encyclopedia/explosion-proof-junction-box.html, https://industrialmonitordirect.com/web-pixels@02d13049w588a3a08pb529f9b2m27ddd415/custom/web-pixel-shopify-custom-pixel@0530/sandbox/modern/blogs/knowledgebase/ex-d-vs-ex-e-hazardous-area-equipment-selection-guide and https://novatelia.com/instrumentation/cable-glands-junction-boxes. Construction data are subject to the official certificate and data sheet.

IV. Installation and Maintenance Points

StageRequirementConsequence if ignored
Gland and enclosure matchPer the IEC 60079-14 selection table: Ex d enclosures accept only Ex d glands; Ex e enclosures accept Ex e or Ex dAn Ex e gland on an Ex d enclosure breaks the flame path
Thread engagementEngagement length and form must meet the certificateInsufficient engagement removes flameproof performance
Flame path protectionNo PTFE tape or paint on a flame path unless the certificate allows itChanged gap dimensions invalidate flameproofing
Cable and sealClamping range matches cable OD; armoured cable has a reliable earth pathSeal failure allows water ingress or flame travel along the cable
Spare entriesClose with certified blanking elements of the matching typeOpen entries break ingress and explosion protection
Marking and recordsVerify nameplate marking against the certificate number and keep inspection recordsCompliance cannot be demonstrated and wrong parts may be refitted

The data in this section was obtained via web search. Source: IEC 60079-14 / IEC 60079-1 / IEC 60079-7 standard numbers, https://cncablegland.com/pt/ex-d-vs-ex-e-cable-gland/, https://automationforum.co/?p=27181/ and https://eksen.com.tr/en/useful-information/ex-d-vs-ex-e-protection-types. Installation is subject to the certificate and official instructions.

V. Common Pitfalls and Checklist

Pitfall / check itemCorrect practiceBasis
Mixing Ex ia intrinsic safety with Ex d flameproofDifferent principles; select separately by certificate and loop calculationIEC 60079-11 / IEC 60079-1
Assuming an Ex e gland fits an Ex d enclosureIt does not; an Ex d enclosure requires an Ex d glandIEC 60079-14 selection table
Replacing a blue IS gland with an ordinary plastic oneSelect the certified type and cable OD; use a barrier or isolator as requiredIEC 60079-14, SAMSON 3730-3 operating manual
Field-drilling additional cable entriesOrder the certified number and position of entries with spare waysOfficial certificate and data sheet
Checking IP rating but not the Ex markingIP and Ex are separate systems and both must be satisfiedIEC 60529 and IEC 60079 series
Assuming an approval exists when it cannot be foundState "unable to confirm, please verify with the manufacturer"; never imply a model exclusively holds an approvalDocument writing rule

The data in this section was obtained via web search. Source: IEC 60079 series and IEC 60529 standard numbers, https://cncablegland.com/pt/ex-d-vs-ex-e-cable-gland/ and https://www.sourcebyspec.com/encyclopedia/explosion-proof-junction-box.html. Certification status is subject to the official certificate.

VI. Selection Guide and Common Configurations

Selection guide: First determine the equipment protection level and concept (Ex ia / Ex d / Ex e / Ex de) from zone, gas group and temperature class. Then select the gland by the enclosure concept: an Ex d enclosure accepts only Ex d glands, while an Ex e enclosure accepts Ex e or Ex d. Next verify cable OD, armour type, thread form, clamping range, material and IP rating, and confirm the certified entry count and terminal capacity. During installation preserve the flame path, engagement length and seal, and close spare entries with certified blanking elements. Ex ia intrinsic safety is NOT Ex d flameproof; if an approval cannot be found, state "unable to confirm, please verify with the manufacturer". All dimensions and certificates are subject to the official data sheet, certificate and nameplate.

Common configurations: Blue Ex i marked glands with isolators for IS loops; Ex d brass or stainless glands with certified blanking plugs on flameproof enclosures; Ex e glands with certified terminals on increased-safety boxes; 316L or GRP enclosures for corrosive service. The M20 x 1.5 plastic/nickel-plated brass/stainless glands and 1/2 NPT adapters listed in the manuals are examples of available accessories; ordering is subject to the device nameplate and official selection table.

If you are specifying cable entries or junction boxes for a hazardous area, please send us the zone, gas group, enclosure type, cable outer diameter and material requirement. We can review the gland type, clamping range and certification item by item against the IEC 60079 series and official manuals.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.