Home » Products » Fisher
Fisher FIELDVUE DPC2K Digital Process Controller
Fisher FIELDVUE DPC2K Digital Process Controller
Fisher FIELDVUE DPC2K Digital Process Controller

Fisher FIELDVUE DPC2K Digital Process Controller

Details

1. Product Overview

The Fisher FIELDVUE DPC2K is a single-loop digital process controller that performs a continuous PID control loop. The internal PID algorithm executes every 50 ms, or 20 times per second.

The process variable can come from the integrated process pressure sensor or from an external transmitter. Output can be an analog 4-20 mA signal to drive an electric actuator or positioner, or a pneumatic signal for a single-acting valve actuator.

The controller can be mounted on Fisher 657 / 667 actuators, rotary actuators, linear applications or a 2 in pipe for remote mounting, and is configured through the local user interface or LoopConnect software.

Above: product appearance / manufacturer literature image.

2. Technical Description

Digital process controller: Single-loop PID controller with 50 ms update.

Flexible PV: Integrated pressure sensor or external 4-20 mA transmitter.

Two output types: Analog 4-20 mA or pneumatic output with five pressure ranges.

Communications: Modbus RTU / TCP, HART-IP and HART-FSK.

Integrated mounting: Fisher 657 / 667, rotary and linear actuator mounting.

Source: Fisher Process Controller Product Literature; official FIELDVUE DPC2K Instruction Manual D104786X0CN and Product Bulletin D104561X0CN.

3. Main Technical Specifications

ParameterSpecification / Description
Instrument typeDigital process controller (PID)
PID update rate50 ms / 20 times per second
MountingIntegrated to Fisher 657 / 667 actuators, rotary actuators, straight-stem linear applications, 2 in pipe remote mounting
Actuator compatibilityLinear stem 6.35-606 mm / 0.25-23.375 in; rotary 45-180 degrees (NAMUR does not support quarter-turn rotary)
Power9-28 V DC with reverse-polarity protection; maximum 28 V DC; typical 1 W, maximum 2 W
CommunicationsModbus RTU RS485 9600-256000 baud (default 115200); Modbus TCP and HART-IP over Ethernet; HART-FSK
Analog inputsTwo 4-20 mA inputs, 250 ohm internal resistance, +/- 0.25 percent accuracy, +/- 30 V DC protection
Analog output4-20 mA, internal 28 V DC supply, maximum load 1 kohm, 0.35 percent accuracy
Operating temperature-40 to 80 C / -40 to 176 F; 5-95 percent relative humidity; up to 2000 m
EnclosurecCSAus Type 4X; ATEX / IECEx IP66
Electrical connection1/2 NPT Female, two conduit entries; 14-22 AWG cable recommended
Process pressure sensorSealed gauge 2.1 / 6.9 / 20.7 / 41.4 / 103 / 344.7 bar; +/- 0.35 percent reference accuracy; 1/4 NPT; 316 stainless wetted parts
Pneumatic outputMaximum 10.0 bar / 145 psig or actuator maximum, whichever lower; supply / output 1/4 NPT, exhaust 3/8 NPT; steady air use 0.056 m3/hr at 1.4 bar
CertificationscCSAus Class I Div 1 / Div 2, ATEX Zone 1 / Zone 2, IECEx, ECAS and MOL; process sensor CRN 0F24844.5
Source: Fisher Process Controller Product Literature; official FIELDVUE DPC2K Instruction Manual D104786X0CN and Product Bulletin D104561X0CN.

4. Selection Guide

Selection sequence: Loop -> Output -> Mounting -> Communications -> Approvals.

StepItemKey point
1LoopConfirm a single continuous PID loop and the required PV source
2OutputChoose analog 4-20 mA or pneumatic output and the pressure range
3MountingSelect integrated actuator mounting or 2 in pipe remote mounting
4CommunicationsChoose Modbus RTU / TCP, HART-IP or HART-FSK channels
5ApprovalsSelect the hazardous-area enclosure and process pressure sensor range

Boundary: Power, communications, pressure ranges and approvals follow the official process controller literature; unlisted values are subject to nameplate / order / official manual.

Source: Fisher Process Controller Product Literature; official FIELDVUE DPC2K Instruction Manual D104786X0CN and Product Bulletin D104561X0CN.

5. Complete Model Enumeration

ConfigurationOutputDescription
DPC2K analog (X1901)4-20 mABase unit with analog output
DPC2K pneumatic (X1920)PneumaticBase unit with pneumatic output option
DPC2K with PPSAnalog or pneumaticVersion with integrated process pressure sensor

6. Related Models

Related modelDescription
DVC7KDigital valve controller (smart positioner)
DVC6000 seriesFIELDVUE digital valve controllers
4190 seriesIndicating controllers such as 4195K
C1Pneumatic controller / transmitter for pressure and differential pressure

7. Common Spare Parts

Spare partDescription
Base unitAnalog output X1901 or pneumatic output X1920
Process pressure sensorSensor by pressure range 2.1 to 344.7 bar
Connection kit1/2 NPT conduit and terminal components
Display moduleLocal user interface replacement

8. Accessories

AccessoryDescription
LoopConnect softwareSetup, operation and maintenance
Process pressure sensorIntegrated pressure measurement option
Pneumatic output kitSingle-acting pneumatic output option
Pipe mounting kit2 in pipe remote mounting bracket

9. Disclaimer

The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.

10. Sources & Contact

Source: Fisher Process Controller Product Literature; official FIELDVUE DPC2K Instruction Manual D104786X0CN and Product Bulletin D104561X0CN.

We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Application area