Home » Products » Fisher
Fisher Type 3722 Electro-Pneumatic Transducer (I/P)
Fisher Type 3722 Electro-Pneumatic Transducer (I/P)
Fisher Type 3722 Electro-Pneumatic Transducer (I/P)

Fisher Type 3722 Electro-Pneumatic Transducer (I/P)

Details

1. Product Overview

The Fisher Type 3722 is an electro-pneumatic transducer (I/P converter) that converts a 4-20 mA current signal into a proportional pneumatic output using a nozzle-flapper mechanism. It is supplied with the Fisher 3710 and 3720 valve positioners.

The transducer accepts 4-20 mA, 4-12 mA or 12-20 mA split-range inputs and gives a standard 0.2-1.0 bar / 3-15 psig or 0.4-2.0 bar / 6-30 psig output, with zero and span adjustments under the cover.

Reference accuracy is +/- 1.0 percent of full scale including hysteresis, linearity and dead band. Clean, dry instrument air or natural gas is required.

Above: product appearance / manufacturer literature image.

2. Technical Description

I/P transducer: Electro-pneumatic transducer with nozzle-flapper conversion.

Split range: 4-20 mA, 4-12 mA and 12-20 mA inputs via dip switch.

Output ranges: 0.2-1.0 bar, 0.4-2.0 bar or 0.14-2.3 bar.

Accuracy: +/- 1.0 percent full scale reference accuracy.

Low air use: Maximum output 8.0 m3/hr / 300 scfh at 1.4 bar supply.

Source: Fisher Electro-Pneumatic Transducer Introduction; official Types 3710/3720 Positioners and Type 3722 Electro-Pneumatic Transducer Instruction Manual.

3. Main Technical Specifications

ParameterSpecification / Description
Instrument typeElectro-pneumatic transducer (I/P, nozzle-flapper)
Input signalStandard 4-20 mA DC; split range 4-12 mA and 12-20 mA by dip switch
Output signal0.2-1.0 bar / 3-15 psig, 0.4-2.0 bar / 6-30 psig, or 0.14-2.3 bar / 2-33 psig
Reference accuracy+/- 1.0 percent of full scale including hysteresis, linearity and dead band
Independent linearity / hysteresis0.5 percent / 0.4 percent
Temperature effect+/- 0.14 percent of output range per degree C (+/- 0.075 percent per degree F)
Supply pressure effect0.2 percent of full scale per 1 psi supply change; vibration below 1 percent of full scale per ISA S75.13
Equivalent circuitSeries circuit with approximately 4 V DC drop and 40 ohm total resistance; two 6.8 V zener diodes
Supply pressureRecommended 0.3 bar / 5 psig above output range maximum; maximum 3.4 bar / 50 psig; air or natural gas
Air qualityClean dry air or natural gas, maximum 40 micrometres (5 micrometres recommended), oil below 1 ppm per ISO 8573-1
Maximum output flow8.0 m3/hr / 300 scfh at 1.4 bar supply
ConnectionsSupply, output and vent 1/4 NPT Female; electrical 1/2 NPT, wire 18-22 AWG
EnclosureCSA Type 4X / 3X; FM NEMA 4X / 3; ATEX IP66 / IP64; IECEx IP66 / IP64
Approximate weight2.5 kg / 5.5 lb
Source: Fisher Electro-Pneumatic Transducer Introduction; official Types 3710/3720 Positioners and Type 3722 Electro-Pneumatic Transducer Instruction Manual.

4. Selection Guide

Selection sequence: Function -> Input -> Output -> Supply -> Approvals.

StepItemKey point
1FunctionConfirm an I/P conversion duty rather than a full positioner
2InputChoose 4-20 mA, 4-12 mA or 12-20 mA split-range input
3OutputSelect 3-15 psig, 6-30 psig or 2-33 psig output range
4SupplyProvide clean dry air or gas at 0.3 bar above the output maximum, within 3.4 bar
5ApprovalsSelect the enclosure and hazard approval required for the installation

Boundary: Accuracy, supply limits and air quality follow the official transducer literature; unlisted values are subject to nameplate / order / official manual.

Source: Fisher Electro-Pneumatic Transducer Introduction; official Types 3710/3720 Positioners and Type 3722 Electro-Pneumatic Transducer Instruction Manual.

5. Complete Model Enumeration

ConfigurationInputDescription
3722 standard4-20 mAElectro-pneumatic transducer with 3-15 psig output (this page)
3722 split range4-12 / 12-20 mASplit-range version set by dip switch
3722 with filter regulator4-20 mATransducer with Fisher 67 series filter regulator

6. Related Models

Related modelDescription
3710Pneumatic valve positioner used with the 3722 transducer
3720Electro-pneumatic valve positioner used with the 3722 transducer
646 / 846Electro-pneumatic transducers in the Fisher range
i2P-100 / 546NSOther Fisher current-to-pressure transducers

7. Common Spare Parts

Spare partDescription
Nozzle and flapper assemblyReplacement nozzle-flapper element
Zero / span potentiometer20-turn adjustment potentiometer
Diaphragm and sealsElastomer service kit
Filter elementReplacement element for the supply filter

8. Accessories

AccessoryDescription
67 series filter regulatorClean, regulated instrument supply
2 in supply gaugeCircular supply pressure gauge
Explosion-proof housingHazardous-area enclosure and cover
Pipe fittings1/4 NPT pneumatic fittings

9. Disclaimer

The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.

10. Sources & Contact

Source: Fisher Electro-Pneumatic Transducer Introduction; official Types 3710/3720 Positioners and Type 3722 Electro-Pneumatic Transducer Instruction Manual.

We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult Tel: +86 028-60220547 / Email: info@bit-cd.com

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Application area