Release time:2026-11-24 14:01:02 | Views:

When a differential-pressure transmitter is paired with a standard primary element such as an orifice plate, flow is proportional to the square root of differential pressure, so square-root extraction is required. It can be performed in the transmitter, the DCS or a flow computer, but in one location only; applying it twice creates a systematic bias. This article covers the mathematical relationship, standards basis, range setting and low-flow considerations. Parameters are subject to the official manual, standard text and nameplate.

I. Technical Positioning

ItemContent
Measurement chainPrimary element (orifice/nozzle/Venturi) to impulse lines and manifold to DP transmitter to 4-20 mA/HART to DCS or flow computer
Core relationshipFlow is proportional to the square root of differential pressure; flow ratio = sqrt(measured DP / full-scale DP)
Primary-element standardsISO 5167-1:2022 (general requirements), ISO 5167-2:2022 (orifice plates); equivalent ASME MFC-3M
Location of extractionInside the transmitter, in a DCS algorithm block, or in a flow computer; choose one, never two
Output formLinear DP 4-20 mA or square-rooted flow 4-20 mA, explicitly documented in the loop
Range parametersLRV (4 mA value), URV (20 mA value) and URL (upper range limit) must be checked separately
CompensationLiquids with stable density convert directly; gas and steam need pressure and temperature compensation or a flow computer

The data in this article was obtained via web search. Source: ISO 5167-1:2022, ISO 5167-2:2022 and ASME MFC-3M standard numbers, https://www.flowtmeter.com/info/differential-pressure-flow-meter-guide-flowt-103593633.html and https://instranova.com/?p=1394. Formulas and scope are subject to the standard texts.

DP transmitter appearance reference
Transmitter appearance reference, not the actual product; parameters subject to the official data sheet

II. Mathematics of Square-Root Extraction

Flow ratioCorresponding DP ratioNotes
100 %100 %Full-scale DP corresponds to maximum flow
75 %56.25 %0.75 squared = 0.5625
50 %25 %0.50 squared = 0.25
25 %6.25 %0.25 squared = 0.0625
10 %1 %Very small DP at low flow; noise and zero drift become significant

The simplified relation is q = C x epsilon x (pi/4)d^2 x sqrt(2 dP / rho) / sqrt(1 - beta^4), where beta = d/D is the diameter ratio, C the discharge coefficient and epsilon the expansibility factor for compressible fluids. Typical limits are beta about 0.1 to 0.75, pipe diameter 50 to 1000 mm and Reynolds number above the standard minimum. Coefficients and applicability must be calculated per ISO 5167-2; the simplified expression does not replace a formal sizing calculation.

The data in this section was obtained via web search. Source: ISO 5167-1:2022 and ISO 5167-2:2022 standard numbers, https://www.flowtmeter.com/info/differential-pressure-flow-meter-guide-flowt-103593633.html and https://www.cbytt.com/blog/orifice_flow_measurement.php. Formulas and coefficients are subject to the standard texts.

III. Where to Perform the Extraction

SchemePracticeAdvantagePrecautions
In the transmitterConfigure output characteristic as square root; 4-20 mA directly represents flowNo DCS calculation needed, straightforward indicationDCS must scale a linear flow signal; never extract the square root again
In a DCS algorithm blockTransmitter sends linear DP; DCS extracts the square root and scalesRaw DP remains visible for impulse-line diagnosticsDocument the location on loop diagrams; prevent duplicate setup after maintenance
In a flow computerMultivariable transmitter sends DP, P and T; the flow computer performs compensation and extractionSuits pressure and temperature compensation for gas and steamAll variables must be connected; a missing input invalidates compensation

Manufacturer guidance consistently stresses that square-root extraction must occur in one place only. If both transmitter and DCS extract the root, the indication is systematically high; if neither does, the displayed value is a DP percentage rather than flow. The SAMSON differential-pressure instrument manual (T 9519 / EB 9519 EN) lists linear, square and DIN 19204 scale options, showing that the characteristic is configurable and must be confirmed transmitter by transmitter before commissioning.

Source: SAMSON official data sheets T 9519 / T 9520 and operating manual EB 9519 EN; the data in this section was obtained via web search, source: https://www.flowtmeter.com/info/differential-pressure-flow-meter-guide-flowt-103593633.html and https://www.processinstrumentsolutions.co.uk/wp-content/uploads/2021/04/sitransf_fodeltap_fi01_en.pdf. Configuration items are subject to the official manual.

IV. Range Setting and 4-20 mA Mapping

ItemSettingExample (full-scale DP 100 kPa)
DP upper valueFrom the primary-element sizing calculation, not the transmitter URL100 kPa
LRV / 4 mAZero DP (or the elevated lower value) corresponds to 4 mA0 kPa to 4 mA
URV / 20 mAMaximum DP corresponds to 20 mA100 kPa to 20 mA
Linear DP outputAt 36 kPa: current = 4 + 16 x 0.369.76 mA (36 % DP)
Square-rooted flowFlow ratio = sqrt(36/100) = 0.6060 % flow; with extraction in the transmitter, output = 4 + 16 x 0.60 = 13.6 mA
DCS scalingScale by flow if extraction is in the transmitter; scale by DP then extract if in the DCSLimits must agree with transmitter LRV/URV

The difference between 13.6 mA and 9.76 mA in the example shows why the extraction location matters: both are valid 4-20 mA signals but represent different engineering quantities. Loop diagrams, configuration sheets and maintenance records should explicitly state "linear DP output" or "square-rooted flow output".

The data in this section was obtained via web search. Source: https://www.flowtmeter.com/info/differential-pressure-flow-meter-guide-flowt-103593633.html. The example illustrates the mapping only; actual ranges are subject to the primary-element calculation and official manual.

V. Low-Flow and Compensation Issues

IssueSymptomCountermeasure
Low-DP resolution10 % flow produces only about 1 % DP, amplifying zero drift and noiseVerify zero stability and damping; change span or use a multi-range scheme
Limited turndownA single orifice/transmitter typically offers about 3:1 to 4:1Use dual transmitters or a multivariable solution for wide rangeability
Impulse-line problemsLiquid accumulation, trapped gas or blockage distorts DP; error grows after extractionProvide condensate pots / seal pots and vents and drains per medium; blow down regularly
Changing gas or steam densityDesign density becomes invalid as pressure and temperature vary, biasing flowAdd absolute pressure and temperature measurement; compensate in a multivariable transmitter or flow computer
Pulsating flowStandard scope generally excludes pulsation, causing fluctuating readingsCheck ISO 5167 applicability; change primary element or add damping

The data in this section was obtained via web search. Source: ISO 5167-1:2022 standard number, https://www.flowtmeter.com/info/differential-pressure-flow-meter-guide-flowt-103593633.html and https://www.cbytt.com/blog/orifice_flow_measurement.php. Compensation algorithms are subject to the standard text and official manual.

VI. Selection Guide and Common Configurations

Selection guide: First obtain the maximum DP and beta ratio from the primary-element sizing calculation, and confirm that medium, pipe size, Reynolds number and straight-run installation meet ISO 5167 conditions. Then decide where to extract the square root and keep exactly one extraction point in the loop diagram and DCS configuration. When setting the range, distinguish LRV/URV from URL and verify the 4/20 mA mapping against measured DP. Evaluate low-flow DP resolution against zero drift, and apply pressure/temperature compensation for gas and steam. All coefficients, accuracy figures and ranges are subject to the standard text, official data sheet and nameplate.

Common configurations: Orifice plate plus DP transmitter with linear DP output and DCS extraction/scaling; orifice plate plus DP transmitter with internal extraction and flow output; steam service with condensate pots and a multivariable transmitter, using a flow computer for compensation and extraction. SAMSON Media 5 / Media 7 DP instruments offer linear and square-root scale options; configuration is subject to the corresponding data sheets T 9519 / T 9520.

If you are investigating inaccurate differential-pressure flow indication, please send us the primary-element type, maximum DP, transmitter output characteristic and DCS scaling parameters. We can review the extraction location and range mapping against ISO 5167 and the official manual to identify duplicate extraction or inconsistent scaling.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.