Static pressure and overpressure are different concepts for a pressure transmitter. Static pressure is the common-mode pressure applied to both sides of a differential-pressure cell, while overpressure is a pressure above the upper range limit that the transmitter can withstand without damage. Selection requires checking the static pressure limit and the overpressure limit separately, and distinguishing both from maximum working pressure and burst pressure. This article organizes the pressure rating hierarchy, static pressure effects and engineering protection measures. All figures are subject to the manufacturer's reference manual and nameplate. I. Positioning and Definitions
Source: Rosemount 3051 reference manual (document number 00809-0100-4808) and 3051 product manual; the data in this article was obtained via web search, source: https://www.emerson.com/documents/automation/manual-rosemount-3051n-smart-pressure-transmitter-for-nuclear-service-en-89488.pdf and http://fluidprocessing.it/wp-content/uploads/2016/12/10356_3051.pdf. Parameters are subject to the official manual and nameplate.
II. Pressure Rating Hierarchy (Published Manual Examples)
High-static DP versions such as the 3051SHP list separately in the published manual: overpressure limit 22500 psi (1551 bar) for the static version and 15000 psi (1034 bar) for the DP version, maximum working pressure up to 15000 psig, and burst pressure 37500 psi (2585 bar). These figures only illustrate the hierarchy of ratings and do not apply to every model; the limits for the selected range code must be checked against that model's manual. The data in this section was obtained via web search. Source: Rosemount 3051 reference manual 00809-0100-4808, https://www.emerson.com/documents/automation/manual-supplement-rosemount-3051s-series-of-instrumentation-high-pressure-solutions-en-187362.pdf and https://www.nexinstrument.com/assets/images/3051C%20pdf.pdf. Figures are subject to the official manual and nameplate. III. Static Pressure Effects and Error Mechanisms
The data in this section was obtained via web search. Source: Rosemount 3051 reference manual 00809-0100-4808 and the high-pressure solutions manual supplement (Emerson PDF, see previous source). Error specifications are subject to the official manual. IV. Overpressure Protection Measures
Manifold and isolation practices are recognized engineering methods. Source: Rosemount 3051 reference manual 00809-0100-4808, NAMUR NE 43 standard number and IEC 60079-14 (hazardous-area installation). Relief setpoints and fill fluids are subject to the official data sheet. V. Selection and Installation Checklist
Checklist compiled from published manuals and standard numbers. Source: Rosemount 3051 reference manual 00809-0100-4808, ASME B16.5 / DIN PN flange standards, IEC 60079-14 and NAMUR NE 43. Actual selection is subject to the official data sheet and nameplate. VI. Selection Guide and Common ConfigurationsSelection guide: First determine whether the measurement is DP or gage/absolute. For DP service, state the maximum line static pressure and check the static limit and static zero error before accepting a standard model; for gage/absolute service, check URL and overpressure limit. Second, use the range code to find the overpressure limit and ensure the relief device setpoint is below it, then derate the flange rating at process temperature. Third, verify fill fluid, O-ring material and hazardous-area approval, and finally configure NAMUR NE 43 fault thresholds in the DCS. Ex ia intrinsic safety is NOT Ex d flameproof; if an approval cannot be found, state "unable to confirm, please verify with the manufacturer". All pressure limits are subject to the official manual, data sheet and nameplate. Common configurations: Conventional DP service with a three-valve or five-valve manifold, equalizing before admitting pressure; steam service with condensate pots and remote seals; high-pressure service with a high-static model and a rechecked flange rating; corrosive service with diaphragm seals and compatible fill fluid. The manual statement that re-zeroing is required after overpressure should be reflected in the commissioning procedure. If you are checking the static or overpressure conditions of a pressure transmitter, please send us the medium, maximum working pressure, range code and flange rating. We can verify the static limit, overpressure limit and relief setpoint against the official manual so that an overpressure limit is never mistaken for a usable range. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |