A temperature transmitter converts an RTD or thermocouple signal into a standard 4-20 mA output. Depending on whether power and signal share one wire pair, two basic wiring schemes exist: two-wire (loop-powered) and four-wire (separately powered). They differ greatly in loop budget, AI channel powering, hazardous-area and intrinsic-safety design; wrong wiring can cause signal drift, channel overcurrent or even damage. This article follows recognized wiring practice and manufacturer data sheets; terminal definitions are subject to the official manual and nameplate. I. Technical Positioning
Source: SAMSON official data sheets u T 6132 and T 6134 (four-wire and two-wire converter wiring); the data in this article was obtained via web search, source: https://www.instrumentationblog.in/?p=13246 and https://industrialautomation.net/c143-various/post/how-do-you-select-calibrate-and-wire-industrial-field-instrumentation-OCqd8nvmrK51RBT. Terminal definitions are subject to the official manual.
II. Fundamental Difference
Taking comparable SAMSON converters as an example: the four-wire Type 6132 accepts 230/115/24 V AC or 24 V DC, outputs 0/4-20 mA and 0/2-10 V, and is IP20; the two-wire Type 6134 is powered by a 12-30 V DC loop, outputs only 4-20 mA, is available in Ex ia / Ex d versions, and is IP54/IP65. The two wiring methods are not interchangeable. Source: SAMSON official data sheets u T 6132 EN and T 6134 EN (supply, output and ingress rating for two-wire/four-wire converters); the data in this section was obtained via web search, source: https://www.instrumentationblog.in/?p=13246. Parameters are subject to the official data sheets. III. Loop Budget and Load Calculation
The data in this section was obtained via web search. Source: NAMUR NE 43 standard number; https://www.instrumentationblog.in/?p=13246, https://industrialautomation.net/c143-various/post/how-do-you-select-calibrate-and-wire-industrial-field-instrumentation-OCqd8nvmrK51RBT and https://itotconvergentie.nl/en/hart. Calculation formulas are subject to the official manual. IV. Typical Wiring and Terminal Treatment
An active four-wire output must not be connected directly to a powered AI channel, and a two-wire transmitter must be connected to an AI channel that provides loop power. These are the two most common field wiring errors and should be marked separately on loop diagrams and termination drawings. The data in this section was obtained via web search. Source: https://industrialautomation.net/c143-various/post/how-do-you-select-calibrate-and-wire-industrial-field-instrumentation-OCqd8nvmrK51RBT and https://www.yyledi.com/article/174.html. Terminal numbers are subject to the official manual and nameplate. V. Selection Criteria and Common Pitfalls
The data in this section was obtained via web search. Source: NAMUR NE 43 standard number, https://www.yyledi.com/article/174.html and https://www.instrumentationblog.in/?p=13246. Ranges and alarm thresholds are subject to the official manual. VI. Selection Guide and Common ConfigurationsSelection guide: First check whether the AI card provides 24 V loop power and an IS barrier. If so, select a two-wire temperature transmitter and budget the 250 ohm sense resistor plus HART load. If not, or if an independent supply or 0-10 V output is required, select a four-wire unit and set the AI channel to passive input. Second, match the output range and NAMUR NE 43 fault thresholds so transmitter LRV/URV and DCS scaling agree exactly. Design segregation and earthing per IEC 60079-14 and ISA-RP12.6 for hazardous areas; if an approval cannot be found, state "unable to confirm, please verify with the manufacturer". Voltage ranges, terminal numbers and approvals are subject to the official manual, data sheet and nameplate. Common configurations: Head-mounted two-wire temperature transmitter (Pt100/thermocouple input, 4-20 mA + HART) fed by a powering AI channel; rail-mounted four-wire transmitter with an independent 24 V DC supply and passive AI channel; two-wire transmitter through a galvanic isolator for IS loops. SAMSON Type 6132 is four-wire and Type 6134 is two-wire, and their wiring is not interchangeable; verify other brands against their official data sheets. If you are selecting a transmitter for a temperature point, or are unsure whether your AI card can drive a two-wire loop, please send us the card model, power scheme, sensor type and Ex requirement. We can review the wiring scheme, loop budget and range scaling against the official manual. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |