Honeywell MICRO SWITCH BX / BX2 are flameproof (Ex d) hazardous-area limit switches: the BX has an aluminum housing and the BX2 a 316L stainless steel housing, typically marked II 2 GD Ex db IIC T6 Gb / Ex tb IIIC T85 C Db. Installation, set-point adjustment and wiring must follow the official instructions: actuator head orientation, lever position, cam set point, terminal torque and flame paths are all specified. This article covers installation, adjustment and set-point calibration based on Honeywell official data sheets and installation instructions.

I. Product Positioning

ItemContent
Brand ownershipHoneywell MICRO SWITCH product family; BX / BX2 belong to the Honeywell brand
Model differencesBX = aluminum housing flameproof limit switch; BX2 = 316L stainless steel housing flameproof limit switch (enhanced corrosion resistance)
Ex markingII 2 GD Ex db IIC T6 Gb / Ex tb IIIC T85 C Db (flameproof enclosure Ex db, not intrinsically safe Ex ia)
Typical approvalsUL, CSA/cULus, ATEX, IECEx, NEPSI, etc.; verify against the specific ordering code and nameplate
Main documentsHoneywell official data sheet 002306 Issue 11; BX installation instructions 50083427; BX2 installation instructions 50047766

The data in this article was obtained via web search. Source: Honeywell official data sheet 002306 Issue 11, BX installation instructions 50083427, BX2 installation instructions 50047766; standards IEC 60079-0, IEC 60079-1, IEC 60079-31.

Limit switch illustration
Limit switch illustration, not a Honeywell product; parameters subject to the official data sheet

II. Pre-installation Check and Mechanical Mounting

ItemRequirement (extract)
Unpacking checkCheck Ex marking, conduit size, electrical ratings and circuit diagram on the nameplate; confirm enclosure, window and entries are intact
Mounting dimensionsLocate per the hole drawings in the installation instructions (Figures 8-10); do not modify the housing or flame paths
Actuator head orientationHead can be mounted in any of four positions: loosen the four captive head screws, set to the desired position, then tighten evenly to 1.4 Nm to 1.8 Nm (12 to 16 lb-in)
Conduit entryConduit size and electrical ratings shown on the nameplate; unused openings must be closed with certified plugs and entries must be certified flameproof glands
GroundingInternal ground screw for equipment grounding, external ground screw for supplementary bonding where local codes permit or require; ensure reliable connection

The data in this article was obtained via web search. Source: Honeywell official BX2 installation instructions 50047766, Mounting / Actuator Head sections; BX installation instructions 50083427 for similar requirements; dimensions subject to the official drawings.

III. Set-point and Actuator Head Adjustment

Adjustment itemMethod and points
Lever angle (rotary type)Lever adjustable through 360 degrees around the shaft: loosen the screw with a 9/64-inch hex key, move to the desired position, tighten until the teller tab cannot be moved by hand, then tighten a further 1/8 to 1/4 turn
Adjustable-length leversRequire a 9/64-inch hex key; this key is supplied in the adjustment tool set LSZ4005
Side rotary actuation directionBX2A/BX2H/BX2L/BX2P/BX2R can be set to clockwise, counter-clockwise or both; BX2M (center neutral) and BX2N (maintained) operate in both directions but cannot be reversed
Cam set pointLoosen head screws and remove the head, lift the hinged cover at the underside, slide the cam back so it rotates freely, rotate it with a screwdriver to the desired actuating position, slide it forward and close the cover; tighten head screws to 1.4 Nm to 1.8 Nm
Roller plungersTop roller plunger: set the roller plane by orienting the head; side roller plunger: rotate to horizontal or vertical with pliers; roller lever may be reversed in/out (except offset roller levers)

The key to set-point calibration is "position first, then lock the cam/lever": verify switch action at the actual fully open and fully closed valve positions, repeat fine adjustment if necessary; after adjustment, re-tighten all screws and restore sealing to prevent set-point drift from vibration.

The data in this article was obtained via web search. Source: Honeywell official BX2 installation instructions 50047766, Adjusting Instructions and Reversing Direction of Actuation sections (Issue 11/16); tool set LSZ4005 listed in that instruction.

IV. Wiring and Grounding Requirements

ItemRequirement (extract)
Wire sizeUp to #12 AWG solid or stranded wire; pressure-type terminals accept stripped ends, spade or ring connectors
Terminal compatibilitySpade width max 7.9 mm (0.312 in); ring diameter max 7.9 mm (0.312 in); use pre-insulated connectors or heat-shrink tubing between spade/ring terminals
Double-pole wiring sequenceFor double-pole units, connect lead wires to the terminals nearest the conduit opening first
Grounding and torqueInternal ground screw on the right side, external ground screw at upper left; terminal and ground screws 1 Nm to 1.8 Nm (9 to 16 lb-in); cover reassembly 10 Nm (90 lb-in); cover locking clamp 1.4 Nm to 1.8 Nm
Electrical ratings10 A continuous; AC15 A600, DC13 R300; specific voltage/current and circuit diagram shown on the nameplate

Never open a flameproof enclosure while energized; after maintenance restore cover threads, seals and locking clamp. After wiring, perform continuity/insulation and function tests to confirm NO/NC status matches the actual valve position.

The data in this article was obtained via web search. Source: Honeywell official BX2 installation instructions 50047766, Wiring Instructions and Table 1 electrical ratings; BX installation instructions 50083427 for similar requirements; circuit diagram per nameplate.

V. Ex Maintenance and Post-calibration Verification

ItemRequirement
Flame pathsMax gap at push rod and bearing 0.076 mm; cylindrical spigot joint must remain intact (Table 3 of BX2 installation instructions)
Lever replacementUse only non-sparking levers to retain the explosion-proof qualities
Part replacementDo not substitute parts from another switch without consulting Honeywell technical support
Cover openingNever open a flameproof enclosure while energized; after maintenance restore threads and seals and re-tighten to specified torque
Static chargeNon-conducting coating may build ignition-capable static under certain conditions; avoid high-pressure steam and clean with a damp cloth

After calibration, three verifications are recommended: switch action matches fully open/fully closed positions; terminal torque and cover sealing are restored; explosion-protection integrity (flame paths, plugs, entries, grounding) is intact. Area classification and medium properties must come from the project classification documents.

The data in this article was obtained via web search. Source: Honeywell official BX2 installation instructions 50047766, Flame Path Measurements and warnings, BX installation instructions 50083427; installation and maintenance subject to the official manual.

VI. Selection Guide and Common Models

Selection guide: First determine the required EPL, gas group (IIA/IIB/IIC) and temperature class (T1-T6) from area classification and medium, then verify BX/BX2 Ex db IIC T6 Gb / Ex tb IIIC T85 C Db meets them. Then select housing by environment (BX aluminum / BX2 316L stainless steel), conduit entry by wiring (1/2", 3/4" NPT or 20 mm), and seal by temperature (fluorosilicone/fluorocarbon). Ex db is flameproof, NOT intrinsically safe Ex ia; if an intrinsically safe loop is required on site, verify whether a corresponding approval exists - if not found, state "unable to confirm, please verify with the manufacturer".

Common models: BXA3K (BX aluminum side-rotary SPDT, 1/2" NPT), BXAC3K (fully fluorocarbon sealed); the BX2 series uses a 316L stainless steel housing with interfaces and approvals per the specific ordering code. LSZ4005 is the official adjustment tool set (includes a 9/64-inch hex key). Final markings and certificates follow the nameplate and original certificate documents.

If you need to verify whether the mounting orientation, set point or wiring of a BX/BX2 unit suits your site requirements, please send us the nameplate data, valve travel and area classification. We can review the head orientation, cam setting and terminal torque item by item against the official installation instructions.