Home » Service & Support » Technical Documentation
TOPWORX Limit Switches - Contact Forms & Wiring Diagrams
Release time:2026-11-24 13:40:51 | Views:

A key difference among TOPWORX (an Emerson Process Management brand) D-Series discrete valve controllers and T-Series position feedback switchboxes is the contact/sensor fitted inside the switchbox: sealed GO Switch dry contacts, mechanical SPDT/DPDT, gold-plated contacts, proximity switches, inductive NAMUR and 4-20 mA transmitters. Each contact form has different ratings, terminal wiring and area-classification limits. This article covers contact forms, switch ratings and wiring points based on the official TopWorx manual.

I. Product Positioning

ItemContent
Brand ownershipTOPWORX, a brand of Emerson Process Management; GO Switch is its non-contact position sensing product line
Applicable seriesD-Series DXP/DXR/DXS; T-Series TXP/TXS/TVA; contact code is digit 2 (bus/sensor) of the ordering code
Contact formsSealed GO Switch SPDT/DPDT, mechanical SPDT/DPDT, gold-plated SPDT, proximity SPDT, inductive NAMUR, 4-20 mA HART transmitter
Ex determining digitSet by digit 3 (area classification): 0 intrinsically safe Ex ia / 1 and C flameproof Ex d / 2 non-incendive Ex nA / G general purpose / W no certification; independent of the housing series letter
Main documentsTopWorx official Discrete Valve Controller manual (TOPWORX.pdf) and GO Switch manual (Chinese edition)

Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf) and GO Switch manual; specific configuration subject to the original ordering code/nameplate.

TOPWORX limit switch illustration
TOPWORX limit switch illustration, not the actual model; parameters subject to the official data sheet

II. Contact (Sensor) Form Comparison

Order codeContact formConfiguration and notes
L2 / L4GO Switch sealed SPDT (Form C)2 / 4 units; sealed dry contact, low hysteresis, intrinsically safe; non-solenoid versions only
Z2 / Z4GO Switch sealed DPDT (Form CC)2 / 4 units; sealed dry contact, for applications needing two independent circuits
M2 / M4 / M6Mechanical SPDT2 / 4 / 6 units; area classification cannot be 2
T2Mechanical DPDT2 units
K2 / K4Mechanical SPDT with gold-plated contacts2 / 4 units; for low-level / weak signal circuits
PN / PSProximity switch SPDT modulePN without LED, PS with LED; max current 1 A / 250 mA respectively
R2 / R4 / P2Proximity switch SPDTR2/R4 max 200 mA; P2 max 3 A
E2 / E4Inductive NAMUR sensor (p+f NJ2+V3-N)2 / 4 units; NAMUR output 8 VDC, requires barrier/isolator
X / H4-20 mA position transmitter (HART)1 analog channel; 8.5-34 VDC; LH not for solenoid versions, DXR has no LH/ZH

Confirm the contact form from digit 2 of the ordering code before wiring. An SPDT has three terminals (common COM, normally open NO, normally closed NC), a DPDT is two independent SPDTs; NAMUR is a 2-wire 8 VDC signal requiring a barrier/isolator to the DCS; the 4-20 mA transmitter is a 2-wire loop. Terminal definitions subject to the supplied wiring diagram and nameplate.

Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf), sensor and switch code tables. Combination codes not spelled out are subject to the original ordering code/nameplate; no guessing.

III. Switch Ratings and Load Matching

Contact formRating (extract)Load matching points
GO Switch L2/L4, Z2/Z4 (35 Series)4 A / 120 VAC; 3 A / 24 VDCSealed contacts, low hysteresis, intrinsically safe; resistant to vibration, moisture, contamination and extreme temperatures
Mechanical M2/M4/M6, T2, K2/K415 A / 120 VACHigh rating but life limited by mechanical wear; M2/M4 not for area 2
Proximity switch P2Max 3 AHighest rating among proximity switches
Proximity switch R2/R4Max 200 mASuitable only for low-current signal circuits
Proximity switch PN / PSPN max 1 A; PS max 250 mAPS has LED indication; note LED leakage current effect on PLC inputs
Inductive NAMUR E2/E48 VDC signalMust go through a NAMUR isolator/barrier, not a ordinary DI
4-20 mA transmitter X/H8.5-34 VDC supply2-wire loop; verify loop voltage and load resistance

Load current must not exceed the contact rating; add surge suppression for inductive loads (relay coils, solenoid valves). Intrinsically safe loops also require checking safety-barrier parameters and cable distributed capacitance/inductance, subject to the loop calculation and official manual.

Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf) and GO Switch manual, 35 Series electrical rating tables; subject to nameplate/order.

IV. Wiring Methods and Conduit Entries

ItemCommon optionsNotes
Wiring methodTerminal, wire, cable, quick-connect (Micro/Mini Change, 3/4/5/7 pins), underwater connectorSelect per ordering code and site wiring; quick-connect pin count must match the system
T-Series conduit entryP=(2)1/2" NPT; M=(2)M20; E=(2)3/4" NPT; 3=(4)M20; 4=(2)3/4" NPT+(2)1/2" NPTDXP flameproof class C requires E or M entry
O-ringT-Series M = silicone; D-Series B = nitrile / S = silicone / E = EPDM / V = fluorocarbonMaterial depends on medium and ambient temperature
Housing materialTXP/DXP aluminum; TXS/DXS 316 stainless steel; TVA engineering resinSelect corrosion resistance by environment
Display and shaftG = 90 deg green open/red closed; B = 90 deg black open/yellow closed; F = flat knurled indicator (TXP/TXS only); shaft N = NAMUR 304, L = 1" extended linear shaftConfigure together with sensor count and mounting

Unused openings on flameproof equipment must be closed with certified plugs, and entries must be certified flameproof glands, otherwise the flame path is compromised. For 4/6-contact schemes, verify terminal count and conduit entry capacity.

Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf), sections 1.3.4 and 1.4.3, shaft, conduit entry and pneumatic accessory tables; terminal diagrams subject to the supplied manual.

V. Area Classification Limits on Contact Forms

Area classificationAllowed contacts/busesProhibited or restricted
0 (Ex ia intrinsically safe)L2, Z2, P2, E2, FF, etc.; barrier required for IS loopAS, DN and ES buses cannot be used in area 0
1 (Ex d IIB, DXP IIB+H2)AS, PB, DN and mechanical/GO Switch contactsSealing required for Group A and B
C (Ex d IIC flameproof)Mechanical/GO Switch contacts and PB bus; non-solenoid versions onlyDXP requires E or M conduit entry
2 (Ex nA non-incendive)Contacts must be L, Z, P, AS, FF or DNM2/M4 mechanical switches, PB/ES not applicable
G / W (general purpose / no certification)Per data sheet configurationNon-flameproof, Type 4X / IP66-68

Ex ia intrinsic safety is NOT Ex d flameproof: IS requires a safety barrier while flameproof relies on the enclosure and flame path; their terminals, grounding and cover-opening rules differ and must never be mixed. If a certificate cannot be found, state "unable to confirm, please verify with the manufacturer".

Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf), area classification and option compatibility tables; Ex markings subject to nameplate and original certificates.

VI. Selection Guide and Common Models

Selection guide: First choose the contact form by the wiring loop: for passive dry contacts with high reliability / intrinsic safety choose GO Switch L2/Z2; for 15 A high-current choose mechanical M2/M4/T2/K2/K4; for DCS NAMUR input choose E2/E4 with isolator; for continuous valve position choose X/H transmitter. Then check area classification: area 0 allows only IS-compatible contacts with a barrier; M2/M4 are not allowed in area 2; flameproof class C is limited to non-solenoid versions. Finally verify conduit entry, O-ring, display and shaft. Combination codes not spelled out in the manual (e.g., 0H, N2) are subject to the original ordering code/nameplate.

Common models: TXS-L2CFLPM (T-Series 316 stainless steel, L2 two GO Switch SPDT sealed dry contacts, class C Ex d IIC flameproof); TXP-M20FLPM (aluminum, M2 two mechanical SPDT, class 0 Ex ia IIC T4 intrinsically safe); DXP-0H0GN4B (D-Series, class 0 IS, NAMUR shaft, conduit entry 4). The GO Switch 35 Series SPDT/DPDT is designed for built-in valve monitoring, 4 A/120 VAC, 3 A/24 VDC.

If you have an old limit switch whose contact form, terminal definition or replacement part needs checking, please send us the nameplate, ordering code and site wiring method. We can review the contact rating, area classification and conduit entry item by item against the official code tables.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.