| SAMSON 3730 - Fail-safe Behavior on Signal Loss | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-24 13:40:51 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The fail-safe behavior of a SAMSON 3730 positioner is determined by the spring-return direction of the actuator: in SAFE mode the positioner vents its output and the valve moves to the mechanical fail-safe position defined during startup. The exact behavior on signal loss, low current or solenoid de-energization depends on the model, wiring and parameters. This article summarizes the topic based on the 3730-3 operating instructions and related data sheets, without claiming unverified functions such as "three-break hold". I. Product Positioning
Source: SAMSON official EB 8384-3 EN (section 7.11.2 Fail-safe position / SAFE) and model data sheets; exact fault current thresholds and safety levels follow the official manual and certificates.
II. SAFE Mode and Mechanical Fail-safe Position
SAFE is an operating mode in which the positioner actively vents so the valve reaches the mechanical fail-safe position; it relies on actuator spring force and is not a position-holding function built into the positioner. If position holding on loss of air and signal is required, external lock-up valves are needed; do not promise "three-break hold" on a standard 3730. III. Signal Loss and Low-Current Behavior
Industry references treat "three-break hold" as a specialty of some brands; the standard SAMSON 3730 is a spring-return fail-safe type on loss of air or power. The exact action and threshold on signal loss must be confirmed against the specific model manual and project wiring diagram. Source: SAMSON EB 8384-3 EN appendix error codes and 3731 platform generic technical data; signal-loss thresholds follow the official manual of the actual model. IV. Solenoid Valve and De-energized Behavior
A de-energized solenoid vents the actuator and is used as a safety trip element for fast fail-safe action. Its normal-open / normal-close direction and wiring must be confirmed in the project loop diagram, not inferred from the positioner model alone. V. Sub-Series Safety Boundaries
The 3.8 mA / 4.4 mA emergency shut-off thresholds apply only to the corresponding function digit of the 3730-6 TS safety version and must not be transferred to a standard 3730-3. Where flameproof protection is required, select the 3731 series rather than promising Ex d on 3730-0/1/2/3/4/5. Source: SAMSON T 8384-6 EN (3730-6 TS emergency shut-off 3.8 / 4.4 mA), T 8387-3/5 EN (3731 SIL levels) and NA 0122; safety applications follow the SIL certificate. VI. Selection Guide and Common ModelsSelection guide: First define the fail-safe position by actuator spring direction (stem extends = air-to-open / fail-close; stem retracts = air-to-close / fail-open); then choose the base model by control method (HART 3730-3, PA 3730-4, FF 3730-5, pressure monitoring 3730-6, flameproof 3731); then select the solenoid (ordering digit P3=4, 24 V DC), inductive limit switch and EXPERTplus diagnostics as needed; for SIS duties use 3730-6 TS or the 3731 series and verify the SIL certificate, never writing a standard 3730 as a safety type. Exact signal-loss and low-current thresholds follow the specific model manual and project wiring diagram. Common models: 3730-3 (HART, with or without 24 V DC solenoid), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring), 3730-6 TS (TROVIS SAFE with emergency shut-off), 3731-3 / 3731-5 (flameproof Ex d). Any "position hold on signal loss" requirement must be verified with an external lock-up scheme and cannot be promised by a standard 3730. If you need to confirm the valve action on signal loss, air loss or power loss, please send us the actuator model, wiring diagram and positioner ordering code. We can review the fail-safe position, solenoid status and safety options against the official manual. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |