SAMSON 3730 - Fail-safe Behavior on Signal Loss
Release time:2026-11-24 13:40:51 | Views:

The fail-safe behavior of a SAMSON 3730 positioner is determined by the spring-return direction of the actuator: in SAFE mode the positioner vents its output and the valve moves to the mechanical fail-safe position defined during startup. The exact behavior on signal loss, low current or solenoid de-energization depends on the model, wiring and parameters. This article summarizes the topic based on the 3730-3 operating instructions and related data sheets, without claiming unverified functions such as "three-break hold".

I. Product Positioning

ItemDescription
Brand ownershipSAMSON AG, an independent brand
Series3730 series smart electropneumatic positioners and the flameproof 3731 series
Fail-safe basisActuator spring-return direction: stem extends (air-to-open, fail-close) or stem retracts (air-to-close, fail-open)
SAFE modeThe positioner vents the output; the valve moves to the mechanical fail-safe position
Data sourceSAMSON EB 8384-3 EN, T 8384-3/4/5/6 EN, T 8387-3/5 EN, NA 0122

Source: SAMSON official EB 8384-3 EN (section 7.11.2 Fail-safe position / SAFE) and model data sheets; exact fault current thresholds and safety levels follow the official manual and certificates.

SAMSON 3730 series positioner
SAMSON 3730 series positioner, same-series illustration; parameters subject to the official data sheet

II. SAFE Mode and Mechanical Fail-safe Position

ElementOfficial descriptionPoint
How to enterSelect SAFE at Code 0; "S" appears after confirmationSwitching between AUTO / MAN and SAFE is possible at any time
Positioner actionVents the output completelyNo air supplied to the actuator diaphragm chamber
Valve actionMoves to the mechanical fail-safe position defined at startupSpring direction determines fully closed or fully open
How to exitSelect AUTO or MAN at Code 0 and confirmRestores the previous operating mode
DisplayShows current valve position in percent in SAFEReadable when initialized

SAFE is an operating mode in which the positioner actively vents so the valve reaches the mechanical fail-safe position; it relies on actuator spring force and is not a position-holding function built into the positioner. If position holding on loss of air and signal is required, external lock-up valves are needed; do not promise "three-break hold" on a standard 3730.

III. Signal Loss and Low-Current Behavior

ItemOfficial data / basisNote
Input signal4-20 mA two-wire; minimum current 3.6 mA (for display); load at 20 mA up to 450 ohm (3731 platform)Below minimum current, follow the fault logic in the manual
Static destruction limit40 V with internal current limit 60 mA (3731 platform)Wiring and loop design must comply
Fault alarm outputSpecific error codes (57, 58, 60, 62, 64-70, 76) always trigger the fault alarm outputCodes 32 / 33 only affect some condensed-state alarms
Three-break holdNot listed as a standard 3730 feature in the official catalogIf required, use an external lock-up scheme and verify separately
Exact thresholdFollow the manual of the actual modelIf not found, state "subject to official manual / nameplate"; do not invent

Industry references treat "three-break hold" as a specialty of some brands; the standard SAMSON 3730 is a spring-return fail-safe type on loss of air or power. The exact action and threshold on signal loss must be confirmed against the specific model manual and project wiring diagram.

Source: SAMSON EB 8384-3 EN appendix error codes and 3731 platform generic technical data; signal-loss thresholds follow the official manual of the actual model.

IV. Solenoid Valve and De-energized Behavior

StateDisplay / actionNote
Solenoid installed and energizedCode 45 shows YES / HIGH alternatelySolenoid energized; air path held per configuration
Solenoid installed but de-energizedCode 45 shows YES / LOW alternatelyActuator vented, "S" icon shown, in fail-safe position
No solenoid installedCode 45 shows NoNo solenoid-related action
Ordering code P30 = none; 4 = with 24 V DC solenoid valveFill per the 3730-3 digit table

A de-energized solenoid vents the actuator and is used as a safety trip element for fast fail-safe action. Its normal-open / normal-close direction and wiring must be confirmed in the project loop diagram, not inferred from the positioner model alone.

V. Sub-Series Safety Boundaries

ModelSafety-related featureBoundary
3730-3HART; SIL 2 / SIL 3 depending on configurationMainly intrinsic safety Ex ia; no flameproof Ex d
3730-4 / 3730-5PROFIBUS PA / FF busDiagnostics over bus per T 8384-4/5 EN
3730-6 TSTROVIS SAFE version; emergency shut-off thresholds 3.8 mA / 4.4 mAFor SIS on/off safety duties; verify against SIL certificate
3731-3 / 3731-5Flameproof Ex d enclosure; SIL 2 single / SIL 3 redundant15-digit ordering code per T 8387-3/5 EN

The 3.8 mA / 4.4 mA emergency shut-off thresholds apply only to the corresponding function digit of the 3730-6 TS safety version and must not be transferred to a standard 3730-3. Where flameproof protection is required, select the 3731 series rather than promising Ex d on 3730-0/1/2/3/4/5.

Source: SAMSON T 8384-6 EN (3730-6 TS emergency shut-off 3.8 / 4.4 mA), T 8387-3/5 EN (3731 SIL levels) and NA 0122; safety applications follow the SIL certificate.

VI. Selection Guide and Common Models

Selection guide: First define the fail-safe position by actuator spring direction (stem extends = air-to-open / fail-close; stem retracts = air-to-close / fail-open); then choose the base model by control method (HART 3730-3, PA 3730-4, FF 3730-5, pressure monitoring 3730-6, flameproof 3731); then select the solenoid (ordering digit P3=4, 24 V DC), inductive limit switch and EXPERTplus diagnostics as needed; for SIS duties use 3730-6 TS or the 3731 series and verify the SIL certificate, never writing a standard 3730 as a safety type. Exact signal-loss and low-current thresholds follow the specific model manual and project wiring diagram.

Common models: 3730-3 (HART, with or without 24 V DC solenoid), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring), 3730-6 TS (TROVIS SAFE with emergency shut-off), 3731-3 / 3731-5 (flameproof Ex d). Any "position hold on signal loss" requirement must be verified with an external lock-up scheme and cannot be promised by a standard 3730.

If you need to confirm the valve action on signal loss, air loss or power loss, please send us the actuator model, wiring diagram and positioner ordering code. We can review the fail-safe position, solenoid status and safety options against the official manual.