SAMSON 3730 - Process Value Monitoring & Communication Variables
Release time:2026-11-24 13:40:51 | Views:

SAMSON 3730 positioners expose set-point deviation, travel times, output signal level and solenoid status through the local LCD and HART / PROFIBUS PA / FOUNDATION Fieldbus interfaces; the 3730-6 additionally monitors supply pressure and output (signal) pressure. Based on the 3730-3 operating instructions EB 8384-3 EN code list and the series data sheets, this article summarizes readable variables, communication version differences and NE 107 status classes. Variable numbers follow the device description (DD/DTM).

I. Product Positioning

ItemDescription
Brand ownershipSAMSON AG, an independent brand
Series3730-0/1/2/3/4/5 plus 3730-6 and 3731 series
Local interfaceLCD with single rotary pushbutton; variables by numbered codes
CommunicationHART (3730-3), PROFIBUS PA (3730-4), FF (3730-5), HART plus pressure monitoring (3730-6)
DiagnosticsEXPERT / EXPERTplus with NAMUR NE 107 status indication
Data sourceSAMSON official EB 8384-3 EN, T 8384-3/4/5 EN, T 8384-6 EN, NA 0122

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, NA 0122 and operating instructions EB 8384-3 EN; variables follow the original device description and firmware version.

SAMSON 3730 series positioner
SAMSON 3730 series positioner, same-series illustration; parameters subject to the official data sheet

II. Locally Readable Process and Device Variables

CodeVariableType and range
39Set-point deviation eRead only, -99.9 to 99.9 %, e = w - x
40 / 41Opening / closing travel timeRead only, 0 to 240 s, minimum measured during initialization
42Automatic set point Auto-wRead only, 0.0 to 100.0 %, corresponding to 4-20 mA
43Firmware versionRead only, positioner type and firmware shown alternately
44Control signal yRead only, 0 to 100 % / OP (fully vented) / MAX (maximum output pressure)
45Solenoid statusRead only, YES / HIGH / LOW / No; LOW means actuator vented and in fail-safe position
37 / 38Position transmitter / inductive limit switchRead only, indicates whether the option is installed

These variables can be read on the local LCD by code or via the communication interface by the control / asset management system. HART variable numbers and names follow the DD / DTM files; this article lists only variables explicitly documented in the official manual.

Source: SAMSON EB 8384-3 EN appendix code list (Codes 37-45); HART variable mapping follows FDT/DTM and DD files.

III. Communication Versions and Variable Differences

ModelProtocolVariable / function focusOrdering code point
3730-3HART, 4-20 mA two-wireDeviation, travel times, output, diagnostics; HART load max 410 ohm16 digits; Ex protection uses 1 digit P1
3730-4PROFIBUS PABus process values and diagnostics per PA profile16 digits; 4th digit fixed to 0
3730-5FOUNDATION FieldbusFunction blocks (PID/AO/DI) and process values per FF configuration16 digits; Ex protection uses 4 digits; leak sensor option
3730-6HART plus pressure monitoringAdds online supply pressure and output (signal) pressure monitoring14 digits; Ex protection uses 3 digits P1-P3
3731-3 / 3731-5HART / FF, flameproof Ex dSame platform as the corresponding 3730 model, flameproof enclosure15 digits per T 8387-3/5 EN

The 3730-4 is the PROFIBUS-PA version, the 3730-6 the 14-digit pressure-monitoring version and the 3731 the flameproof Ex d family. Their variable sets and ordering-code structures differ and must not be mixed.

IV. 3730-6 Pressure Monitoring Variables

Monitoring itemDescriptionPurpose
Supply pressureOnline monitoring via integrated pressure sensorAir quality and low-supply alarm
Output / signal pressureOnline monitoring via integrated pressure sensorValve thrust and actuator diagnostics
Pressure value transmissionPressure measurements superimposed over HARTControl system reading and trending
Exclusive Ex optionEx d[ja] / Ex db[ja], ordering code 210 / 211Not available on 3730-0/1/2/3/4/5

Source: SAMSON official data sheet T 8384-6 EN and NA 0122; the 3730-6 ordering code has 14 digits and must not be confused with the 16-digit table of the 3730-3. Pressure alarm thresholds follow the official manual setting ranges.

V. NE 107 Status and Diagnostic Indication

Status classDisplay meaningAction orientation
NormalNo errorNormal operation
Out of specificationOut of specificationCheck duty and device condition
Maintenance requiredMaintenance requiredPlanned inspection
Maintenance demandedMaintenance demandedArrange maintenance soon
Maintenance alarmMaintenance alarmHandle immediately

EXPERT / EXPERTplus diagnostics classify errors into these states and transmit them via the fault alarm output or bus alarm. Codes 32 / 33 set whether errors are reported in the condensed "function check" and "maintenance required" states, but specific error codes (for example 57, 58, 60, 62, 64-70, 76) always trigger the fault alarm output.

VI. Selection Guide and Common Models

Selection guide: First determine the variable access path by protocol: HART uses 3730-3, PROFIBUS PA 3730-4, FF 3730-5, pressure monitoring 3730-6 and flameproof duties 3731. Then confirm whether set-point deviation, travel times, output y and solenoid status need to be read locally. Then select position transmitter, inductive limit switch, solenoid valve and diagnostic tier per control system requirements. All variable numbers follow the corresponding DD/DTM and firmware version, not menus from another model.

Common models: 3730-3 (HART, commonly used for Codes 39-45), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (supply / output pressure monitoring, 14-digit code), 3731-3 / 3731-5 (flameproof Ex d). Configurations with position transmitter, EXPERTplus and solenoid valve are filled in per the relevant ordering-code digits.

If you need to verify readable variables or HART / bus mapping of a 3730, please send us the model, firmware version and communicator / system readings. We can review the variables and status classes against the official manual and device description.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.