The SAMSON 3730 series smart electropneumatic positioner uses a hybrid platform of analog PD control plus a microprocessor. It offers four initialization modes - MAX, NOM, MAN and SUb - plus tuning parameters for pin position, nominal travel, direction of action, volume restriction and travel time. This article summarizes the auto-tuning workflow and tuning parameters based on the official 3730-3 data sheet T 8384-3 EN and operating instructions EB 8384-3 EN, and distinguishes 3730-3/4/5/6 from the flameproof 3731 series.

I. Product Positioning

ItemDescription
Brand ownershipSAMSON AG, an independent brand
Series3730 series smart electropneumatic positioners (3730-0/1/2/3/4/5)
Control principleAnalog PD control plus microprocessor (hybrid technology platform)
InitializationMAX / NOM / MAN / SUb modes
Display and operationLCD with single rotary pushbutton; settings by numbered codes
Data sourceSAMSON official data sheets T 8384-3/4/5 EN, T 8384-6 EN and operating instructions EB 8384-3 EN

Source: SAMSON official data sheets T 8384-3/4/5 EN, NA 0122 and operating instructions EB 8384-3 EN; parameters follow the latest original documents.

SAMSON 3730 series positioner
SAMSON 3730 series positioner, same-series illustration; parameters subject to the official data sheet

II. Four Initialization Modes

ModeOfficial nameMeaning and application
MAXMaximum rangeInitialization over the full travel from the closed position to the opposite actuator stop
NOMNominal rangeInitialization to the entered nominal travel / angle; the positioner checks the valve can pass it without collision
MANManual settingMove the valve manually to OPEN; the positioner computes the difference as the operating range
SUbSubstitute calibrationControl parameters are estimated without full initialization; used to replace a positioner while the process runs

Before initialization, complete mechanical mounting, pneumatic and electrical installation. Enter Code 3 to enable configuration (expires after 120 seconds without input), then set Code 4 pin position, Code 5 nominal range and Code 6 initialization mode, and press INIT. In NOM mode, if the maximum possible travel is smaller than the entered nominal travel, initialization is canceled with Code 52.

Source: SAMSON EB 8384-3 EN section 7.6 (MAX / NOM / MAN / SUb initialization) and code list.

III. Pin Position and Nominal Travel

Code 4 pin positionStandard travelCode 5 adjustment range (mm)
17 mm7.5 mm3.6 - 17.7
25 mm7.5 mm5.0 - 25.0
35 mm15.0 mm7.0 - 35.4
50 mm30.0 mm10.0 - 50.0
70 mm40.0 mm14.0 - 70.7
100 mm60.0 mm20.0 - 100.0
200 / 300 mm120.0 mm40.0 - 200.0
90 degrees (rotary)90.0 degrees24.0 - 100.0

A pin position that is too small makes the positioner switch to SAFE mode for safety reasons. Code 5 is available only after Code 4 is selected. After successful initialization, Code 7 shows the direction of action: air-to-open remains increasing/increasing, air-to-close changes to increasing/decreasing; it can be changed manually if necessary.

IV. Tuning-Related Parameters

Parameter / CodeOfficial valuesTuning significance
Volume restriction QMIN SIDE / MAX SIDE / MIN BACK / MAX BACKAdapts air output capacity to actuator size: MIN for actuators below 240 cm2 or travel time below 1 s, otherwise MAX; SIDE/BACK per signal pressure connection
Code 7 directionSame / oppositeRelationship between set point w and travel x; adapted automatically after initialization
Code 39 deviation-99.9 to 99.9 %Read only, e = w - x, for observing steady-state deviation
Code 40/41 travel time0 to 240 sRead only, minimum opening / closing time measured during initialization
Code 44 output y0 to 100 % / OP / MAXRead only, control signal in percent
Code 36 resetStd / diAGStd resets all parameters and requires re-initialization; diAG resets diagnostics only

The volume restriction is a start-up setting; after changing it the positioner must be initialized again. With an analog input option, MIN SIDE must always be used for actuators with an air volume below one liter. Travel time can be adjusted separately for inflation and exhaust within 0-240 s to suppress oscillation of small actuators or meet slow process requirements.

Source: SAMSON EB 8384-3 EN section 7.2 Volume restriction Q and appendix code list (Codes 36-44); tuning ranges follow the manual for the specific firmware version.

V. Sub-Series Differences and Initialization Boundaries

ModelCommunication / featureInitialization and tuning hint
3730-3HART, 16-digit ordering codeThis article's workflow follows EB 8384-3 EN
3730-4PROFIBUS PA, 16 digits, 4th digit fixed to 0Follow T 8384-4 EN and bus configuration tool
3730-5FOUNDATION Fieldbus, 16 digits, Ex protection uses 4 digitsFollow T 8384-5 EN and function block configuration
3730-6HART plus pressure monitoring, 14-digit codeSame platform but different code structure; do not apply the 16-digit table
3731-3 / 3731-5Flameproof Ex d versionsOrdering code per T 8387-3/5 EN, separate digit table

All 3730 sub-series share the control platform but differ in ordering-code length and Ex encoding. 3730-0/1/2 are non-communication basic types, 3730-4 is PROFIBUS-PA, 3730-6 is the 14-digit pressure-monitoring type and 3731 is the flameproof Ex d type; digit tables must not be mixed.

VI. Selection Guide and Common Models

Selection guide: First choose the base model by communication (non-communication 3730-0/1/2, HART 3730-3, PROFIBUS PA 3730-4, FF 3730-5, pressure monitoring 3730-6, flameproof 3731); then select bracket and pin position by mounting; then set volume restriction Q by actuator air volume; complete NOM or MAX initialization by valve type, using MAN or SUb where needed; finally verify direction of action, travel time and diagnostic options. All tuning parameters follow the data sheet and operating instructions of the specific model, not menus from another sub-series.

Common models: 3730-3 (HART, widely used), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring, 14-digit code), 3731-3 / 3731-5 (flameproof Ex d), 3730-1 / 3730-2 (non-communication digital types). Configurations with EXPERTplus diagnostics, position transmitter and solenoid valve are filled in per the ordering-code digits.

If you need to check the initialization mode, pin position or volume restriction of a 3730, please send us the model, actuator area and travel. We can review the commissioning steps and parameters against the official manual.