The SAMSON 3730 series smart electropneumatic positioner uses a hybrid platform of analog PD control plus a microprocessor. It offers four initialization modes - MAX, NOM, MAN and SUb - plus tuning parameters for pin position, nominal travel, direction of action, volume restriction and travel time. This article summarizes the auto-tuning workflow and tuning parameters based on the official 3730-3 data sheet T 8384-3 EN and operating instructions EB 8384-3 EN, and distinguishes 3730-3/4/5/6 from the flameproof 3731 series. I. Product Positioning
Source: SAMSON official data sheets T 8384-3/4/5 EN, NA 0122 and operating instructions EB 8384-3 EN; parameters follow the latest original documents.
II. Four Initialization Modes
Before initialization, complete mechanical mounting, pneumatic and electrical installation. Enter Code 3 to enable configuration (expires after 120 seconds without input), then set Code 4 pin position, Code 5 nominal range and Code 6 initialization mode, and press INIT. In NOM mode, if the maximum possible travel is smaller than the entered nominal travel, initialization is canceled with Code 52. Source: SAMSON EB 8384-3 EN section 7.6 (MAX / NOM / MAN / SUb initialization) and code list. III. Pin Position and Nominal Travel
A pin position that is too small makes the positioner switch to SAFE mode for safety reasons. Code 5 is available only after Code 4 is selected. After successful initialization, Code 7 shows the direction of action: air-to-open remains increasing/increasing, air-to-close changes to increasing/decreasing; it can be changed manually if necessary. IV. Tuning-Related Parameters
The volume restriction is a start-up setting; after changing it the positioner must be initialized again. With an analog input option, MIN SIDE must always be used for actuators with an air volume below one liter. Travel time can be adjusted separately for inflation and exhaust within 0-240 s to suppress oscillation of small actuators or meet slow process requirements. Source: SAMSON EB 8384-3 EN section 7.2 Volume restriction Q and appendix code list (Codes 36-44); tuning ranges follow the manual for the specific firmware version. V. Sub-Series Differences and Initialization Boundaries
All 3730 sub-series share the control platform but differ in ordering-code length and Ex encoding. 3730-0/1/2 are non-communication basic types, 3730-4 is PROFIBUS-PA, 3730-6 is the 14-digit pressure-monitoring type and 3731 is the flameproof Ex d type; digit tables must not be mixed. VI. Selection Guide and Common ModelsSelection guide: First choose the base model by communication (non-communication 3730-0/1/2, HART 3730-3, PROFIBUS PA 3730-4, FF 3730-5, pressure monitoring 3730-6, flameproof 3731); then select bracket and pin position by mounting; then set volume restriction Q by actuator air volume; complete NOM or MAX initialization by valve type, using MAN or SUb where needed; finally verify direction of action, travel time and diagnostic options. All tuning parameters follow the data sheet and operating instructions of the specific model, not menus from another sub-series. Common models: 3730-3 (HART, widely used), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring, 14-digit code), 3731-3 / 3731-5 (flameproof Ex d), 3730-1 / 3730-2 (non-communication digital types). Configurations with EXPERTplus diagnostics, position transmitter and solenoid valve are filled in per the ordering-code digits. If you need to check the initialization mode, pin position or volume restriction of a 3730, please send us the model, actuator area and travel. We can review the commissioning steps and parameters against the official manual. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |