| Masoneilan SVI3 & Actuator Matching - Tuning Points | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-24 13:40:51 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Masoneilan SVI3 positioner is nominally single-acting. Matching it to an actuator involves actuation mode, travel range, magnet configuration, supply pressure and air-volume matching, SmartCal one-button calibration and preset tuning groups. This article summarizes these matching and tuning points based on the SVI3 official data sheet and manual, and explains the magnet and bracket rules shared with SVi1000 / SVI2. Specific figures follow the official data sheet and nameplate. I. Product Positioning
Source: Masoneilan official SVI3 Fact Sheet / Data Sheet and SVI3 Instruction / Operation Manual; mounting and magnet rules cross-checked against the three-generation SVi1000 / SVI II AP / SVI3 data sheets.
II. Actuation Mode and Actuator Matching
The reversing booster is optional: SVi1000 and SVI3 are nominally single acting and require a reversing booster for double acting; SVI II AP natively supports single and double acting. These capabilities must not be written as identical. III. Travel and Magnet Configuration
Confirm whether the valve is linear or rotary before quotation and give the correct magnet type. End users should proactively order the magnet with the positioner to avoid an incomplete delivery. Bracket and magnet compatibility follows the official list. Source: Compilation of Masoneilan official SVi1000 / SVI II AP / SVI3 manuals and selection data (magnet configuration requirements chapter). IV. SmartCal Calibration and Preset Tuning Groups
SmartCal is the official SVI3 function name. Calibration results depend on travel end points, supply pressure and magnet installation quality; after calibration, recheck end points and direction and recalibrate if necessary per the manual. V. Supply Air, Air Volume and Response Tuning
Source: Masoneilan SVI3 official Fact Sheet / Data Sheet, Pneumatic / Specifications sections; volume boosters and reversing boosters are optional accessories verified against the official list. VI. Selection Guide and Common ConfigurationsSelection guide: First confirm actuator actuation mode (single / double acting) and fail-safe position; double acting needs a reversing booster. Then confirm valve travel type and value and select the matching linear / rotary magnet and bracket without duplicate magnet orders. Then verify that supply pressure exceeds the spring-range upper limit and add a volume booster if needed. Finally use SmartCal to set travel end points, air action, autotuning and preset tuning groups. Diagnostic tier, 4-20 mA retransmission and remote position sensor are set by IO options, and the final ordering code follows the official tool output. Common configurations: SVI3 single acting with linear magnet and standard bracket (general globe valve); SVI3 single acting with rotary magnet and rotary bracket (ball / butterfly valve); SVI3 with reversing booster (double-acting actuator); SVI3 with volume booster (large air volume / long stroke); SVI3 with 4-20 mA retransmission (IO option f=2) and remote position sensor for split mounting. If you are matching an SVI3 to an actuator, please send us the valve travel type, travel value, single / double acting and supply pressure. We can review the magnet, bracket, booster and tuning parameters against the official data sheet. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||