Home » Service & Support » Technical Documentation
Fisher DVC2000 vs DVC6200 - Spare Parts List Comparison
Release time:2026-11-24 09:02:41 | Views:

Fisher DVC2000 and DVC6200 both belong to the FIELDVUE digital valve controller family, but they are different platforms: the DVC2000 is an entry-level, single-acting, aluminum unit with an LCD and four pushbuttons, while the DVC6200 is a mid-to-high-end platform supporting HART / FF / PROFIBUS PA and multiple diagnostic levels. Their spare-part systems therefore differ. This article compares their spare parts lists based on Fisher parts lists and manuals.

I. Product Positioning

ItemContent
Brand / ownershipFisher, an Emerson brand
ComparisonDVC2000 (entry level) vs DVC6200 (mid-to-high-end / project)
Common pointsHall-effect non-contact position feedback; configuration and diagnostics via HART communicator / ValveLink
Core differenceDVC2000 single-acting, aluminum, with LCD; DVC6200 single/double acting, aluminum or stainless, no LCD (LED status)
SourceFisher parts number compilation, DVC6200 manual D103409X012, data sheet D104363X0CN

Source: Fisher digital valve controller data sheet D104363X0CN and DVC6200 manual D103409X012. Part numbers are subject to the official parts list.

Illustration, not the exact model
Fisher DVC6200 digital valve controller, same-series illustration

II. Platform Comparison

FeatureDVC2000DVC6200
CommunicationHART 5 (4-20 mA)HART 5 / 7, FF, PROFIBUS PA; SIS version also available
ActuationSingle actingSingle acting / double acting
HousingAluminumAluminum or stainless steel
Local interfaceLCD + 4-key LUI (multiple languages)No LCD / no keys, LED status
Remote mountNot applicableDVC6205 + DVC6215
Extreme low temperaturePer data sheetXT option -52 C (stainless housing with fluorosilicone standard)

Source: Fisher D104363X0CN, D103409X012, D103557X012 (DVC6200 SIS); subject to the official data sheet.

III. Spare Parts List Comparison

DVC6200 categoryPart number (example)Description
I/P converter kit38B6041X152I/P CONVERTER, standard (listed under DVC6000; confirm for DVC6200 by manual)
Cover assembly38B9580X022 / X032 / X042Standard aluminum / extreme-temperature aluminum / stainless steel
Pressure gauge18B7713X012 / X022 / X032 / X042 / X072 / X0822013 list; 2 required single acting, 3 double acting; different ranges/units
Junction box19B5401X012 / X022 / X032 / X042Standard / extreme-temperature / natural-gas approval combinations
Magnetic feedback arrayGG20243X012DVC6200 SIS sliding-stem feedback kit
Controller assemblyGE40184XAT2HART / housing type B / aluminum / with I/O / double acting
DVC2000 counterpartDescription
Gauge / cover / I/PThe DVC2000 is a separate platform; its part numbers are not interchangeable with DVC6200. Refer to the DVC2000 official parts list
FeedbackDVC2000 uses Hall-effect non-contact feedback; DVC6200 uses a magnetic array / magnet strip; mounting parts differ
Mounting bracketSome brackets fit both DVC2000 and DVC6200 (e.g. stainless bracket for 657/667), but must be checked against the actuator model
Common magnet stripsR4300AAX012/112, GE43895X012, GE02575X012 selected by travel; not interchangeable across different series

Source: Fisher parts number compilation, DVC6200 manual replacement-parts chapter and the pressure gauge parts compilation. Where DVC2000 part numbers are not listed in official sources, state 'subject to the official manual / nameplate'.

IV. Spare Parts Ordering and Identification

PointDescription
Order by serial numberBodies and most structural parts are ordered by serial number + size + material; manuals list key numbers, not single part numbers
Diagnostic level vs partsAC / HC / AD / PD / ODV are software/firmware levels, not mechanical spares; upgrades require manual verification and authorization
Material distinctionAluminum and stainless covers and junction boxes have different part numbers; extreme-temperature versions use fluorosilicone
No interchangeDVC2000 and DVC6200 feedback, covers and gauges are not interchangeable; verify against the order confirmation and packing list

Source: Fisher DVC6200 manual Replacement Parts chapter. The data in this article was obtained via web search. Source: Emerson DVC6200 product page https://emerson.com/en/final-control/products/fisher-dvc6200.

V. Selection Guide and Common Models

Selection guide: First identify whether the installed device is a DVC2000 or DVC6200 (including H/F/P/SIS variants); then determine housing, actuation and diagnostic level from the ordering code; finally check spares by category (I/P, cover, gauge, feedback, junction box). ODV is a diagnostic level for DVC6200H (HART) only, not a spare part. Where a part number cannot be found, do not assume one - refer to the official manual / nameplate.

Common models: DVC2000; DVC6200H / F / P, DVC6200 SIS; remote DVC6205 + DVC6215.

If you need to verify a spare part number for a positioner, please send us the ordering code, serial number and nameplate photo. We can distinguish the parts applicable to DVC2000 and DVC6200 against the Fisher official parts list to avoid a wrong shipment.