Fisher DVC6200 HART Communication Variables & Parameter Mapping
Release time:2026-11-24 09:02:41 | Views:

The Fisher FIELDVUE DVC6200 is a digital valve controller with Hall-effect, linkage-less position feedback. Protocol variants include DVC6200H (HART), DVC6200F (FOUNDATION fieldbus) and DVC6200P (PROFIBUS PA), plus DVC6200 SIS with partial stroke testing. On HART versions the loop exposes valve position, setpoint, travel and diagnostic variables. This article covers the protocol variants, HART variables and parameter mapping, and clarifies that ODV diagnostics apply to the HART version only.

I. Product Positioning

ItemContent
Brand / ownershipFisher, an Emerson brand
SeriesFIELDVUE DVC6200 digital valve controller
FeedbackHall-effect, linkage-less, non-contact position feedback with no mechanical wear
Input / air supply4-20 mA DC; maximum inlet 10.0 bar (145 psig) or actuator rating, whichever is lower
Linearity / enclosureIndependent linearity typically ±0.50% of output span; CSA/FM Type 4X, IP66; ATEX/IECEx IP66
SourceFisher DVC6200 manual D103409X012; data sheet D104363X0CN

Source: Fisher FIELDVUE DVC6200 manual D103409X012 Table 1-2 and digital valve controller data sheet D104363X0CN. The data in this article was obtained via web search. Source: Emerson DVC6200 product page https://emerson.com/en/final-control/products/fisher-dvc6200.

Illustration, not the exact model
Fisher DVC6200 digital valve controller, same-series illustration

II. Protocol Variants

ModelProtocolKey difference
DVC6200HHART 5 (H7 option enables HART 7)Only the HART version supports AC auto-calibration and ODV diagnostics
DVC6200FFOUNDATION fieldbusDiagnostic level written as FD; no ODV; PS partial stroke test optional
DVC6200PPROFIBUS PADoes not support ODV; some AD/PD diagnostic combinations unavailable
DVC6200 SISHART 5 (HART 7 optional)SIL3 (exida), standard PST, low-air-consumption booster for safety instrumented systems

Source: Fisher DVC6200 SIS manual D103557X012, DVC6200 manual D103409X012 and data sheet D104363X0CN; ODV level per D103605X012.

III. HART Variables and Parameter Mapping

Variable / parameterMeaningSource / mapping
PV (primary variable)Stem travel / valve position (mapped to rotary travel when configured)Measured by non-contact Hall feedback; 4-20 mA input is A/D converted and compared with travel
SP / setpointTarget position corresponding to the control system input current4 mA = 0% (or configured low); 20 mA = 100% (or configured high); split range supported
Output pressurePneumatic signal to the actuatorController drives I/P and booster from the error; travel span 0.4-9.5 bar
Travel / end pointsCalibrated zero and full travelDefined by auto-calibration (AC) or manual travel calibration
VariableTypical range / note
Input signal4-20 mA DC; minimum 11 V at the terminals for HART point-to-point; multi-drop 11-30 VDC at 8 mA; max 30 VDC
Input impedanceEquivalent 550 ohm (about 11 V at 20 mA)
Steady-state air consumptionStandard relay below 0.38 Nm3/h at 1.4 bar and below 1.3 Nm3/h at 5.5 bar; lower with low-consumption relay
Independent linearityTypically ±0.50% of output span

Source: Fisher D103409X012 Table 1-2 Specifications. Parameters are subject to the official manual and device configuration; no variable values are assumed.

IV. Diagnostic Levels and ODV Limitation

LevelFunctionApplicable protocol
ACAuto-calibration set up through a device communicatorDVC6200H only
HC / FDBasic HART / fieldbus communication and alarmsHC for HART, FD for FF; same function
ADAdvanced diagnostics: adds offline diagnostics (requires ValveLink)HART / FF; not P
PDPerformance diagnostics: adds online diagnostics (requires ValveLink)HART / FF; not P
ODVOptimized Digital Valve: all HC/AD/PD functions plus PST and lead/lag setpoint filterDVC6200H (HART) only, per D103605X012
PSPartial stroke action testDVC6200F only

The data in this article was obtained via web search. Source: Emerson DVC6200 product page https://emerson.com/en/final-control/products/fisher-dvc6200; level definitions are subject to Fisher D104363X0CN and D103605X012.

V. Selection Guide and Common Models

Selection guide: Choose H/F/P by the control system protocol, then the hazard approval and housing material (aluminum or stainless steel), then verify air supply, actuator action and feedback mounting, and finally select the diagnostic level. ODV applies only to the HART version DVC6200H; DVC6200F and DVC6200P do not offer ODV; SIS projects should select DVC6200 SIS. The exact variable list is subject to configuration and the official manual.

Common models: DVC6200H (HART), DVC6200F (FF), DVC6200P (PROFIBUS PA), DVC6200 SIS; remote-mount versions DVC6205 + DVC6215; DVC6200S stainless-steel housing variant.

If you need to verify the protocol variant of a DVC6200 or whether an ODV diagnostic level applies, please send us the ordering code and control system protocol. We can review the communication variables and diagnostic levels item by item against the Fisher official data sheet.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.