Control Valves - Cv / Kv Conversion & Unit Systems
Release time:2026-11-23 15:03:23 | Views:

Cv and Kv are the two core flow coefficient (flow capacity) indices of control valves. They belong to the imperial and metric unit systems respectively and convert into each other by fixed factors. This article covers the definitions, unit systems, conversion relationship, sizing framework for liquid/gas/steam, and selection checkpoints. The formulas listed are industry-recognized expressions; specific values are subject to the official data sheet and the original standard.

I. Definition and Unit Systems

ItemDescription
MeaningFlow capacity coefficient describing the flow a valve passes at a given travel and pressure drop; the core basis for valve size and trim selection
Cv (imperial)US gallons per minute of 60 F water flowing through a fully open valve at 1 psi pressure drop
Kv (metric)Cubic meters per hour of water flowing through a fully open valve at 1 bar pressure drop
ConversionCv = 1.156 x Kv; Kv = 0.865 x Cv (exact factor varies slightly with the unit basis)
Main standardsANSI/ISA-75.01.01, IEC 60534-2-1, VDI/VDE 2173 (Kv definition)
NatureCv/Kv is a tested value of valve design (size, trim, travel), not a fluid or operating parameter

Cv/Kv is measured by the manufacturer and varies with valve opening; when sizing, request the Cv-versus-travel curve for the relevant opening rather than only the fully open maximum.

Source: Fluid Control Institute Tech Sheet CVR 409; ANSI/ISA-75.01.01, IEC 60534-2-1, VDI/VDE 2173; definitions and conversion data from web search, source: https://www.fluidcontrolsinstitute.org/assets/downloads/SpecSheetsTechDocs/TechDocs/ControlValveRegulator/TechSheet409_MetricDefinitionCoefficient.pdf

Control valve illustration
Control valve illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Conversion and Unit Comparison

QuantityCv (US)Kv (metric)
Flow rate QUS gpm (gallons/min)m3/h (cubic meters/hour)
Pressure drop dPpsibar
Test mediumWater, 60 F (approx. 15.6 C)Water, stated reference temperature (approx. 5-30 C)
Conversion factorCv = 1.156 x KvKv = 0.865 x Cv
SourceFCI CVR 409 / ISA-75.01.01VDI/VDE 2173 / IEC 60534
CvKv (= 0.865 x Cv)Note
10.865Base conversion point
108.65Common small-bore range
5043.3Medium bore
120104Common large-bore range

Source: conversion factors and example data from web search, sources: https://www.wikiwand.com/en/Flow_coefficient and http://vakovalve.com/news-detail/Valve-Cv-and-Kv-Explained--Definitions--Conversion-and-Sizing-Calculations; subject to the official data sheet / original standard.

III. Sizing Framework

ServiceFormula (recognized expression)Key point
Liquid (turbulent, non-choked)Cv = Q x sqrt(Gf / dP)Q in US gpm, Gf specific gravity, dP in psi
Liquid (metric)Kv = Q x sqrt(rho / (1000 x dP))Q in m3/h, rho in kg/m3, dP in bar
Gas / steamISA/IEC compressible-flow equationsUse absolute pressure with compressibility factor Z and temperature T; choked flow at critical drop
Viscosity correctionFR at low Reynolds numberHigh-viscosity media corrected per the official method
Fitting correctionFP for reducers/expandersCorrect per standard when mounted between size changes

Never apply the liquid formula to gas or steam; choked flow, flashing and cavitation change the applicability of the simple formula and require the official sizing software or the original standard.

Source: sizing formulas and correction factors from web search, sources: https://www.vajravyuh.com/blog/valve-sizing-pressure-drop-cv-calculation and http://vakovalve.com/news-detail/Valve-Cv-and-Kv-Explained--Definitions--Conversion-and-Sizing-Calculations; subject to the original standard.

IV. Leakage Class and Its Relation to Cv

ItemDescription
Leakage standardANSI/FCI 70-2 and IEC 60534-4
ClassesClass II, III, IV, V, VI (VI strictest, common with soft seat)
Relation to CvAllowable leakage is often expressed as a percentage of rated Cv, so Cv is also the basis for leakage calculation
Test conditionsPer the standard pressure drop, medium and temperature; subject to the official test report
NoteCv does not indicate cavitation, noise, exit velocity or operating torque; check these separately

Source: ANSI/FCI 70-2, IEC 60534-4; the relation between leakage class and rated Cv is described in FCI Tech Sheet CVR 409.

V. Selection Guide and Common Mistakes

MistakeCorrect practice
Comparing metric enquiry directly against imperial data sheetUnify Cv/Kv units before comparing to avoid unit errors
Sizing valve by pipe diameterSelect valve size and trim from the required Cv; valve body size may differ from pipe size
Oversizing the valveRated Cv is typically about 1.25-1.5 times required Cv; oversizing causes oscillation and wear
Considering only fully open CvCheck the Cv-versus-travel curve and rangeability at the working opening

Selection guide: The path is "define medium and service, choose the liquid/gas/steam formula, calculate required Cv/Kv, unify units, select size and trim from the manufacturer Cv table, then check rangeability, cavitation and noise". This is a general topic; recognized formulas and conversion factors are given, and specific parameters are subject to the official data sheet, original standard and nameplate.

Common models: Conventional control valves provide a series Cv table by size and trim type; small-flow valves can have extremely low Cv and require verification of accuracy and units. Specific values are subject to the selected model's official data sheet.

If you have both Cv and Kv data sheets and are unsure whether the units are mixed, or want to verify whether the required flow capacity matches the valve size, please share the medium, flow rate and pressure drop. We can review the conversion and selection together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.