An electro-pneumatic (I/P) converter converts a 4-20 mA controller output into a proportional 0.2-1.0 bar (3-15 psi) pneumatic signal, interfacing electronic control with pneumatic actuators. Using Fisher 646/846 as examples, this article explains force-balance and nozzle/flapper principles, calibration, general classification and selection points. Parameters are subject to the official manual / nameplate. I. Product Positioning
Source: Fisher 646 electro-pneumatic transducer instruction manual D101351X012; Fisher 846 product bulletin. Principle and calibration data obtained via web search, source: https://www.emerson.com/documents/automation/product-bulletin-fisher-846-electro-pneumatic-transducer-en-11745420.pdf
II. Working Principle
Source: Fisher 646 electro-pneumatic transducer instruction manual D101351X012; Fisher 846 product bulletin. Principle and calibration data obtained via web search, source: https://www.emerson.com/documents/automation/product-bulletin-fisher-846-electro-pneumatic-transducer-en-11745420.pdf The force-balance and nozzle/flapper principle above was obtained via web search, source: https://www.manualslib.com/manual/1372141/Emerson-Fisher-646.html?page=13; construction is subject to the model-specific manual. III. Calibration and Signal Mapping
Source: Fisher 646 electro-pneumatic transducer instruction manual D101351X012; Fisher 846 product bulletin. Principle and calibration data obtained via web search, source: https://www.emerson.com/documents/automation/product-bulletin-fisher-846-electro-pneumatic-transducer-en-11745420.pdf IV. General Classification and Construction
Source: Fisher 646 electro-pneumatic transducer instruction manual D101351X012; Fisher 846 product bulletin. Principle and calibration data obtained via web search, source: https://www.emerson.com/documents/automation/product-bulletin-fisher-846-electro-pneumatic-transducer-en-11745420.pdf Ex ia intrinsic safety and Ex d flameproof enclosure must not be mixed. Where the exact Ex marking, gas group or electrical data cannot be found, write "please consult for confirmation". V. Selection Points
Source: Fisher 646 electro-pneumatic transducer instruction manual D101351X012; Fisher 846 product bulletin. Principle and calibration data obtained via web search, source: https://www.emerson.com/documents/automation/product-bulletin-fisher-846-electro-pneumatic-transducer-en-11745420.pdf Selection guide: The sequence is: input and output range, then supply and mounting, then air consumption, response and Ex approval. The I/P output is a continuous pneumatic signal; if the actuator is slow or large, add a volume booster or positioner. Parameters are subject to the official manual and nameplate. Common models: Common types: Fisher 646 (force-balance basic) and 846 (self-calibrating). Other brands and models differ in ranges, air use and approvals; verify against official data sheets rather than applying values from this article. If you need to convert 4-20 mA into 3-15 psi, or are unsure whether to choose an I/P converter or a positioner, please share the controller output, actuator type and air supply conditions. We can review the output range and air consumption requirements together. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |