Differential Pressure Transmitters - Liquid Level Measurement Applications
Release time:2026-11-23 12:03:36 | Views:

DP level measurement is based on hydrostatics, DP = rho x g x h. Comparing the lower process tap with the vapour or reference side cancels vessel gas pressure. This article covers open tanks, closed tanks with dry or wet leg, and double-flange remote seals, with principles, range calculations, capillary notes and selection points. Formulas and classifications are subject to official data sheets / standards / nameplate.

I. Measurement Principle

ItemDescriptionNote
Basic formulaDP = rho x g x h = SG x h (water column units)rho is liquid density, h is level height
Open tankH side at bottom, L side to atmosphereDP depends only on liquid head
Closed tankH side at bottom, L side to vapour spaceP0 cancels on both sides; DP remains rho x g x h
Condensable vapourWet leg pre-filled on L sideAvoids random error from condensate column
Interface measurementDP = g x h x (rho2 - rho1)Both densities known and stable

Source: General hydrostatic level principles and classification, subject to official data sheets / standards / nameplate; worked example obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation

DP transmitter level measurement illustration
Transmitter illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Range Calculation for Open and Closed Tanks

CaseLRVURVFeature
Open tank, transmitter h below tapSG1 x hSG1 x (h + L)Suppression, positive LRV
Closed tank, dry leg0 (or corrected for vapour offset)SG1 x LNo wet leg; L side stays dry
Closed tank, wet leg (SG2, height H)- SG2 x HSG1 x L - SG2 x HElevation; range often negative
Double-flange remote sealFrom fill-fluid column differenceFrom fill-fluid column differenceCapillary fill density varies with temperature

Source: General hydrostatic level principles and classification, subject to official data sheets / standards / nameplate; worked example obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation

In every case Span should equal SG1 x L. If the calculated Span differs, recheck the arithmetic and units before inspecting the impulse lines for liquid accumulation or blockage. General formulas obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation.

III. Remote Seals and Capillaries

ItemPointRisk
Single flangeFor open tanks; diaphragm contacts processInsertion type for hot, viscous or crystallising media
Double flangeFor closed tanks; remote diaphragms on both sidesFill-fluid density should match on both sides
Fill fluidCompatible with process and temperature rangeDensity change at high temperature causes zero drift
Capillary lengthAs short as practical and equal on both sidesLong lines slow response and increase temperature error
Mounting elevationKeep transmitter near the lower flangeElevation difference adds static head error

Source: General hydrostatic level principles and classification, subject to official data sheets / standards / nameplate; worked example obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation

IV. Density and Temperature Compensation

ConditionEffectAction
Process temperature changeDensity change alters head at same levelRecalculate LRV/URV with actual density
Steam condensationReference leg head becomes unstableUse a maintained wet leg or remote seals
Non-negligible vapour densityVapour head affects DPApply density / pressure compensation
Crystallisation / foulingBlocked tap gives false levelUse insertion flange or purging; please consult for confirmation

Source: General hydrostatic level principles and classification, subject to official data sheets / standards / nameplate; worked example obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation

Where hot density, vapour pressure or other compensation data cannot be obtained from the process package or official sources, write "please consult for confirmation" rather than assume values.

V. Selection Steps

StepActionOutput
1 VesselOpen/closed, condensing or notGP or DP; dry or wet leg
2 RangeL, SG1, h, wet-leg SG2/HLRV, URV, Span
3 ConstructionFlange, remote seal, insertion typeTap and wetted-part solution
4 Service checkTemperature, pressure, corrosion, crystallisationFill fluid and diaphragm material
5 ApprovalsIS/flameproof and area classificationEx code and certificate

Source: General hydrostatic level principles and classification, subject to official data sheets / standards / nameplate; worked example obtained via web search, source: https://zeroandspan.com/blog/zero-suppression-vs-zero-elevation

Selection guide: The path is: vessel and medium, range and shift, flange/remote seal and fill fluid, then Ex approval. The key is not the transmitter itself but stable taps, impulse lines and fill fluid; a wrong shift direction shows up as a constant offset.

Common models: Open tanks may use a GP transmitter or single-flange DP; closed tanks use double-flange DP with a wet leg or remote seals; interface service needs two stable densities. Exact models are subject to the official data sheet and order code.

If you are selecting a DP level solution for a tank or reactor, or are unsure whether to use a dry or wet leg and single or double flange, please share the vessel pressure, process density and temperature range. We can review the range calculation and tap arrangement together.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.