The Honeywell BX/BX2 limit switches are flameproof (Ex d) hazardous-area switches marked II 2 GD Ex db IIC T6 Gb / Ex tb IIIC T85 C Db, with global approvals including UL, CSA, ATEX, IECEx and NEPSI. Selection requires checking the protection level, gas group, temperature class and electrical interface (conduit thread, seals, grounding) item by item. This article covers the Ex marking breakdown, approval comparison and interface selection based on Honeywell's official data sheet and installation instructions.

I. Explosion Protection Marking

Marking segmentMeaning
II 2 GDGroup II surface industry equipment, category 2 (G gas / D dust), for Zone 1/2 and corresponding dust zones
Ex db IIC T6 GbFlameproof enclosure "db", protection level b, gas group IIC, temperature class T6, EPL Gb
Ex tb IIIC T85 C DbDust protection by enclosure "tb", dust group IIIC, max surface temperature 85 C, EPL Db
Temperature rangeFluorosilicone seal -40 to +70 C; fluorocarbon seal -12 to +70 C (depends on seal material)

Ex db is a flameproof enclosure (Ex d), not intrinsic safety Ex ia. Flameproof relies on an enclosure that withstands internal explosion and cools escaping gases through flame paths; intrinsic safety limits circuit energy. Their wiring, cover-opening and installation rules differ and must never be mixed. BX/BX2 are flameproof; if an intrinsically safe loop is required on site, verify whether a corresponding approval exists - if not found, state "unable to confirm, please verify with the manufacturer".

The data in this article was obtained via web search. Source: Honeywell official data sheet 002306 Issue 11, BX2 installation instructions 50047766, BX installation instructions 50083427; standards IEC 60079-0, IEC 60079-1, IEC 60079-31.

Limit switch illustration
Limit switch illustration, not a Honeywell product; parameters subject to the official data sheet

II. Global Approval Comparison

Approval schemeBX/BX2 coverageCertificate / marking (extract)
ATEX (EU)II 2 GD Ex db IIC T6 Gb, Ex tb IIIC T85 C DbSIRA 00ATEX1037X
IECEx (international)Same protection level as ATEXIECEx SIR 07.0102X
NEPSI (China)China explosion-protection approvalGYJ111016
UL / CSA / cULusNEMA 7 gas Class I Div 1&2 Groups B/C/D; NEMA 9 dust Class II Div 1&2 Groups E/F/GUL 894, CSA C22.2 No.25 / No.30
OthersKOSHA/KTL (Korea), INMETRO, EAC, UKEX (selected models)Model-dependent, verify by nameplate

Approvals depend on model and conduit interface; not every combination carries every approval. Verify against the specific ordering code and nameplate. Where a certificate cannot be found, state "unable to confirm, please verify with the manufacturer" and do not imply that only a certain model holds a certain certificate.

The data in this article was obtained via web search. Source: Honeywell official data sheet 002306 Issue 11 Agency Certifications table and installation instructions 50083427; subject to nameplate and original certificates.

III. Electrical Interface Selection

ItemSelection points
Conduit thread0.5"-14 NPT, 0.75"-14 NPT, 20 mm; must match site conduit / gland
Approval vs interfaceData sheet lists approval coverage separately for BX (aluminum) / BX2 (stainless steel) and M20/NPT; check each item before ordering
SealingIP67, NEMA 1/3/4/6/13 (BX2 additionally 4X); verify for outdoor and wash-down environments
GroundingExternal and internal ground screws are provided for agency compliance; ensure reliable equipotential bonding
Electrical ratings10 A continuous; AC15 A600, DC13 R300; 24 VDC inductive / resistive 10 A each

The conduit interface is more than a size issue: unused openings on flameproof equipment must be closed with certified plugs, and entries must be certified flameproof glands, otherwise the flame path and explosion protection integrity are compromised.

The data in this article was obtained via web search. Source: Honeywell official data sheet 002306 Issue 11 Termination types and electrical ratings tables; subject to the official data sheet.

IV. Installation and Maintenance Requirements

ItemRequirement
Referenced standardsGB 15577, GB/T 3836.13, GB/T 3836.15, GB/T 3836.16, GB 50257 (listed in BX installation instructions)
Flame pathsMax gap at plunger and bearing 0.076 mm, bearing and housing 0.02 mm (cylindrical spigot); keep intact
Cover openingNever open a flameproof enclosure while energized; restore threads and seals after maintenance
Static chargeNon-conducting coating may build ignition-capable static under extreme conditions; avoid high-pressure steam and clean with a damp cloth
Part replacementDo not substitute parts from another switch without consulting Honeywell technical support

The data in this article was obtained via web search. Source: Honeywell official BX installation instructions 50083427 and BX2 installation instructions 50047766, warnings and flame-path tables; installation and maintenance subject to the official manual.

V. Zone and Group Matching Principles

CoordinateBX/BX2 coverageVerification method
ZoneZone 1/2 (Gb) and corresponding dust zones (Db)Check required EPL against the area classification drawing; Zone 0 generally not suitable for flameproof enclosure
Gas groupIIC (covers IIB and IIA)IIC covers IIB/IIA, not vice versa; verify against the medium MSDS
Temperature classT6 (max surface temperature 85 C)T6 covers T1-T5; verify against the medium autoignition temperature
DustEx tb IIIC T85 C Db conductive dust group IIIC, surface temperature 85 C

In Ex db IIC T6 Gb, the three elements IIC, T6 and Gb together define the applicable range: IIC covers lower gas groups, T6 covers lower temperature classes, and Gb applies to Zones 1 and 2. The area classification and medium properties must come from the project classification documents.

The data in this article was obtained via web search. Source: Honeywell official data sheet 002306 Issue 11 Ex marking; area classification per IEC 60079-10-1 (GB/T 3836.14).

VI. Selection Guide and Common Models

Selection guide: First determine the required EPL, gas group (IIA/IIB/IIC) and temperature class (T1-T6) from the area classification (Zone 0/1/2) and medium. Then verify BX/BX2 Ex db IIC T6 Gb / Ex tb IIIC T85 C Db meets them. Then select enclosure material by environment (BX aluminum / BX2 316L stainless steel), conduit entry by wiring (1/2", 3/4" NPT or 20 mm), and seal by temperature (fluorosilicone/fluorocarbon). Ex ia intrinsic safety is NOT Ex d flameproof; where a certificate or combination cannot be confirmed, state "unable to confirm, please verify with the manufacturer".

Common models: BXA3K (BX aluminum side-rotary SPDT, 1/2" NPT), BXAC3K (fully fluorocarbon sealed); the BX2 series uses the 316L stainless-steel housing with interfaces and approvals per the specific ordering code. The final marking and certificates follow the nameplate and original certificate documents.

If you need to verify whether a BX/BX2 explosion marking and conduit interface suit your site area classification, please send us the nameplate data, area classification and medium parameters. We can review the protection level, groups and interface against the official data sheet and certificate requirements.