The TOPWORX DXP is a D-series world-class discrete valve controller for local valve position indication and discrete control of on/off valves. It uses a visual position indicator for local open/closed status and internal cams plus switch assemblies to set the position signals. It accepts up to six mechanical switches, optional pilot valves, spool valves and Cv options, and the DXS stainless-steel version supports SIL-3 partial stroke testing. This article covers the DXP local indication codes, setting points, related coding positions and how it differs from the T-series, based on the official D-series manual. I. Product Positioning
Source: TopWorx official Discrete Valve Controller manual (TOPWORX.pdf), section 1.3 D-series selection and coding tables; subject to the latest official data and nameplate.
II. Local Visual Position Indication Codes
The DXP visual indicator is mechanically linked to the valve stem shaft, converting actuator angular or linear travel into a locally readable open/closed color code. Position 4 changes only the display form, not the switching signal or the protection level. A wrong display code does not affect the position feedback function but affects local reading habits. Source: TopWorx official Discrete Valve Controller manual, section 1.3.2 D-series visual indication device table; subject to the official data sheet. III. Position Setting Points
Switch setting relies on the relative position of internal cams and switch assemblies; the specific cam structure, adjustment tools and torque follow the TopWorx official installation manual and are not invented here. The T-series TwistSet cam is a stepless-adjustment feature; the D-series setting method is different and the two are not interchangeable. Source: TopWorx official Discrete Valve Controller manual and installation instructions; the setting steps are a general engineering workflow, subject to the official manual. IV. D-Series Coding Positions Relevant to Indication and Mounting
Example DXP-0H0GN4B: DXP = D-series tropicalized aluminum; 3rd position 0 = Ex ia IIC T4/T6 intrinsically safe; G = 90 deg green-open/red-close; N = NAMUR 304 shaft; 4 = (2)3/4" NPT plus (2)1/2" NPT conduit entry; B = nitrile O-ring. The leading combination code 0H is not spelled out in the manual and must follow the official ordering code or nameplate. Source: TopWorx official Discrete Valve Controller manual, section 1.3.3 area classification and section 1.3.4 shaft and conduit entry tables; combination codes are not invented. V. Differences: DXP vs TXP/TXS
Key point: choose DXP or TXP/TXS based on mounting, need for a pilot valve, number of sensors and SIL - never based on protection. The protection level is determined by the 3rd-position area classification code. Ex ia intrinsic safety is NOT Ex d flameproof enclosure; their wiring and cover-opening rules differ and they must never be mixed. Source: TopWorx official Discrete Valve Controller manual, D/T-series comparison and protection-misconception correction note; where a certificate cannot be confirmed, verify with the manufacturer. VI. Selection Guide and Common ModelsSelection guide: First decide the series by mounting conditions: bracket mounting, pilot/spool valve/Cv, up to six mechanical switches or SIL-3 ESD (DXS) leads to the D-series; direct mount to ISO/NAMUR, bracket-free and compact leads to the T-series. Then configure position by position: position 3 area classification determines protection (0 IS / 1, C flameproof / 2 non-incendive), position 4 visual display by local reading habit (G/B/Y), position 5 shaft (NAMUR 304 commonly N), position 6 conduit entry by site wiring (E/M/4 etc.), position 7 O-ring by medium and temperature. Never open a flameproof enclosure while energized; where a certificate cannot be confirmed, state "unable to confirm, please verify with the manufacturer". Common models: DXP-0H0GN4B (IS, green-open/red-close, NAMUR shaft, mixed entry), DXP-0H0GNEB (entry E=(2)3/4" NPT), DXP-M21GNEB; the DXS is the 316 stainless-steel SIL-3 version. DXP and TXP/TXS are different platforms and their codes are not interchangeable. If you are specifying local valve position indication for an on/off valve, or are unsure how to combine the DXP display code, shaft type and conduit entry, please send us the actuator interface and site protection requirements. We can review the indication, setting and protection positions against the official coding table. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |