Home » Service & Support » Technical Documentation
TOPWORX TXP / TXS - Model Code Decoding
Release time:2026-11-23 09:02:36 | Views:

TOPWORX is a valve monitoring brand of Emerson Process Management. The TXP and TXS both belong to the T-series compact direct-mount switchbox family: they share the same coding structure and explosion-protection scheme, and differ only in enclosure material. The TXP uses tropicalized aluminum, while the TXS uses 316 stainless steel. This article decodes the TXP/TXS ordering code position by position based on the official discrete valve controller manual, highlighting the rule that the 3rd position (area classification) determines the protection concept.

I. Product Positioning and Series

ItemDescription
BrandTOPWORX (a brand of Emerson Process Management)
SeriesT-series compact direct-mount valve position feedback switches / limit switches: TXP, TXS, TVA
MountingDirect mounting to ISO/NAMUR actuators, no bracket; TwistSet cam for stepless adjustment
EnclosureTXP = tropicalized aluminum; TXS = 316 stainless steel; TVA = engineering resin
ProtectionII2GD, IP66/67, NEMA Type 4X; extreme environments -60 to +80 C
ReferenceTopWorx Discrete Valve Controller manual (TOPWORX.pdf) coding tables

Source: TopWorx official Discrete Valve Controller product manual (TOPWORX.pdf, 32 pages), section 1.4 T-series selection and coding tables; subject to the latest official ordering tool and nameplate.

TOPWORX limit switch / valve position controller
TOPWORX limit switch / valve position controller illustration, not the actual model; parameters subject to the official data sheet

II. T-Series 12-Position Ordering Code Overview

PositionMeaningMain options (extract)
1stModel / enclosureTXP (tropicalized aluminum) / TXS (316 stainless steel) / TVA (engineering resin)
2ndBus / sensorAS, PB, L2, M2/M4, K2, T2, R2/R4, P2, PN/PS, E2, 12, X/H
3rdArea classification (determines Ex)0 IS / C, 1 flameproof / 2 non-incendive / G general purpose / W no approval
4thVisual indicationG 90 deg green-open/red-close, B 90 deg black-open/yellow-close, Y 90 deg yellow-open/black-close, F flat knurled (T-series only)
5thShaftN NAMUR 304 stainless steel / L 1-inch extended linear shaft (TXP/TXS only)
6thConduit entryP=(2)1/2" NPT, M=(2)M20, E=(2)3/4" NPT, 3=(4)M20, 4=(2)3/4"+(2)1/2" NPT
7thO-ringM silicone (T-series)
8th-12thPilot / spool / Cv / manual / certificatee.g. 1=24VDC fail-open/close pilot; N(NEPSI)/R(GOST)/B(InMetro)

The code is a position-by-position combination: the first seven positions define enclosure, sensor, protection, display, shaft, conduit entry and seals; the tail covers pilot valves, pneumatic accessories and certificates. A few combination codes (e.g. 0H, N2) are not spelled out in the manual tables; they are not invented here and must follow the official ordering code or nameplate.

Source: TopWorx official Discrete Valve Controller manual, section 1.4.3 T-series ordering code structure; extract only, full codes subject to the official ordering tool.

III. Position 3 Area Classification and Protection (Red Line)

CodeClassificationProtection type (extract)
0Intrinsically safeEx ia IIC T4 (II2GD, TXP/TXS; requires a certified safety barrier)
CFlameproofEx d IIC (only TXP/TXS without pilot valve)
1FlameproofEx d IIB (TXP/TXS only)
2Non-incendiveEx nA IIC (TXP/TXS only)
GGeneral purposeNEMA Type 4X
WNo approvalPer enclosure category

Ex ia intrinsic safety is NOT Ex d flameproof enclosure. Code 0 is intrinsic safety and requires a certified safety barrier; codes C/1 are flameproof enclosures with different wiring and cover-opening rules. Protection is determined by the 3rd position area classification, not by the T/D series letter or the P/S suffix. Never infer the protection level from the TXP/TXS letter. Where the certificate (ATEX/IECEx/CCC/NEPSI) cannot be confirmed from documentation, state "unable to confirm, please verify with the manufacturer".

Source: TopWorx official Discrete Valve Controller manual, section 1.4.2 T-series protection and protection-rating table and section 1.3.3 area classification table; Ex ia per IEC 60079-11 and Ex d per IEC 60079-1.

IV. Position 2 Sensors/Buses and Switching Capacity

CodeSensor / busCapacity and limits
L2 / L4GO Switch sealed SPDT dry contact (2/4)4A/120VAC, 3A/24VDC, intrinsically safe; L2 only without pilot valve
M2 / M4Mechanical SPDT (2/4)15A/120VAC; area classification cannot be 2
E2 / E4Inductive NAMUR (p+f NJ2+V3-N)8VDC output, per EN 60947-5-6
P2 / R2Proximity switch SPDTP2 max 3A; R2/R4 max 200mA
X / H4-20 mA position transmitter (H with HART)8.5-34VDC; H not available with pilot valve
AS / PB / FFAS-i / Profibus DP / FOUNDATION FieldbusAS cannot be used in area 0; PB requires 1/C/W

Source: TopWorx official Discrete Valve Controller manual, T-series switch/sensor and bus tables; switching capacities are manual extracts, subject to the official data sheet.

V. Decoding Examples from Delivered Units

ModelPosition-by-position decoding (extract)
TXP-M20FLPMTXP tropicalized aluminum; M2 two mechanical SPDT (15A/120VAC); 0 area classification 0, Ex ia IIC T4 IS; F flat knurled indicator; L 1-inch extended linear shaft; P (2)1/2" NPT; M silicone O-ring
TXP-N20GLPM00000N004TXP tropicalized aluminum; 0 Ex ia IIC T4 IS; G 90 deg green-open/red-close; L extended linear shaft; P (2)1/2" NPT; M silicone; tail 00000N004 = pilot/spool/Cv/certificate extension; leading N2 not listed in manual, follow official ordering code
TXS-L2CFLPMTXS 316 stainless steel; L2 two GO Switch sealed SPDT; C area classification C, flameproof Ex d IIC (only without pilot valve); F flat knurled; L extended linear shaft; P (2)1/2" NPT; M silicone
TXS-N20GLPM00000N004TXS 316 stainless steel; other positions identical to TXP-N20GLPM00000N004; 3rd position 0 Ex ia IIC T4 IS; differs from TXP only in enclosure material, same protection level

The only difference between TXP and TXS is the enclosure material (tropicalized aluminum vs 316 stainless steel); the coding structure and protection level are the same. TXP-N20GLPM and TXS-N20GLPM are not different protection levels but different enclosure materials.

Source: TopWorx official product manual coding tables and delivered ordering codes; combination codes not spelled out in the manual (0H, N2) are marked "follow official ordering code / nameplate" and are not invented.

VI. Selection Guide and Common Models

Selection guide: First confirm the mounting method: direct mount to ISO/NAMUR, bracket-free and compact leads to the T-series. Then configure position by position: 2nd sensor/bus, 3rd area classification (protection), 4th display, 5th shaft, 6th conduit entry, 7th O-ring, then pilot valve and certificate positions. Protection is defined only by the 3rd position; Ex ia and Ex d must never be mixed. Observe compatibility limits: L2 only without pilot valve, M2 not for area 2, AS not for area 0. Where a certificate cannot be found, state "unable to confirm, please verify with the manufacturer".

Common models: TXP-M20FLPM, TXP-N20GLPM00000N004, TXS-L2CFLPM (Ex d IIC flameproof), TXS-N20GLPM00000N004; the same platform also includes the TVA engineering-resin type. DXP/DXS belong to the D-series, a different platform whose codes are not interchangeable.

If you have a complete TXP/TXS ordering code and want to verify the protection, sensor and conduit entry position by position, please send it to us. We can review each position, the compatibility limits and the certificate requirements against the official coding table, and help avoid mixing intrinsic safety with flameproof enclosure.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.