The SAMSON 3730 positioner can be ordered with several position feedback and limit switch accessories: the inductive limit switch (SJ2-SN), 4-20 mA position transmitter, split / external position sensor, solenoid valve and forced venting, leakage sensor and digital inputs. These options are distributed over fields P2, P3 and P4-P7, where P4-P7 is a mutually exclusive group allowing only one additional device at a time. Following official data sheets and the ordering bit table, this article sets out the function, electrical data and filling rules of each accessory.

I. Accessory Overview and Fields

AccessoryOrdering fieldFunction
Inductive limit switchP2 (0 none / 1 SJ2-SN)Discrete open/closed feedback to a switching amplifier
Position transmitterP4-P7 exclusive group (P4=1)4-20 mA continuous position feedback
Split position sensorP4-P7 (P5=1 or 2)Position sensing remote from the positioner body
Analog inputP4-P7 (P5=3)Accepts an external analog signal
Leakage sensorP4-P7 (P6=1)Detects stem / packing leakage
Digital inputP4-P7 (P7=2)Accepts a discrete switch signal
Solenoid / forced ventingP3 (0 none / 4 with 24 V DC)Fail-safe quick exhaust or shutdown

Source: SAMSON official data sheets T 8384-3/5 EN, mounting and operating instructions EB 8384-3 EN, master data sheet NA 0122, and the SAMSON smart positioner specification section 3.4 (additional equipment bit table); specific options subject to the official ordering tool.

SAMSON 3730 series smart electropneumatic positioner
SAMSON 3730 series positioner, same-series illustration; parameters subject to the official catalog

II. Position Feedback Options

OptionOutputKey point
Position transmitter4-20 mA continuous signalSet P4=1 in the P4-P7 exclusive group; HART type can superimpose digital data; check load and compliance voltage per catalog
Split position sensorRemote position signalP5=1 (or 2 = pre-connected), requires P2=0 and P10=0 (aluminum housing); cable and mounting per official manual
External position sensor (3730-5)Position signal10 m cable, M12x1 connector, IP67; -60 to +105 C with fixed connection, vibration immunity up to 10 g
FF bus feedback (3730-5)Function block variablesPosition sent over the bus via AI/AO/PID function blocks; Link Master enables autonomous loops

Source: SAMSON official data sheets T 8384-3/5 EN, mounting and operating instructions EB 8384-3 EN, master data sheet NA 0122, and the SAMSON smart positioner specification section 3.4 (additional equipment bit table); specific options subject to the official ordering tool.

Distinguish two kinds of "feedback": continuous 4-20 mA position transmission belongs to the P4-P7 group (P4=1), while a discrete limit switch belongs to P2 (P2=1). Example 3730-3 1001000400000000 is 4-20 mA feedback, while 3730-3 1100000400000000 has a discrete limit switch; the two must not be mixed.

III. Limit Switches and Proximity Detectors

ItemParameter / note
Inductive limit switchSJ2-SN, normally closed (NC) contact, P2=1; connects to a switching amplifier per EN 60947-5-6
Detection currentPlate not detected >=3 mA; plate detected <=1 mA
Binary output (e.g. 3731-3)NAMUR / PLC output as a separate option field
FunctionProvides a discrete signal when the valve reaches the open/closed end for interlocks, feedback and sequencing
Difference from transmitterA limit switch gives only end-point digital states; a position transmitter gives a continuous full-stroke value

Source: SAMSON official data sheets T 8384-3/5 EN, mounting and operating instructions EB 8384-3 EN, master data sheet NA 0122, and the SAMSON smart positioner specification section 3.4 (additional equipment bit table); specific options subject to the official ordering tool.

IV. Solenoid, Leakage Sensor and Digital Input

AccessoryParameter / note
Solenoid valve (P3=4)24 V DC, reverse polarity protection, static destruction limit 40 V; I=(U-5.7 V)/3840 ohm; life >5 x 10^6 cycles; emergency venting at 0 V
Forced ventingFail-safe quick exhaust for SIL applications; per IEC 61508/61511
Leakage sensor (P6=1)Suitable for hazardous areas, temperature -40 to +130 C, tightening torque 20±5 Nm, detects stem packing leakage
Digital input (P7=2)Floating contact, R<100 ohm, contact load 100 mA; the 3730-5 binary input 1 is 0-30 V DC with a 40 V static destruction limit
Analog input (P5=3)Accepts an external analog signal for control or diagnostics

Source: SAMSON official data sheets T 8384-3/5 EN, mounting and operating instructions EB 8384-3 EN, master data sheet NA 0122, and the SAMSON smart positioner specification section 3.4 (additional equipment bit table); specific options subject to the official ordering tool.

For SIL safety applications, emergency venting with an optional solenoid follows IEC 61508 and IEC 61511: a single device with HFT=0 can reach SIL 2, redundant HFT=1 can reach SIL 3. The exact certificate scope and ordering code are subject to official data sheets (T 8384-5 EN, T 8387-3 EN) and the SIL certificate.

V. Filling Rules and Selection Notes

RuleNote
Mutually exclusive groupSelect only one additional device in P4-P7 at a time; do not fill both position transmitter and leakage sensor
PreconditionsA split position sensor (P5=1/2) requires P2=0 and P10=0 (aluminum housing)
Feedback distinctionContinuous 4-20 mA -> P4=1; discrete limit switch -> P2=1; do not mix
Ex linkageWith accessories still check area certification via P1 (or P1+P14-P16); accessories must not reduce Ex integrity
Ex typeEx ia intrinsic safety and Ex d flameproof enclosure must not be mixed; flameproof applications go to the 3731 family
Final confirmationThe full code is subject to the bit result generated by the official ordering tool

Source: SAMSON official data sheets T 8384-3/5 EN, mounting and operating instructions EB 8384-3 EN, master data sheet NA 0122, and the SAMSON smart positioner specification section 3.4 (additional equipment bit table); specific options subject to the official ordering tool.

Selection sequence: first decide whether digital or continuous feedback is needed and choose the corresponding field; add a P3 solenoid for fail-safe venting; add a P6 leakage sensor for condition monitoring; finally check the Ex and housing fields. Where the official catalog gives no value, state "subject to the official catalog / ordering tool" and do not invent.

Selection guide: For 3730 accessories, first distinguish a discrete limit switch (P2=1) from continuous 4-20 mA position transmission (P4=1); the P4-P7 group allows only one at a time; add a P3 solenoid for fail-safe venting and a P6 leakage sensor for condition monitoring, then check the Ex and housing fields.

Common models: Common accessory combinations: SJ2-SN inductive limit switch, 4-20 mA position transmitter, split / external position sensor, 24 V DC solenoid with forced venting, leakage sensor, digital / analog inputs; the flameproof 3731-3 offers a binary output (NAMUR/PLC).

If you are unsure whether the site needs a digital feedback contact or a continuous 4-20 mA valve position, or are concerned about split-sensor preconditions and exclusive-group filling, please send us the feedback method and ordering code. We can check the accessories item by item against the official bit table.