| SAMSON 3730 Series - Communication Protocol Comparison (HART / FF / PROFIBUS-PA) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-23 09:02:36 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The SAMSON 3730 family splits into versions by communication protocol: 3730-0/1/2 have no fieldbus, 3730-3 is HART, 3730-4 is PROFIBUS PA and 3730-5 is FOUNDATION Fieldbus; the pressure-monitoring 3730-6 and flameproof 3731 family are additional branches. The three main protocols differ in physical layer, power supply, data rate and ordering-code identifier field. This article compares them item by item against official data sheets and gives the selection order of communication first, Ex second and additional equipment last. I. Family Version Overview
Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.
II. Three Main Protocols Compared
Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog. Although all three share the 3730 platform (same housing, mounting and pneumatic interfaces), different protocols mean different segment design, power budgeting and configuration tools. HART keeps 4-20 mA as the primary signal and suits retrofit and installed systems; FF/PA are bus powered and require FISCO/FNICO or bus load calculations, suiting new bus projects. III. Ordering Code Structure and Identifier Fields
Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog. Red line: the 3730-4 is PROFIBUS PA and the 3730-6 is a 14-digit special design with pressure monitoring - do not mix them. The 3731 family is flameproof Ex d with a completely different bit table that cannot be copied from the 3730. Although 3730-3/4/5 are all 16 digits, their Ex coding and exclusive options differ, so their bit tables cannot be interchanged either. IV. Ex Protection Types and Flameproof Boundary
Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog. Ex ia intrinsic safety and Ex d flameproof enclosure are different protection types: the former limits energy, the latter relies on a robust enclosure; wiring, cabling and cover-opening rules differ and must never be mixed. The 3730-0 to 5 have no flameproof Ex d body; where flameproof is required, select the 3731 family (or the exclusive Ex d[ja] option on the 3730-6), subject to the certificate and nameplate. V. Selection Notes and Common Models
Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog. Common combinations: 3730-3 (HART, most used), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring), 3731-3/3731-5 (flameproof). The TROVIS 3793 (HART, modular high capacity) and 3797 (PROFINET) are separate models outside the 3730-0 to 5 bit system. Selection guide: The 3730 selection path is communication first, Ex second and options last: HART -> 3730-3, FF -> 3730-5, PA -> 3730-4; Ex by area (Ex ia / Ex nA / dust) with flameproof going to the 3731 family; pressure monitoring to 3730-6. The three main protocols all use 16-digit codes but differ in identifier field and Ex coding, so bit tables cannot be interchanged. Common models: 3730-3 (HART, 16 digits), 3730-4 (PROFIBUS PA, 16 digits, field 4 = 0), 3730-5 (FF, 16 digits, field 4 = 0, four Ex fields), 3730-6 (pressure monitoring, 14 digits), 3731-3 / 3731-5 (flameproof Ex d, 15 digits). If you are unsure whether the site needs HART, FF or PROFIBUS PA, or want to confirm the meaning of field 4 in a 3730 ordering code or whether flameproof requires a 3731, please share the bus parameters and certification requirement. We can check the protocol version and code bit by bit against the official data sheets. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |