SAMSON 3730 Series - Communication Protocol Comparison (HART / FF / PROFIBUS-PA)
Release time:2026-11-23 09:02:36 | Views:

The SAMSON 3730 family splits into versions by communication protocol: 3730-0/1/2 have no fieldbus, 3730-3 is HART, 3730-4 is PROFIBUS PA and 3730-5 is FOUNDATION Fieldbus; the pressure-monitoring 3730-6 and flameproof 3731 family are additional branches. The three main protocols differ in physical layer, power supply, data rate and ordering-code identifier field. This article compares them item by item against official data sheets and gives the selection order of communication first, Ex second and additional equipment last.

I. Family Version Overview

ModelCommunicationKey point
3730-0None (analog 4-20 mA)Low-cost version, DIP switches set travel range
3730-1None (analog 4-20 mA)Non-contact position detection, rotary button, TROVIS-VIEW configuration
3730-2Not listed in official catalogBit positions subject to T 8384-2 / official ordering tool
3730-3HARTIntegrated EXPERTplus, 16-digit code
3730-4PROFIBUS PAIEC 61158-2, Profile Class B v3.0, 16-digit code
3730-5FOUNDATION FieldbusIEC 61158-2, integrated PID function block, 16-digit code
3730-6HART + pressure monitoringSupply/output pressure sensors, 14-digit code, T 8384-6 EN
3731-3HARTFlameproof Ex d housing, 15-digit code, T 8387-3 EN
3731-5FOUNDATION FieldbusFlameproof Ex d housing, bus powered, 15-digit code, T 8387-5 EN

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.

SAMSON 3730 series smart electropneumatic positioner
SAMSON 3730 series positioner, same-series illustration; parameters subject to the official catalog

II. Three Main Protocols Compared

DimensionHART (3730-3)PROFIBUS PA (3730-4)FF (3730-5)
Physical layer4-20 mA analog with HART superimposedIEC 61158-2IEC 61158-2, 31.25 kbit/s H1
PowerTwo-wire loop poweredBus poweredBus powered 9-32 V DC
Data rateHART (order of 1200/9600 bit/s)31.25 kbit/s31.25 kbit/s
Function blocksDevice variables and diagnostics via communicator / AMSPA profile device, configured in control systemPID/DI/DO/AI function blocks, Link Master autonomous loops
Load / currentMax load 410 ohmBus segment power budgetingMax current 15 mA, FISCO/FNICO
Ordering identifier16 digits, no forced bus field16 digits, field 4 forced to 0 (PA identifier)16 digits, field 4 forced to 0 (FF identifier)
Ex codingP1 one field + P15-P16P1 one fieldP1 + P14-P16, four fields
Key data sheetT 8384-3 ENT 8384-4 ENT 8384-5 EN

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.

Although all three share the 3730 platform (same housing, mounting and pneumatic interfaces), different protocols mean different segment design, power budgeting and configuration tools. HART keeps 4-20 mA as the primary signal and suits retrofit and installed systems; FF/PA are bus powered and require FISCO/FNICO or bus load calculations, suiting new bus projects.

III. Ordering Code Structure and Identifier Fields

ModelCode lengthEx fieldSpecial identifierData sheet
3730-316 digitsP1 one field (+P15-P16 special version)No forced bus fieldT 8384-3 EN
3730-416 digitsP1 one fieldField 4 forced to 0 = PROFIBUS PA identifierT 8384-4 EN
3730-516 digitsP1 + P14-P16, four fieldsField 4 forced to 0 = FF identifierT 8384-5 EN
3730-614 digitsP1-P3, three fieldsPressure monitoring; includes Ex d[ja] options (210/211)T 8384-6 EN
3731-315 digitsEx 2 fields + certification 3 fieldsFlameproof Ex d; version digit 1 = 3T 8387-3 EN
3731-515 digitsEx 3 fields + certification 3 fieldsFlameproof Ex d; version digit 1 = 5T 8387-5 EN

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.

Red line: the 3730-4 is PROFIBUS PA and the 3730-6 is a 14-digit special design with pressure monitoring - do not mix them. The 3731 family is flameproof Ex d with a completely different bit table that cannot be copied from the 3730. Although 3730-3/4/5 are all 16 digits, their Ex coding and exclusive options differ, so their bit tables cannot be interchanged either.

IV. Ex Protection Types and Flameproof Boundary

TypeMarkingApplies toNote
Intrinsic safetyEx ia / Ex icMain option for 3730-0 to 5 and 3730-6Energy limited, for Zone 0/1; wiring must match barrier parameters
Non-sparkingEx nA / Ex nLOptions on 3730-3/4/5/6No sparks in normal operation, for Zone 2
Dust protectionEx tb / Ex tcOptions on 3730-3/4/5/6Dust areas, IP66
FlameproofEx d / Ex db3731 family; exclusive 3730-6 options 210/211Robust enclosure withstands internal explosion; never open while energized
Safety versionTROVIS SAFE3730-6 TS / 3731-3 TS / 3793SIS safety applications with partial stroke test (PST)

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.

Ex ia intrinsic safety and Ex d flameproof enclosure are different protection types: the former limits energy, the latter relies on a robust enclosure; wiring, cabling and cover-opening rules differ and must never be mixed. The 3730-0 to 5 have no flameproof Ex d body; where flameproof is required, select the 3731 family (or the exclusive Ex d[ja] option on the 3730-6), subject to the certificate and nameplate.

V. Selection Notes and Common Models

StepKey point
1 Define protocolRetrofit of installed 4-20 mA -> HART (3730-3); new FF bus -> 3730-5; PROFIBUS PA -> 3730-4
2 Define ExChoose Ex ia / Ex nA / dust by area certification; for flameproof go to the 3731 family
3 Define special functionsPressure monitoring -> 3730-6; SIS safety -> 3730-6 TS / 3731-3 TS
4 Define optionsFill limit switch, solenoid, position feedback and leakage sensor in the correct fields
5 Verify the codeRely on official data sheets T 8384-x / T 8387-x and the complete code from the ordering tool

Source: SAMSON official data sheets T 8384-3/4/5/6 EN, T 8387-3/5 EN, T 8493S EN, NA 0122, and the official catalog table of 3730/3731 suffix (-x) versus communication protocol; subject to the latest official catalog.

Common combinations: 3730-3 (HART, most used), 3730-4 (PROFIBUS PA), 3730-5 (FF), 3730-6 (pressure monitoring), 3731-3/3731-5 (flameproof). The TROVIS 3793 (HART, modular high capacity) and 3797 (PROFINET) are separate models outside the 3730-0 to 5 bit system.

Selection guide: The 3730 selection path is communication first, Ex second and options last: HART -> 3730-3, FF -> 3730-5, PA -> 3730-4; Ex by area (Ex ia / Ex nA / dust) with flameproof going to the 3731 family; pressure monitoring to 3730-6. The three main protocols all use 16-digit codes but differ in identifier field and Ex coding, so bit tables cannot be interchanged.

Common models: 3730-3 (HART, 16 digits), 3730-4 (PROFIBUS PA, 16 digits, field 4 = 0), 3730-5 (FF, 16 digits, field 4 = 0, four Ex fields), 3730-6 (pressure monitoring, 14 digits), 3731-3 / 3731-5 (flameproof Ex d, 15 digits).

If you are unsure whether the site needs HART, FF or PROFIBUS PA, or want to confirm the meaning of field 4 in a 3730 ordering code or whether flameproof requires a 3731, please share the bus parameters and certification requirement. We can check the protocol version and code bit by bit against the official data sheets.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.