The SAMSON 3730-5 is the bus-powered smart positioner of the 3730 family with FOUNDATION Fieldbus (FF) communication, based on IEC 61158-2 transmission technology, compliant with the FF specification and able to host an integrated PID function block for closed-loop control in the field. Following official data sheet T 8384-5 EN, this article covers electrical, bus, pneumatic and environmental data and gives the 16-digit ordering code that differs from the 3730-3: a four-digit Ex protection field, a field 4 forced to zero, and a leakage sensor option.
I. Product Positioning
| Item | Description |
| Brand | SAMSON (independent German brand) |
| Series | 3730 family, type 3730-5 (FOUNDATION Fieldbus version) |
| Positioner type | Bus-powered smart electropneumatic positioner, single/double acting |
| Control principle | Analog PD control plus microprocessor with integrated PID function block |
| Communication | FOUNDATION Fieldbus, IEC 61158-2, 31.25 kbit/s, H1 |
| Function blocks | PID, DI, DO, AI (AO/MAO), IS, etc.; Link Master capability for autonomous closed loops |
| Ex protection | Ex ia / Ex nA / dust protection, varying with certification code; the device itself is not flameproof Ex d |
| Key data sheets | T 8384-5 EN, NA 0122 |
Source: SAMSON official data sheet T 8384-5 EN (Type 3730-5 with FOUNDATION fieldbus), NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.3 (bit-by-bit table). Ex marking varies with the certification code; subject to the official ordering tool.

SAMSON 3730 series positioner, same-series illustration, not the actual 3730-5; parameters subject to the official catalog
II. Main Technical Data
| Parameter | Value / note |
| Bus power supply | 9-32 V DC powered over the bus line; Physical Layer Class 113 (non-Ex) / 111 (Ex) |
| Max operating current | 15 mA; additional current in case of error 0 mA |
| Communication standard | FF specification; FF device rev 1/2/3 interoperability tested per ITK 4.6 / 5.2 / 6.2 |
| Baud rate | 31.25 kbit/s, twisted pair physical layer, H1 compliant |
| Supply air | 1.4-7 bar (20-105 psi); air quality ISO 8573-1 particles class 4 / oil class 3 / humidity class 3 |
| Rated travel | Direct on 3277: 3.6-30 mm; NAMUR IEC 60534-6 / VDI-VDE 3847: 3.6-300 mm; rotary 24 deg to 100 deg |
| Characteristic / deviation | Linear / equal percentage / reverse equal percentage / user-defined; deviation <=1% |
| Hysteresis / sensitivity | <=0.3% / <=0.1%; direction of action reversible |
| Air consumption | Independent of supply air, < 110 l/h |
| Output capacity (fill) | Delta p = 6 bar: 8.5 m3/h; Delta p = 1.4 bar: 3.0 m3/h; Kvmax = 0.09 |
| Output capacity (vent) | Delta p = 6 bar: 14.0 m3/h; Delta p = 1.4 bar: 4.5 m3/h; Kvmax = 0.15 |
| Ambient temperature | -20 to +80 C (all versions); low-temperature special version -45 to +80 C with metal cable gland |
| Degree of protection | IP66 / NEMA 4X |
| Electrical connection | One M20x1.5 gland (6-12 mm), second M20x1.5 thread; terminals 0.2-2.5 mm2 |
| Housing material | Die-cast aluminum EN AC-AlSi12(Fe), chromated and powder coated; special version stainless 1.4581; external parts 1.4404/316L |
| Weight | Approx. 1.0 kg; stainless special version approx. 2.2 kg |
Source: SAMSON official data sheet T 8384-5 EN (Type 3730-5 with FOUNDATION fieldbus), NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.3 (bit-by-bit table). Ex marking varies with the certification code; subject to the official ordering tool.
III. Function Blocks and Options
| Item | Description |
| Function block execution | FF rev 2: PID 20 ms, DI 20 ms, AO 30 ms, MAI 50 ms; rev 3: AO 30 ms, DI 20 ms, PID 40 ms |
| Local / software interface | SAMSON SSP interface plus serial adapter; TROVIS-VIEW requires the 3730-5 database module |
| Binary input 1 | 0-30 V DC, reverse polarity protection, static destruction limit 40 V, 3.5 mA at 24 V; signal 1 >5 V, 0 <3 V |
| Binary input 2 | Floating contact, R<100 ohm, contact load 100 mA, static destruction limit 20 V / 5.8 mA |
| Solenoid valve | 24 V DC, static destruction limit 40 V, I=(U-5.7 V)/3840 ohm; life >5 x 10^6 cycles; emergency venting at 0 V |
| Leakage sensor | Suitable for hazardous areas, temperature -40 to +130 C, tightening torque 20±5 Nm |
| SJ2-SN proximity switch | For connection to a switching amplifier per EN 60947-5-6; plate not detected >=3 mA, detected <=1 mA |
| External position sensor | 10 m cable, M12x1 connector, IP67; -60 to +105 C with fixed connection, vibration immunity up to 10 g |
| Functional safety | Per IEC 61508/61511, SIL 2 (single device HFT=0), SIL 3 (redundant HFT=1) |
Source: SAMSON official data sheet T 8384-5 EN (Type 3730-5 with FOUNDATION fieldbus), NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.3 (bit-by-bit table). Ex marking varies with the certification code; subject to the official ordering tool.
IV. 16-Digit Ordering Code, Bit by Bit
| Field | Option | Code | Meaning |
| P1+P14-P16 | Explosion protection (4 fields) | 0000 / 1000 / 5000 / 8000 / 1012 / 8013 / 1009 / 8010 / 3000 / 1014 / 1029 | 0000 none; 1000 ATEX Ex ia; 5000 ATEX Ex tb; 8000 ATEX Ex nA + Ex tc; 1012 IECEx Ex ia; 8013 IECEx Ex nA + Ex tc; 1009 CCC Ex ia; 8010 CCC Ex ic / Ex nA; 3000 CSA Ex ia; 1014 EAC Ex ia; 1029 KCS Ex ia |
| Field 4 | FF bus identifier | 0 (forced) | Field 4 is forced to 0 as the FOUNDATION Fieldbus identifier; no other value allowed |
| P2 | Inductive position switch | 0 / 1 | 0 none; 1 SJ2-SN (NC contact) |
| P3 | Solenoid valve | 0 / 4 | 0 none; 4 with 24 V DC |
| P5 | Split position sensor | 0 / 0100 | 0 none; 0100 with sensor |
| P6 | Leakage sensor | 0 / 1 | 0 none; 1 with sensor |
| P7 | Digital input | 0 / 01 | 0 none; 01 floating contact |
| P8 | Self-diagnostics | 4 | EXPERTplus |
| P10 | Housing material | 0 / 01 | 0 aluminum (standard); 01 stainless steel 1.4408 |
| P13 | Special application | 0 / 1 / 2 / 6 / 7 | None / same paint color as device / exhaust port with 1/4-18 NPT thread and rear seal / connection per VDI-VDE 3847 / interface prepared per VDI-VDE 3847 |
| P? | Special version | 000 | None (subject to the official ordering tool) |
Source: SAMSON official data sheet T 8384-5 EN (Type 3730-5 with FOUNDATION fieldbus), NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.3 (bit-by-bit table). Ex marking varies with the certification code; subject to the official ordering tool.
Key differences from the 3730-3: the 3730-5 has a four-digit Ex protection field (P1 plus P14-P16) while the 3730-3 has only P1; both families force field 4 to 0, but with different meanings - for the 3730-4, field 4 = 0 is the PROFIBUS PA identifier, for the 3730-5 it is the FF identifier. The 3730-5 includes a leakage sensor option (P6=1); the 3730-3 puts the leakage sensor inside the P6=1 mutually exclusive group. The full code is subject to the 16-digit result from the official ordering tool.
V. Selection Notes and Common Models
| Point | Note |
| Define communication first | Fieldbus FF -> 3730-5; HART -> 3730-3; PROFIBUS PA -> 3730-4 |
| Bus power | The 3730-5 is bus powered (9-32 V); check segment current (max 15 mA) and FISCO/FNICO entity parameters |
| Check Ex | Fill the four fields P1+P14-P16 by certification code; exact Ex marking varies, so check the certification field of the full order number |
| When flameproof is required | Switch to 3731-5 (FF, Ex d flameproof, 15-digit code, T 8387-5 EN); do not promise Ex d on a 3730-5 |
| Feedback and diagnostics | Select P2 limit switch, P5 split sensor, P6 leakage sensor and P8 EXPERTplus as needed |
| Alarms and status | The FF device provides status and alarms per the FF specification and NAMUR NE 107; configure in the DCS / asset management system |
Source: SAMSON official data sheet T 8384-5 EN (Type 3730-5 with FOUNDATION fieldbus), NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.3 (bit-by-bit table). Ex marking varies with the certification code; subject to the official ordering tool.
Red line: Ex ia intrinsic safety is not Ex d flameproof enclosure and the two must not be mixed; the 3730-5 is intrinsically safe / non-sparking, and flameproof applications go to the 3731-5. Field 4 is forced to 0 and must not be filled with another communication code. Where the official catalog gives no value, state "subject to the official catalog / ordering tool".
Selection guide: Selection sequence for 3730-5: fix FF fieldbus and bus power first, then fill the four Ex fields P1+P14-P16 by certification (field 4 forced to 0), then select limit switch, split sensor, leakage sensor and diagnostics as needed, and finally rely on the 16-digit code from the official ordering tool. Flameproof applications go to the 3731-5.
Common models: Common configurations are FF bus powered, ATEX/IECEx/CCC Ex ia or Ex nA, with EXPERTplus, optional position transmission / leakage sensor and aluminum or stainless housing; flameproof FF goes to 3731-5, HART to 3730-3 and PROFIBUS PA to 3730-4.
If you are selecting a positioner for an FF segment, or are unsure how to fill the four-digit Ex code, the bus power current or the leakage sensor option on a 3730-5, please share the segment parameters and certification requirement. We can check the ordering code bit by bit against the official table.
Orders & Inquiries
Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.